GE Multilin
D30 Line Distance Protection System
6-17
6 ACTUAL VALUES
6.3 METERING
6
The metered values for real, reactive, and apparent power, as well as power factor, are displayed in this menu. The "SRC
1" text is replaced by whatever name was programmed by the user for the associated source (see
SETTINGS
SYSTEM
SETUP
SIGNAL SOURCES
).
When VTs are configured in wye, the D30 calculates power in each phase and three-phase power is measured as
S = V
A
x Î
A
+ V
B
x Î
B
+ V
C
x Î
C
(EQ 6.1)
When VTs are configured in delta, the D30 does not calculate power in each phase and three-phase power is measured as
S = V
AB
x Î
A
+ V
CB
x Î
C
(EQ 6.2)
where
S is the apparent power
V
A
, V
B
, V
C
, I
A
, I
B
, I
C
are phase voltage and phase current phasors
V
AB
and V
CB
are phase-to-phase voltage phasors
Î is the conjugate of I
g) FREQUENCY METERING
PATH: ACTUAL VALUES
METERING
SOURCE SRC 1
FREQUENCY
The metered frequency values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was pro-
grammed by the user for the associated source (see
SETTINGS
SYSTEM SETUP
SIGNAL SOURCES
).
SOURCE FREQUENCY
is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the
SYSTEM SETUP
POWER SYSTEM
settings). The signal used for frequency estimation is low-pass filtered. The
final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.
6.3.3 SYNCHROCHECK
PATH: ACTUAL VALUES
METERING
SYNCHROCHECK
SYNCHROCHECK 1(4)
If a synchrocheck function setting is "Disabled", the corresponding actual values menu item is not displayed.
MESSAGE
SRC 1 POWER FACTOR
φ
a: 1.000
MESSAGE
SRC 1 POWER FACTOR
φ
b: 1.000
MESSAGE
SRC 1 POWER FACTOR
φ
c: 1.000
FREQUENCY
SRC 1
SRC 1 FREQUENCY:
0.00 Hz
SYNCHROCHECK 1
SYNCHROCHECK 1 DELTA
VOLT: 0.000
V
MESSAGE
SYNCHROCHECK 1 DELTA
PHASE: 0.0°
MESSAGE
SYNCHROCHECK 1 DELTA
FREQ: 0.00
Hz
Содержание D30D00HCHF8AH6AM6BP8BX7A
Страница 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Страница 52: ...2 22 D30 Line Distance Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 96: ...3 44 D30 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 126: ...4 30 D30 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Страница 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Страница 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Страница 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Страница 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Страница 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Страница 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Страница 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Страница 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Страница 646: ...x D30 Line Distance Protection System GE Multilin INDEX...