Becker VRP-SB-PID Series Natural Gas Controllers Instruction Manual | 2
© 2016 General Electric Company. All rights reserved.
Scope of this Manual
This manual provides information on operation principles,
applications, installation, adjustment, and maintenance of the
VRP-SB-PID. For information concerning actuators, valves, and
accessories, refer to the instruction manuals provided with the
specific product.
Note: Only those qualified through training or experience should
install, operate, or maintain Becker controllers. If there are any
questions concerning these instructions, contact your sales
representative, sales office, or manufacturer before proceeding.
Technical Assistance
Should you have any questions, please contact your local GE sales
representative or technical assistance at:
GE Oil & Gas
Attn: Becker Control Valves Technical Assistance
12970 Normandy Boulevard
Jacksonville, FL 32221
USA
Tel. +1-844-VALVE-GE
www.geoilandgas.com/valves
Technical Information
Table 1: Technical Specifications
Technical Specifications
Maximum Control
Pressure
1500 psig
10,342 kPa
Power Gas Requirements
Dry, filtered (40 micron) gas. Sufficient
pressure to operate positioner or actuator
Power Gas Maximum
Pressure
40, 80, 125 psig
Bleed to Pressure System
(BPS)
25 psig maximum
Output Signal
Three models are available depending
on the maximum power gas pressure.
40, 80 and 125 psig.
Output Capacity
1.5 Cv maximum
Action
Direct and reverse acting
Control Accuracy
3/4% of setpoint pressure
Resolution
0.2% of setpoint pressure
Operative Ambient
Temperature Range
-20°F to 160°F
-29°C to 71° C
Steady State Gas
Consumption
Zero
Approximate Weight
20 pounds
9kg
Pressure Connections
1/4 inch female NPT
Housing
Meets NEMA 3 Classification (Weather
tight)
Installation Orientation
Controller should be installed in the
vertical position
Model Number
The VRP-SB-PID model number is an alphanumeric combination,
which characterizes your specific unit. This number can be found
on the name tag located on the spring cartridge.
Example: VRP-600-SB-PID-40
VRP = Valve Regulator Pilot/Controller
600 = Maximum allowable control pressure
SB = Single Acting
PID = Proportional, Integral, Derivative Control
40 = Maximum power gas
Each unit has a stainless steel control tag fastened under one
of the bolts of the spring cartridge. The range of the control
spring is stamped on the face side of the tag. The shipping date
and seven-character part number are stamped on the bottom
side of the tag.
Table 2: Materials of Construction
Materials of Construction
External Parts
Anodized 2024 aircraft alloy aluminum
(1)
Internal Parts
316 stainless steel and 2024 anodized aluminum
Springs
Alloy Steel
Diaphragms
Buna-N reinforced by nylon fabric
Seats and O-Rings
Buna-N
Tubing
316 stainless steel
Fittings
316 stainless steel
Gauges
2-1/2 inch dial liquid filled stainless steel
connection w/stainless steel case
(1)
All stainless steel external construction available.
Exterior or corrosion resistant coating also available.
Example
A. Typical diaphragm actuator w/ Globe Valve.
Power gas = 40 psig max.
Typical bench set 11 to 23
BPS available up to 5 psig (fuel system or low
pressure distribution)
B. Typical piston actuator.
Power gas = 150 psi max. with BPS = 25 psig max.