D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
INSTALLATION
CONFIGURATION
SWITCHES
The configuration switches are used to set the DeviceNet MAC ID and baud rate settings.
Normally, these switches are covered by a plastic hatch. Note that the node address can
not be changed during runtime, i.e. the D485 requires a reset for any changes to have
effect. Recycle the power supply to reset the module.
Figure 2-10: D485 configuration switches
Table 2–5: D485 status indicators
Number
Description
State
Status
1
Network status Off
Not powered / not online
Green
Link OK, online, connected
Green flashing
Online, not connected
Red
Critical link failure
Red flashing
Connection timeout
2
Module status
Off
No power to device
Green
Device operational
Green flashing
Data size larger than configured
Red
Unrecoverable fault
Red flashing
Minor fault
3
Not used
-
-
4
Not used
-
-
5
Modbus
status *
Off
Power off
Green, flashing
Initializing and not running
Green
Running
Red
Stopped or subnet error, or timeout
6
Device status
Off
Power off
Red/green
alternating
Invalid or missing configuration
Green
Initializing
Green flashing
Running
Red flashing
If the device status LED is flashing in a
sequence starting with one or more red
flashes, note the sequence pattern and
contact GE Multilin
* This LED turns green when all transactions have been active at least once. This includes any
transactions using “change of state” or “change of state on trigger”. If a timeout occurs on a
transaction, this LED will turn red.
8
7
6
5
4
3
2
1
Содержание D485
Страница 32: ...3 14 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE DATA EXCHANGE ...
Страница 46: ...4 14 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE SOFTWARE OVERVIEW ...
Страница 52: ...5 6 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE COMMUNICATION MODEL ...
Страница 92: ...9 20 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE APPLICATION EXAMPLE ...
Страница 94: ...10 2 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE MISCELLANEOUS ...