D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
5–1
D485 Modbus to DeviceNet
Converter
Chapter 5: Communication model
GE
Grid Solutions
Communication model
Introduction
DESCRIPTION
In master mode, the D485 is configured to run as a master on the Modbus sub-network,
using a scan-list for communication with the Modbus slave devices. The scan-list is
created using EnerVista P485/D485 Setup and can consist of multiple nodes with multiple
transactions.
Communications between the D485 and the sub-net nodes (Modbus slaves) is based on
transactions with a query/response architecture. The D485 sends out a query on the
Modbus sub-network, and the addressed node is expected to send a response to this
query. Slave nodes are not allowed to respond without first receiving a query.
An exception to this is broadcaster functionality. Most protocols offer some way of
accessing all network nodes. In the D485, this is called a ‘broadcaster’. The broadcaster
can transmit messages to all nodes on the sub-network without expecting a response.
In Modbus, it is possible to broadcast a message to all nodes by sending a message to
node address 0. The Modbus slaves will receive the message, but not Respond to it.
Figure 5-1: Master mode overview
Node 1
(Modbus Slave)
Node 2
(Modbus Slave)
Query
Query
Query
Response
Response
Response
Modbus devices
PLC
Fieldbus Master
Broadcast
D485
Fieldbus slave
and
Modbus master
Содержание D485
Страница 32: ...3 14 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE DATA EXCHANGE ...
Страница 46: ...4 14 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE SOFTWARE OVERVIEW ...
Страница 52: ...5 6 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE COMMUNICATION MODEL ...
Страница 92: ...9 20 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE APPLICATION EXAMPLE ...
Страница 94: ...10 2 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE MISCELLANEOUS ...