![GE D400 Substation Data Manager Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/ge/d400-substation-data-manager/d400-substation-data-manager_user-manual_4113027017.webp)
GE
Energy
D400 Substation Data Manager User's Manual
17
Electrical
AC-DC
100-240 VAC (±10 %) 127 VA maximum
100-300 VDC (±10 %) 135 W maximum
Rated power supplies
DC-DC
20-55 VDC (±10 %) 135 W maximum
AC-DC
26.5 A
peak
(< 145 VAC / 205 VDC)
AC-DC
40 A
peak
(< 264 VAC / 370 VDC)
Peak inrush current at
25 °C on cold start
DC-DC
35 A
peak
(< 60 VDC)
Rated frequency (AC-DC)
47 to 63 Hz (50/60 Hz)
Contact closures
Solid-state photo-MOS device
Output ratings at maximum ambient temperature:
– Continuous current: 0.1 A continuous at 300 VAC / 300 VDC
– Peak current: 0.28 A peak for 10 ms
– Maximum on resistance: 35 ohm
Physical
Overall height
2U (3.47”) [88.12 mm]
Width
19” rack mount [482.59 mm]
Depth
12.24” [310.95 mm] for chassis and rear connectors
13.04” [331.34 mm] with front clearance for protruding parts
11
.18
" [
28
4.0
5 m
m]
19"
rac
k m
oun
t [4
82.5
9 m
m]
2U
[3.4
7"
/8
8.1
2
mm
]