Planning the Installation

3

UL 1635 Digital Alarm Communicator System

Note  

For UL 1635 installations, 
Entry Delay plus Dialer 
Abort Delay must not 
exceed 60 seconds.

Same as UL 1023 & 985 plus:

AC FAILURE set to on

PHONE NUMBER must be programmed

HIGH LEVEL REPORTS set to on.

LOW LEVEL REPORTS set to on

PHONE TEST set to on

AUTO PHONE TEST set to on

PHONE TEST FREQ. set to 1

NEXT PHONE TEST set to 1

LOW CPU BATTERY set to on

COMM FAILURE set to on

RF TX TIMEOUT set to 4 hours

Central Station Reporting

The panel has been tested with the following central station receivers using SIA and Contact ID 
reporting formats:

ITI CS-5000 Central Station Receiver

Sur-Gard Central Station Receiver with models SG-DRL2A and SG-CPM2

UL-Canada Listed Systems

This section describes the requirements for ULC (UL Canada) Listed systems.

CSA Certified Accessories
The UL-Canada Basic System is nearly the same as the “UL Basic System” described previ-
ously, the only difference being that you must use the ITI 60-679-CN Class II transformer 
(Basler part number BE 116250-AAA) to power the panel.

Residential Burglary Alarm System Unit
(CAN/ULC-S309)
Same as “UL Basic System and Household Burglary Alarm System Unit (UL 1023)” 
described previously and siren timeout must be set to 5 minutes or more.

Residential Fire Warning System Control Unit (CAN/ULC-S545-M89)

Same as “UL Basic System and Household Fire Warning System (UL 985)” described previ-
ously.

Note  

For 24-hour backup, exter-
nal power drain is limited to 
90 mA continuous using a 
4.0AH battery.

California State Fire Marshall Listed Systems

Same as 

Household Fire Warning System (UL 985)

, plus:

SMOKE VERIFY must be set to off

Planning the 
Installation

This section describes the system capabilities to help you get familiar with the system. To help 
you prepare for system installation, Appendix A provides planning sheets with tables that let you 
record the hardware and programming configuration of the system.

Standard Panel

The following describes the basic panel (out-of-box) hardware capabilities.

Power:

 Input for an AC step-down, plug-in style transformer.

Auxiliary Power Output:

 Output that supplies up to 750 mA (90 mA for UL Listed systems) 

at 12 VDC for bus devices and hardwired detectors, such as touchpads and motion detectors.

Cancel Report Annunciation

Enabled

Function

Operation

Содержание Concord express

Страница 1: ...g h d e l a y d o o r 2 3 1 P r e s s 2 C O D E C l o s e a l l p r o t e c t e d d o o r s a n d w i n d o w s P r e s s 4 t o a r m d e l a y d o o r s i n s t a n t l y A r m t o A W A Y Z o n e S e n s o r N u m b e r P r e s s 1 C O D E 2 1 P r e s s A o r B t o s c r o l l t h r o u g h m e n u s M a k e s u r e s y s t e m i s d i s a r m e d 2 1 P r e s s 7 1 t o t u r n C H I M E o n o r ...

Страница 2: ...ompliant See the Installation Instructions for details Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation It must be able to do this even if other equipment telephone answering system computer modem etc already has the telephone line in use To do so alarm dialing equipment must be connected to a properly installed RJ31X jack that is electric...

Страница 3: ...ion Le matériel doit également etre installé en suivant une méthod acceptée de raccordement Dans certains cas les fils intérieurs de l enterprise utilisés pour un service individuel a ligne unique peuvent etre prolongés au moyen d un dispositif homologué de raccordement cordon prolongateur téléphonique interne L abonné ne doit pas oublier qu il est possible que la conformité aux conditions énoncée...

Страница 4: ...s 12 Connecting Siren Drivers Self Contained Sirens and Bells 13 Connecting Touchpads 14 Installing an RJ 31X Phone Jack 13 081 14 Connecting the Phone Line to the Panel with a DB 8 Cord 15 Connecting the AC Power Transformer 16 Powering Up the Panel 16 Programming the Panel 17 Entering Programming Mode 17 Touchpad Button Programming Functions 18 Moving Through Program Mode Tiers and Menus 18 Prog...

Страница 5: ...play LCD Touchpad Chime and Trouble Beep Tones 49 Troubleshooting 50 Appendix A System Configuration Worksheets 54 Cross Zoning 57 Appendix B Programming Mode Menus and Settings 66 Specifications 68 Wiring Diagram Back Page ...

Страница 6: ...ry 12 VDC 4 AH 60 681 SuperBus 2000 2x16 LCD Touchpad 60 746 01 SuperBus 2000 Fixed Display Touchpad 60 820 SuperBus 2000 2x20 LCD Touchpad 60 803 or SuperBus 2000 2x20 VFD Touchpad 60 804 Standard Class II 16 5 VAC 25 VA Power Transformer manufacturer Tech Elec tro Ind Inc Part No 48A0164 60 822 15 Watt Dual Tone Siren 13 469 or Hardwire Siren 13 046 Household Burglary Alarm System Unit UL 1023 B...

Страница 7: ...nts The following table describes programming requirements to meet ANSI SIA CP 01 The following table describes non programmable hard coded system operation as required to meet ANSI SIA CP 01 and is provided only for your reference Shortcut Function Programming Page Reference Testing Page Reference Default Setting Required Setting 0003 SIA False Alarm Reduction 21 46 On On 0013 Exit Extension 22 4...

Страница 8: ... to power the panel Residential Burglary Alarm System Unit CAN ULC S309 Same as UL Basic System and Household Burglary Alarm System Unit UL 1023 described previously and siren timeout must be set to 5 minutes or more Residential Fire Warning System Control Unit CAN ULC S545 M89 Same as UL Basic System and Household Fire Warning System UL 985 described previ ously Note For 24 hour backup exter nal ...

Страница 9: ... not installer or dealer programming Displays system messages and indi cates system status SnapCard The following SnapCards expand the system as described 8Z Input SnapCard Provides eight additional hardwire zone inputs of which two are dedi cated for 2 wire smoke detectors 4 Output SnapCard Provides four form C relay outputs that can be set up to activate other signalling devices based on system ...

Страница 10: ...r by a nonconductive barrier OR B Class 2 Class 3 and power limited fire alarm cir cuit conductors must be installed as Class 1 or higher circuits Table 1 describes panel voltage current output ranges See Appendix A for maximum and standby device current draw Total system wire allowed varies depending on devices powered by the panel wire length between devices and the panel and the combined wire l...

Страница 11: ...nting Holes 5 Install anchors where studs are not present 6 Partially insert screws into the two top mounting hole locations then hang the panel on the two screws 7 Recheck for levelness insert the two lower screws and tighten all four mounting screws 2 Wire Smoke Detectors 22 AWG 330 ft 18 AWG 830 ft based on 10 ohms maximum loop resistance 2k end of line Stranded Sirens 22 AWG 80 ft 18 AWG 200 f...

Страница 12: ...ces and making wiring connections familiarize yourself with the main components of the panel Figure 4 shows the main component locations on the circuit board Figure 4 Main Component Locations Connecting the Panel to Earth Ground For maximum protection from lightning strikes and transients connect the lower right circuit board screw to earth ground as shown in Figure Use 16 gauge solid copper wire ...

Страница 13: ...place with two screws included with the card Figure 6 Connect all necessary input output wiring using the installation instructions included with the SnapCard Figure 6 Installing a SnapCard Note Use of the HIM with the Concord Express panel has not been investigated by UL Installing Optional Hardwire Input Modules HIMs Each SuperBus 2000 8 Zone Input Module 60 774 adds eight supervised hardwire zo...

Страница 14: ...n Devices Figure 8 shows the typical wiring for N C and N O door window intrusion detection Figure 8 Connecting N C and N O Intrusion Detection Circuits Figure 9 shows the typical wiring for Optex model RX 040 PI PIR motion detectors The mini mum available panel voltage for hardwired PIR motion detectors is 8 5 VDC 9 1 VDC for UL Listed systems 8642137A DSF 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 ...

Страница 15: ...et up for 2 wire smoke detectors zone 6 can handle up to 10 smoke detectors with 120 µA maximum idle current per detector Maximum total loop current allowed in an alarm condi tion is 80 mA The maximum loop resistance for 2 wire smoke detectors connected to zone input 6 is 10 ohms plus the 2k end of line resistor Connect one or more 2 wire smoke detectors to the panel as shown in Figure 10 1 2 1 3 ...

Страница 16: ...o 01500 For more information on output configuration numbers see the section Programming the Panel and the tables in Appendix A Use only 4 wire smoke detectors that operate on 8 5 to 14 2 VDC Note The Two Wire Smoke set ting in program mode must be off when connecting 4 wire smoke detectors to zone 6 For UL Listed systems 4 wire smoke detectors can not be connected to onboard panel zone inputs Con...

Страница 17: ...l terminal 7 OUT1 12V is a 12V programmable output At the default configuration setting 00410 this output can provide up to 1 25 A during an alarm 650 mA for UL Listed systems if the backup battery is connected The default configuration setting 00410 activates the output during any audible alarm allow ing for a siren connection without changing the output configuration number Note For UL Listed sy...

Страница 18: ...nstead of panel ter minal 4 the supply voltage must be limited to 9 5 VDC maximum and the negative side of the power supply must be connected to panel ground terminal 3 Figure 14 Connecting an Interior Piezo Siren Connecting Siren Drivers Self Contained Sirens and Bells Power for a siren driver self contained siren or bell can be connected to panel terminals 7 OUT1 12V and 3 GND Panel terminal 7 O...

Страница 19: ... PBX phone line These systems are designed only for digital type devices that operate any where from 5 volts DC and up The panel uses an ana log modem and does not have a digital converter adapter or interface to oper ate with such systems Installing an RJ 31X Phone Jack 13 081 Use the following guidelines when installing an RJ 31X phone jack for system control by phone and central station monitor...

Страница 20: ...ke corrections where neces sary Proceed to the Troubleshooting section of this manual if problems persist Connecting the Phone Line to the Panel with a DB 8 Cord After installing the RJ 31X jack you are ready to connect the phone line to the panel A DB 8 cord not included uses a plug at one end for connecting to the RJ 31X module and flying leads on the other end for panel terminal connections To ...

Страница 21: ...f steps described in the following section Power Up the Panel Figure 18 Connecting the Power Transformer Powering Up the Panel Note Without AC power shut down will occur if battery voltage falls below 10 2 VDC After installing SnapCards and wiring all devices to the panel you are ready to apply AC and backup battery power to the panel To power up the panel 1 Connect the red and black battery leads...

Страница 22: ... dealer code default 4321 The system can be put into program mode only when it is disarmed To enter programming mode using an alphanumeric touchpad connected to the panel terminals 1 Make sure the system is disarmed 2 Press 8 CODE 0 0 The touchpad shows SYSTEM PROGRAMMING Note If the programming touchpad is connected before the panel is powered up it will be added learned into panel memory as a pe...

Страница 23: ...pertain to that menu Only when a specific menu is displayed can you advance to those settings For example pressing ƒ from the SENSORS menu gives you access to learning sensors programming sensor text deleting sensors and viewing sensor programming Table 3 Alphanumeric Touchpad Buttons Button Programming Function ƒ Selects menu item or data entry Deselects menu item or data entry if pressed before ...

Страница 24: ...Zone 4 hardwire Group 01 Panic Zone 5 wireless Group 01 Keychain Touchpad Zone 6 wireless Group 13 Kitchen Window COMM FAILURE off Entry Delay 8 seconds Exit Delay 8 seconds Extended Delay 1 minute Siren Timeout 2 minutes Status Beeps on all touchpads Central Station Reporting sensors learned into groups 01 and 03 Duress code use and phone test 8 CODE 2 To turn Demo Kit Mode On or Off 1 With the d...

Страница 25: ...ode 0000 Security Global Default 12345 The 5 digit downloader code is used in conjunction with downloader pro gramming The down loader operator must have the panel account number and downloader code in order to perform any programming Note The Downloader Code cannot be deleted from panel memory To change the Downloader Code to its default setting enter 12345 in the procedure to the right The Downl...

Страница 26: ...s Silent feature is disabled for users if this setting is on OR can be controlled by users if the setting is off Silent Arming on Demand is not affected To turn SIA False Alarm Reduction off or on 1 With the display showing SIA FALSE ALARM current setting press 1 off or 2 on The display flashes the entered setting 2 Press ƒ and the display shows the new set ting Account Number 0010 Security Partit...

Страница 27: ...remises for a forgotten item When Exit Extension is on the panel restarts the exit delay timer if the user reenters the premises through a designated delay door before the exit delay time expires When Exit Extension is off the exit delay timer does not restart if the user reenters the premises This forces the user to disarm the system to avoid set ting off an alarm To turn Exit Extension off or on...

Страница 28: ...lts in false alarms due to code entry errors If a duress code is absolutely necessary use it with an Interrogator audio verification mod ule AVM to reduce false alarms and accidental dispatches Note To use this feature the Duress Option setting under the REPORTING PARTITION 1 menu must be turned on To program a Duress Code 1 With the display showing DURESS CODE enter the desired 4 digit duress cod...

Страница 29: ... on The display flashes the entered setting 2 Press ƒ and the display shows the new set ting Open Close Rpts 0103 cs phone 1 0113 cs phone 2 Phones CS Phone 1 2 Default off When this setting is on the panel sends a report when the system is armed closed or disarmed opened Note To use this feature the Opening Reports and Closing Reports settings under the REPORTING menu must be turned on To turn Op...

Страница 30: ...r enter the desired pager phone number including pauses The dis play flashes the entered number 2 Press ƒ and the display shows the new number To delete a Pager Phone Number 1 With the display showing PHONE NUMBER _ current number press D The display shows PHONE NUMBER _ High Level Rpts 0121 pager 1 0131 pager 2 0141 pager 3 Phones Pager Phone 1 3 Default on When this setting is on the panel repor...

Страница 31: ... off or 2 on The display flashes the entered setting 2 Press ƒ and the display shows the new set ting Streamlining 0125 pager 1 0135 pager 2 0145 pager 3 Phones Pager Phone 1 3 Default on This setting determines whether the panel includes off or excludes on the account number when reporting to a pager To turn Streamlining off or on 1 With the display showing STREAMLINING OFF ON current setting pre...

Страница 32: ...l phone test Thus any successful panel report to the central monitoring station resets the Next Phone Test setting to the Phone Test Freq value The panel only conducts an Auto Phone Test if no other reports are made during the Phone Test Freq time period When this feature is off an Auto Phone Test is always conducted according to the Phone Test Freq setting even if the panel makes other reports to...

Страница 33: ...lay shows the new set ting Cancel Message 02007 Phones Options Global Default on This setting determines whether or not the panel displays a cancel message after the user disarms the system to clear an alarm condition To turn Cancel Message off or on 1 With the display showing CANCEL MESSAGE OFF ON current setting press 1 off or 2 on The display flashes the entered setting 2 Press ƒ and the displa...

Страница 34: ... HANG RING OFF ON current setting press 1 off or 2 on The display begins flashing the entered selection 2 Press ƒ and the display shows the new set ting Supervisory Time 0300 Timers Global Default random This setting determines what time of day the panel sends supervisory low bat tery or auto phone test reports to the central station The setting is based on a 24 hour timer so there is no need to e...

Страница 35: ...er of days 1 255 The display flashes the entered setting 2 Press ƒ and the display shows the new set ting Output Trip Time 0304 Timers Global Default 4 sec This setting determines how long onboard and SnapCard outputs are activated when tripped if they are configured for a momentary response To set the Output Trip Time 1 With the display showing OUTPUT TRIP TIME nn SECONDS current setting enter th...

Страница 36: ...nn SECONDS current setting enter the desired time value 45 184 using 8 second inter vals The display flashes the entered set ting 2 Press ƒ and the display shows the new set ting Extended Delay 0312 Timers Partition 1 Default 4 min This setting determines how much time 1 8 minutes the user has to enter or exit the premises through a designated extended delay door without causing an alarm Note For ...

Страница 37: ...e system When set to ON pressing the LOCK button arms the system directly to AWAY with no Entry and Exit Delay When set to OFF pressing the LOCK button increments the arming level from OFF to STAY and from STAY to AWAY To change the Keychain Touchpad Arm ing setting 1 With the display showing KEYCHAIN TOUCH PAD ARM OFF ON current setting press 1 off or 2 on The display flashes the entered setting ...

Страница 38: ...station or a pager whenever sensors or zones are bypassed To turn Bypass Reports off or on 1 With the display showing BYPASS REPORTS OFF ON current setting press 1 off or 2 on The display flashes the entered setting 2 Press ƒ and the display shows the new set ting Low CPU Battery 05004 Reporting Global Default on When this setting is on the panel reports a low panel battery to the central sta tion...

Страница 39: ...nsor trip does not occur within a 4 minute time period then the panel sends an error report to the central monitor ing station When this feature is turned off the panel does not send Two Trip Error reports Note For UL Listed systems Two Trip Error must be turned off To turn Two Trip Error off or on 1 With the display showing TWO TRIP ERROR OFF ON current setting press 1 off or 2 on The display fla...

Страница 40: ...nel reports to the central monitoring station or pager daily or weekly when the panel detects a wireless device supervisory condition To set RF Supv Report to daily or weekly 1 With the display showing RF SUPV REPORT DAILY WEEKLY current setting press 1 daily or 2 weekly The display flashes the entered setting 2 Press ƒ and the display shows the new set ting Swinger Limit 05014 Reporting Global De...

Страница 41: ...sends a recent closing report to the central station or a pager if an alarm occurs within two minutes after the exit delay time expires Such a report is used to identify a possible exit fault To turn Recent Closings off or on 1 With the display showing RECENT CLOS INGS OFF ON current setting press 1 off or 2 on The display flashes the entered setting 2 Press ƒ and the display shows the new set tin...

Страница 42: ...e A 3 Sensor Group Characteristics Note For UL Listed systems Alarm Verify must be turned off To turn Alarm Verify off or on 1 With the display showing ALARM VERIFY OFF ON current setting press 1 off or 2 on The display flashes the entered setting 2 Press ƒ and the display shows the new set ting System Tamper 0517 Reporting Partition 1 Default off This setting determines the following Whether or n...

Страница 43: ... For UL Listed systems this feature must be off To turn Disable Trouble Beeps off or on 1 With the display showing DISABLE TR BEEPS OFF ON current setting press 1 off or 2 on The display flashes the entered setting 2 Press ƒ and the display shows the new set ting UL 98 Options 0602 Siren Options Global Default off This setting determines whether or not the panel complies with UL 98 require ments 4...

Страница 44: ...ntil the LED flashes two times c Press and hold the UNLOCK button until the LED flashes once 6 Continue tripping sensors to learn them into the selected sensor group To stop learning sen sors into a group press twice and start again from step 1 LEARN SENSORS to learn sensors into another group or use the EDIT SENSORS menu to change group assignment after learning the sensor zone Sensor Text 071 Se...

Страница 45: ...ber P1 partition 1 G13 sensor group 13 NC normally closed HW hardwired and BACK DOOR is the programmed text name You can also change the zone sensor group assignment to eliminate the need to delete and relearn the zone sensor To Edit Sensors 1 With the display showing LEARN SENSORS press B until the display shows EDIT SENSORS 2 Press ƒ and the display shows the lowest sensor number zone sensor ass...

Страница 46: ...on Press ƒ and the display shows the new setting Key Beeps Acc Modules Bus Devices Default on This setting determines whether or not selected touchpads sound beeps when their buttons are pressed This feature is usually turned off if a touchpad is located in or near bedrooms to avoid disturbing persons sleeping To turn Key Beeps on or off 1 With the display showing the desired touchpad press ƒ B ƒ ...

Страница 47: ... ber Press ƒ and the display shows the new setting Note For California State Fire Marshall Listed installations this feature must be off Two Wire Smoke 0901 Onboard Options Inputs Default off This setting determines whether panel zone input 6 is set up for 2 wire smoke detectors on or for standard intrusion or 4 wire smoke detectors off Note If 2 wire smoke detectors are connected to hardwire zone...

Страница 48: ...nt Each security access code Installer Dealer System Master or User must be unique Do not use the same combination of numbers for any two codes The USER CODES menu lets you program change regular user access codes and the system master code Time 00 Time and Date Default 00 00 This setting lets you adjust the panel clock to the correct time The panel uses a 24 hour clock eliminating the need to des...

Страница 49: ...Direct Bypassing 10nn1 nn user 00 thru 15 User Codes Default off User Codes perform basic arm ing and disarming functions The system allows up to 16 user codes user numbers 00 15 User numbers that show indicate no code is currently pro grammed for that user number To turn user code Direct Bypassing off or on 1 With the display showing USER CODES press ƒ and the display shows REGULAR USER CODES 2 P...

Страница 50: ...y flashes the entered selection Press ƒ and the display shows the new setting Silent Arming 21 Options Default off This setting determines whether the partition arms the system with off or without on sounding status beeps from sirens and the touchpad Note Turning this feature on will double the exit time This option is not available when SIA False Alarm Reduction 0003 is on To turn Silent Arming o...

Страница 51: ... System Commands Testing Zones Sensors Testing Phone Communication Testing Central Station Pager Communication You should test the system after installing or servicing and after adding or removing devices from the system UL Listed systems should be tested weekly Refer to the Troubleshooting section if correct test results are not achieved Chime On Close 25 Options Default off This setting determin...

Страница 52: ...Wireless Sensor Does Not Test 4 Press the STATUS button when you think all zones sensors are tested The touchpad displays any untested sensors zones and touchpad panics If all sensors zones and touchpad panics have been tested the display shows SENSOR TEST OK or ZONES ALL TESTED fixed display touchpads 5 Test any untested zones sensors and touchpad panics 6 If you need more time to complete the se...

Страница 53: ...y when displayed depending on pager service Account numbers are not displayed if Streamlining is turned on 1 Call the central station and tell the operator that you will be testing the system 2 Arm the system 3 Test each of the touchpad and wireless panic buttons and trip at least one sensor of each type fire intrusion etc to verify correct operation 4 Check pager displays to verify reports are re...

Страница 54: ...tch 3 When the desired pitch is heard release the button If there is no touchpad activity for about 15 seconds the steady tone stops sounding Table 5 Pager System Event Codes Code System Event 009 Zone Restoral 111 System Disarmed 118 Trouble Condition Cleared 119 Alarm Canceled 222 System Armed to STAY 333 System Armed to AWAY 555 Phone Test 888 System Trouble Condition 999 System in Alarm Table ...

Страница 55: ...ing see the user programming OPTIONS menu Touchpad buttons don t beep when pressed 1 Check for touchpad power and or bus miswiring opens or shorts 2 Check that key beeps option is set to on see the ACCESSORY MODULES BUS DEVICES menu Arming and Disarming System protests and won t arm 1 If arming to level 2 make sure all monitored perimeter doors and windows are closed 2 If arming to level 3 make su...

Страница 56: ...dwire Zones System doesn t go into alarm when zone is tripped 1 System is disarmed Arm system and then trip the zone 2 Zone is not learned into panel memory Enter installer dealer program mode and use the LEARN SENSORS menu to add the zone into memory Zone reports trouble condition 1 Check that onboard and SnapCard zone inputs have a 2k ohm EOL resistor installed at the last device on the loop in ...

Страница 57: ...rom backup battery 1 Check the AC circuit breaker to be sure the circuit is live 2 Check for proper panel and transformer wiring 3 Check that the transformer is plugged into a nonswitched outlet and secured with the provided screw 4 Check that the transformer is supplying AC to the panel Transformer internal fuse may be blown Be careful when securing the transformer to an outlet with a metal cover...

Страница 58: ...Sniffer 60 401 to verify that sensor is transmitting If sensor is not transmit ting check battery for low or no voltage and replace 2 Change mounting position of sensor from horizontal to vertical or vice versa and test sensor several times for consistency 3 Sensor signal is not reaching panel receiver because sensor is too far away Remove sensor from mounted location and test from other locations...

Страница 59: ...1BXT na 1 2 mA for 10 detectors Panel limited to 100 mA 13 463 Visus LP60 PIR Motion Detector 10 mA 10 mA 13 464 DS940 PIR Motion Detector 17 mA 17 mA 13 468 Optex RX 040 PI PIR Motion Detector 17 mA 17 mA SuperBus 2000 Devices 4 maximum 60 746 01 SuperBus 2000 2x16 LCD Alphanumeric Touchpad 57 mA 90 mA 60 820 SuperBus 2000 Fixed Display Touchpad 33 mA 65 mA 60 803 04 SuperBus 2000 2x20 LCD Alphan...

Страница 60: ...le emergency buttons Police Instant 1 2 3 02 Fixed Panic 24 hour silent fixed emergency buttons Silent Instant 1 2 3 03 Portable Panic 24 hour silent portable emergency buttons Silent Instant 1 2 3 04 Fixed Auxiliary 24 hour auxiliary sensor such as Pendant Panic or holdup button Auxiliary Instant 1 2 3 05 Fixed Auxiliary 24 hour auxiliary emergency button Siren shutoff confirms CS report Auxiliar...

Страница 61: ...al Instant Interior 24 hour local alarm zone protecting anything that opens and closes Police Instant 1 2 3 22 Local Delayed Interior Same as group 21 plus activation initiates a delay before going into alarm Police Standard 1 2 3 23 Local Instant Auxiliary 24 hour local alarm zone protecting anything that opens and closes Auxiliary Instant 1 2 3 24 Local Instant Auxiliary 24 hour local alarm zone...

Страница 62: ...pplication Alarm Delay Restoral Supervisory CS Report Chime Active Levels D i n i n g R o o m H a l l B e d r o o m B e d r o o m B e d r o o m P a t h o f P e r s o n W a l k i n g M o t i o n S e n s o r D e t e c t i o n P a t h K i t c h e n M o t i o n S e n s o r D e t e c t i o n P a t h L i v i n g R o o m M o t i o n S e n s o r K i t c h e n L i v i n g R o o m Table A4 Item Numbers and ...

Страница 63: ...34 Chime 074 Force 114 Mat 154 Screen 194 9 035 Closed 075 Foyer 115 Medical 155 Second 195 A 036 Closet 076 Freeze 116 Memory 156 Sensor 196 B 037 Closing 077 Front 117 Menu 157 Service 197 C 038 Code 078 Furnace 118 Mother s 158 Shed 198 D 039 Computer 079 Gallery 119 Motion 159 Shock 199 E 040 Control 080 Garage 120 No 160 Side 200 F Table A4 Item Numbers and Sensor Text Continued Item Sensor T...

Страница 64: ...____ ____________ ____________ ____________ ____________ Immediate Trouble Beeps Off 0600 Installer Code 4321 0001 Keychain TP Arming Off 0403 Keyswitch Sensor None 0015 Latchkey Reports Pagers 1 2 3 all On 0124 pager 1 0134 pager 2 0144 pager 3 ___________ ___________ ___________ Learn Sensors None 070 Low CPU Battery 05004 Low Level Reports CS Phone 1 On CS Phone 2 Off Pagers 1 2 3 all Off 0102 ...

Страница 65: ...rm Reduction 0003 Siren Timeout 4 minutes 0313 Siren Verify Off 0610 Smoke Verify Off 0900 SnapCard Output 1 01400 keychain Touchpad button activation 081000 SnapCard Output 2 00410 any audible alarm 081010 SnapCard Output 3 00903 arming to STAY or AWAY 081020 SnapCard Output 4 01003 arming to AWAY 081030 Star Is No Delay Off 0404 Supervisory Time random 0300 Swinger Limit 1 05014 System Tamper Of...

Страница 66: ...off System Tests off 10070 10071 10072 ___________ ___________ ___________ User Code 08 None Direct Bypassing off System Tests off 10080 10081 10082 ___________ ___________ ___________ User Code 09 None Direct Bypassing off System Tests off 10090 10091 10092 ___________ ___________ ___________ User Code 10 None Direct Bypassing off System Tests off 10100 10101 10102 ___________ ___________ _______...

Страница 67: ...Exterior Siren 016 Interior Siren 017 AVM Trip pulse 018 Table A7 Sensor Group Event Trigger Numbers Sensor Group Trigger No Group 00 in alarm 064 Group 01 in alarm 065 Group 02 in alarm 066 Group 03 in alarm 067 Group 04 in alarm 068 Group 05 in alarm 069 Group 06 in alarm 070 Group 07 in alarm 071 Group 08 in alarm 072 Group 09 in alarm 073 Group 10 in alarm 074 Group 11 in alarm 075 Group 12 in...

Страница 68: ...sor 05 in alarm 133 open 233 Sensor 06 in alarm 134 open 234 Sensor 07 in alarm 135 open 235 Sensor 08 in alarm 136 open 236 Sensor 09 in alarm 137 open 237 Sensor 10 in alarm 138 open 238 Sensor 11 in alarm 139 open 239 Sensor 12 in alarm 140 open 240 Sensor 13 in alarm 141 open 241 Sensor 14 in alarm 142 open 242 Sensor 15 in alarm 143 open 243 Sensor 16 in alarm 144 open 244 Sensor 17 in alarm ...

Страница 69: ...arm 214 No Activity in alarm 216 Fire Panic in alarm 217 Police Panic in alarm 218 Auxiliary Panic in alarm 219 Opening Report in alarm 220 Closing Report in alarm 221 Latchkey Report in alarm 222 Duress in alarm 223 Force Armed Report in alarm 224 Recent Closing Report in alarm 226 Sensor Test Report in alarm 227 Table A10 Response Numbers Siren Tracking Trip Delay Response Time Response No no no...

Страница 70: ...ns siren time response times activate outputs only if sirens are active for another reason 3 If an alarm event does not necessarily require disarming no activity closing report etc out puts set up for a sustained response time remain activated until the next arming level change 4 If an event occurs that activates an output set up for trip delay the delay and output activation can be canceled by tr...

Страница 71: ... Rpts On Off Backup On Off 0114 0104 Reporting Format SIA CID 0115 0105 0124 Latchkey Rpts On Off 0134 Latchkey Rpts On Off 0144 Open Close Rpts On Off Open Close Rpts On Off Open Close Rpts On Off 0123 0133 0143 Low Lev Rpts On Off 0142 High Lev Rpts On Off 0141 0140 Phone Number 0150 Phone Number Streamlining On Off 0125 Streamlining On Off 0135 Streamlining On Off 0145 Phones CS Phone 1 Downloa...

Страница 72: ...uto Phone Test On Off Ring Hang Ring On Off Dialer Abort On Off Pager Delay 15 secs 0 30 02000 02003 02001 02005 02008 0210 0211 B A Auto Test Reset On Off 02002 Dialer Abt Delay 30 secs 15 45 02006 B A Cancel Message On Off 02007 Call Wait Cancel 02009 B A B A 02004 B A B A A B B Global Partition 1 Timers B A B A B A B A B A B A Siren Timeout nn mins 4 RF Tx Timeout nn hours 12 Exit Delay nnn sec...

Страница 73: ...g level is NOT annunciated on exterior siren output B A B A B B B A B B Smoke Verify On Off 2 Wire Smoke On Off Sn nn Item n 0 A B Maximum of 4 bus devices 0 3 Press B to return to Security Menu A B Sensor Group n Text for Sensor nn Delete Sensor nn Done Sensors Learn Sensors Delete Sensors Edit Sensors Trip Sensor nn 070 Sensor Text 071 072 073 Sensor Group nn Bus Devices Accessory Modules Status...

Страница 74: ...rk After disarming and canceling an alarm the system now displays all the alarms that have occurred since the last disarming Downloader Eavesdrop delay for carrier detect on downloader call in is now 5 seconds instead of 2 sec onds This change should eliminate problems connecting with the downloader The panel will recognize the extended version information request from the downloader and will resp...

Страница 75: ...st 24 hours with no AC and specified standby load Radio Frequency 319 5 MHz Nominal Range 750 feet 305 meters typical open air Storage Temperature Range 30 to 140 F 34 to 60 C Operating Temperature Range 32 to 120 F 0 to 49 C Maximum Humidity 90 Relative Humidity non condensing Auxiliary Power Output 12 V 750 mA current limited Dimensions 11 in 28 cm x 9 in 23 cm x 3 0 in 7 6 cm H x W x D ...

Страница 76: ...B U S R e d B l a c k 4 1 2 V I n t e r i o r P i e z o S i r e n 3 0 0 0 6 M a x i m u m 1 0 m A O u t p u t 2 I s O p e n C o l l e c t o r T h a t H a n d l e s U p T o 2 0 0 m A D e f a u l t C o n f i g u r a t i o n N O 0 1 7 1 0 A c t i v a t e s O u t p u t F o r S t a t u s A n d A l a r m T o n e s 2 W i r e S m o k e S e t t i n g I n P r o g r a m m i n g M o d e M u s t B e O n D o N ...

Отзывы: