GE
Energy
D400 Substation Data Manager User's Manual
41
3.10
Redundant Twisted-Pair Et COM2 Port Adapter
The Redundant TP Et COM2 Port card (GE Part No. 520-0218) provides two local
area network connections with unique MAC addresses through Ethernet RJ-45
connectors. The
LAN
input routes to a three-port Ethernet switch and the
WAN
input
routes to the PC/104-Plus Ethernet Module. The Ethernet switch can support a dual-
redundancy network option on the D400. The card also provides an RS-232 DCE
connection through a DB-9 connector. The Redundant TP Et COM2 Port card can
only be installed in the NET1 slot (slot 11) on the D400.
Note:
Use of the Redundant TP Et COM2 Port card requires the installation of the
Dual Redundant Ethernet D400 CPU option, which includes the PC/104-Plus 10/100BaseT
Ethernet module (GE Part No. 580-2717). The COM2 Port requires an external modem to
provide dial-up functionality.
See sections “4.7 Network Connections” and “4.8 Modem Connections” for typical cable
connections.
Configuration Options
There are no selectable options on the Redundant TP Et COM2 Port card.
Redundant TP Et COM2 Port Adapter Card