Attach mounting bracket to ceiling
support structure either directly or
using a GE suspension kit according
to the suspension kit instructions
(see page 2). Maximum distance
between suspension points shall not
exceed the length of the luminaire.
Choose suspension method
Carefully unpack unit and inspect for
defects before installing. Wear work
gloves to prevent dirt and oil from
being transferred to the luminaire.
NOTE:
When installing luminaires use
clean gloves in order to avoid fouling
the reflective surface.
1
2
Installation of an Independent Unit (IS1)
IMPORTANT - Maximum Length of Electrical Run
IS of First Generation
IS of Second Generation
Lumen Code
LumenCode
[42] [84]
[52][A0]
[65] [85]
[A1][A2]
Voltage
[A3][A7]
[B1][B4]
120V
192’
160’
80’
60’
277V or347V
400’
320’
188’
132’
Voltage
A E,G,S or J
B,F or K
M,N,P or R
U,V,W or X
120V
192’
160’
80’
60’
277V or 347V
400’
320’
188’
132’
• Please see technical data sheet for electrical properties
to ensure safe installation.
• Under any circumstance, maximum driver current
through connected fixtures shall not exceed 15A for
types A, G, J, B, F, K, or E.
• Maximum drive current through connected fixtures shall
not exceed 12A for types M, N, P, R.
• Maximum driver current through connected fixtures shall
not exceed 15A for lumen codes [42], [52], [84], or [A0].
• Maxiumum driver current through connected fixtures shall
not exceed 12A for lumen codes [65], [85], [A3], [A7], [A1],
[A2], [B1] or[B4].
Remove package with smaller label. This label
is to be used for customer floor plan or records.
Daintree Node identification label installed
on luminaire back reflector.
1
2
3
IS series luminaires come in two versions: continuous units (ISC series) and independent units (IS1 series). A continuous electrical run
will consist of a number of continuous units up to a maximum current specified above. When installing luminaires use clean gloves
in order to avoid fouling the reflective surface. To insure a clean fixture, install the fixture with the plastic bag around the fixture, and
then remove plastic bag upon completion of any and all construction related activity.
If two additional circuits are included in luminaire, they must be connected in daisy chain to the same
circuit breaker as per diagram below and total current not exceeding a maximum of 15A or 12A (per
above comment).
Daintree Node
Identiftcation Label
1
Breaker
Circuit #1
Circuit #2