Figure 66 Position Limits versus Setpoint Limit
Table 33 lists the position and travel settings as reference.
Table 33 Position and Travel Settings
FF Parameter
SVI FF DTM Field
Description
LIMITS_PROTECTED set to
FALSE
Position Limits Protected
checkbox.
Enables editing of the limits.
ENABLE_HI
Position Limits HI Enabled
checkbox.
Enables the LIMIT_HI parameter.
ENABLE_LO
Position Limits LO Enabled
checkbox.
Enables the LIMIT_LO parameter.
FINAL_VALUE_CUTOFF_HI
Position Limits HI
field.
Use this field to enter the value.
FINAL_VALUE_CUTOFF_LO
Position Limits LO
field.
Use this field to enter the value.
FINAL_VALUE_CUTOFF_HI.
ENABLE
Cut-Offs Full Open Enabled
checkbox.
Enables the
FINAL_VALUE_CUTOFF_HI.CUTOFF_POINT_HI
field.
FINAL_VALUE_CUTOFF_HI.
CUTOFF_POINT_HI
Cut-Offs Full Open Above
field.
If the FINAL_VALUE is more positive than this
value, the valve is forced to its maximum high
value (fully opened).
Содержание Baker Hughes Masoneilan SVI FF
Страница 12: ...This page intentionally left blank ...
Страница 72: ...This page intentionally left blank ...
Страница 82: ...This page intentionally left blank ...
Страница 94: ...This page intentionally left blank ...
Страница 108: ...This page intentionally left blank ...
Страница 198: ...This page intentionally left blank ...
Страница 206: ...This page intentionally left blank ...
Страница 224: ...This page intentionally left blank ...
Страница 228: ...This page intentionally left blank ...
Страница 230: ...This page intentionally left blank ...
Страница 250: ...This page intentionally left blank ...
Страница 262: ...This page intentionally left blank ...
Страница 263: ......