DATA EXCHANGE
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
3–9
Table 3–13: Attributes for instance 2 for connection object 05h
Attr.
Access
Name
Type
Value
Description
1
Get
State
USINT
N/A
0 = Non existent
1 = Configuring
3 = Established
4 = Timeout
2
Get
Instance type
USINT
0
I/O connection
Table 3–14: Attributes for instance 3 for connection object 05h
Attr.
Access
Name
Type
Value
Description
1
Get
State
USINT
N/A
0 = Non existent
1 = Configuring
3 = Established
4 = Timeout
2
Get
Instance type
USINT
0
I/O connection
Table 3–15: Attributes for instance 4 for connection object 05h
Attr.
Access
Name
Type
Value
Description
1
Get
State
USINT
N/A
0 = Non existent
1 = Configuring
3 = Established
4 = Timeout
2
Get
Instance type
USINT
0
I/O connection
3
Get
Transport class
trigger
BYTE
N/A
Defines the behavior of the
connection
4
Get
Produced
connection ID
UINT
N/A
CAN ID for transmission
5
Get
Consumed
connection ID
UINT
N/A
CAN ID for reception
6
Get
Initial
communication
characteristics
BYTE
0Fh (no ACK) Produces over message group 1.
Does not consume.
01h (ACK)
Produces over message group 1.
Consumes over message group
2.
7
Get
Produced
connection size
UINT
N/A
Number of bytes transmitted
across this connection
8
Get
Consumed
connection size
UINT
0
Number of bytes received across
this connection
9
Get/Set Expected packet
rate
UINT
0
Timing associated with this
connection
12
Get
Watchdog
timeout action
USINT
N/A
0 = Transition to the timed
out state
1 = Auto delete
2 = Auto reset
3 = Deferred delete
13
Get
Produced
connection path
length
UINT
0006h
Number of bytes in the produced
connection path attribute
14
Get
Produced
connection path
EPATH
20 04 24 66
30 03h
Application object producing
data on this connection
15
Get
Consumed
connection path
length
UINT
0004h
Number of bytes in the
consumed connection path
length attribute
16
Get
Consumed
connection path
EPATH
20 2B 24
01h
Specifies the application object(s)
that are to receive the data
consumed by this connection
object
Содержание D485
Страница 32: ...3 14 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE DATA EXCHANGE ...
Страница 46: ...4 14 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE SOFTWARE OVERVIEW ...
Страница 52: ...5 6 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE COMMUNICATION MODEL ...
Страница 92: ...9 20 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE APPLICATION EXAMPLE ...
Страница 94: ...10 2 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE MISCELLANEOUS ...