3

Egress control and open connector (IN and OUT)

You can optionally use the IN and OUT terminals for egress 
control and door relay operation.

IN.  

An egress button (normally open, momentary push-
button switch) can be connected across the IN and 0V 
terminals (

Figure 7

). When pressed, the button 

controls the request-to-exit function to the panel.

Out.  

Open collector output must be assigned with a 

number according to the output controller selected. 
Use the first output control assigned to the unit. Refer 
to the control panel programming manual for details.

Note:  

An external UL Listed power supply is required for UL 
installations.

Figure 7. Optional IN and OUT terminals

LED indications

The unit provides both system status and area LEDs.

Status LEDs

The unit has four status LEDs located above the LCD screen 
(

Figure 1

 on page 1) that indicate that following:

Power (green LED).  

The green LED illuminates when the 

control panel is powered by the AC supply.

Fault (yellow LED).  

The yellow LED illuminates to indi-

cate detection of a system fault.

Access (blue LED).  

The blue LED flashes when access to 

an area assigned to the unit is granted. It also flashes 
once when a card is badged at the AL-1116 (subject to 
valid card flashing programming).

Alarm (red LED).  

The red LED illuminates when there is 

a system tamper or an area assigned to the unit is in 
alarm state. To identify the area, view the 16 area 
LEDs hidden by the cover (

Figure 1

 on page 1). See 

Area LEDs

.

Area LEDs

When the unit cover is opened or removed, 16 LEDs are visible 
below the keypad (

Figure 1

 on page 1). Each LED represents an 

area and indicates the following:

• Red LED illuminates when its corresponding area is armed.
• Red LED flashes when a fault is detected in its corre-

sponding area.

• Green LED illuminates when the corresponding area is 

disarmed and ready to arm.

• No illumination indicates the corresponding area is 

disarmed but not ready to arm.

Operating features

The unit includes the following features:

Keyboard backlight and night light.  

By default the 

keyboard backlight is on (bright) for approximately 
4.15 minutes following a key press. The night light by 
default is on (dim). To change these options, see 

Menu 

options

 on page 4.

LCD contrast.  

To adjust the LCD contrast, press and hold 

the 

Menu

 key (

Figure 1

 on page 1) while you press the 

Up

 or 

Down

 keys (

Figure 8

). The default setting is 12.

Figure 8. Keys

Bypass/instant key.  

To bypass active zones when you arm 

the system, press the

 Bypass/instant

 key (

Figure 8

). 

You can also use this key for instant arming. To use 
instant arming, enter the user PIN and press the 

Bypass/instant

 key.

Stay key.  

Use the

 Stay

 key (

Figure 8

) when you are arming 

the system to autobypass the interior zones and arm all 
the perimeter zones for access. 

LCD backlight.  

The LCD backlight illuminates for 30 

seconds following a key press.

Beeper tone.  

To adjust the beeper tone, press and hold the 

Clear

 key (

Figure 1

 on page 1) while you press the 

Up

 

or 

Down

 key (

Figure 8

). The default setting is 16.

LCD text format.  

The 4 line by 16 character LCD can 

display text in the following formats:

Format 1 (default) wraps text using hyphens 
when a word is broken onto the next line.

Format 2 wraps text without hyphens when a 
word is broken onto the next line.

Format 3 wraps text to the next line without 
breaking words.

To change the format, press and hold the

 0

 key while 

you press the 

Up

 or 

Down

 key.

Card reader (AL-1116 only).  

The AL-1116 is fitted with a 

Smart Card reader that uses the address of the unit to 
communicate with the panel and so does not need its 
own system bus address. The reader is located behind 
the keypad with the number 2 key being the approxi-
mate center (

Figure 1

 on page 1). The sensitivity of the 

reader depends on the mounting environment (large 
metal surface will reduce the reader’s sensitivity).

+12

0V

Keypad power

from panel LAN

0V

+12

External door
lock power
source 

To door
strike
solenoid

Door control
relay

Egress

D+

D-

IN

OUT

Up key

Down key

Bypass/instant key

Stay key

Unused key

Unused key

Содержание AL-1111

Страница 1: ...one of the pins away from the body of the unit and pull Figure 1 Unit front 2 The metal mounting plate at the back of the unit is held by a locking screw Figure 2 To remove the mounting plate loosen the screw by at least 0 3 in 8 mm slide the mounting plate down and then pull the bottom of the mounting plate away from the body of the unit Figure 2 Unit back and mounting plate 3 Attach the mounting...

Страница 2: ...e RS 485 system bus You can connect the unit up to 5 000 ft 1 5 km from the control panel or 4 door elevator controller DGP We recommend you use a Beldon 8723 twisted pair shielded data cable The shield of any system bus cable must be connected to system ground at one end only This unit does not provide an Earth connection for this purpose If you daisy chain the system bus to the unit ensure that ...

Страница 3: ...to arm Operating features The unit includes the following features Keyboard backlight and night light By default the keyboard backlight is on bright for approximately 4 15 minutes following a key press The night light by default is on dim To change these options see Menu options on page 4 LCD contrast To adjust the LCD contrast press and hold the Menu key Figure 1 on page 1 while you press the Up ...

Страница 4: ...ter Press 0 Enter to exit the RAS main menu Submenus typically offer a choice between a default setting and alternative settings Navigate the submenus in the following manner Press Enter to accept the currently displayed setting and to return to the main menu Press Menu to scroll to an alternative setting Menu options The RAS menu provides numbered options Options 7 to 12 apply only to the AL 1116...

Страница 5: ... or disable the use of reader configuration cards at the AL 1116 reader If you wish to prevent modification of the reader setup by configuration card you should disable this option 12 Last card Use this option to display the number of the last card badged at the AL 1116 reader The format shows the facility code and the ID number Offline mode If the unit has power available but loses communication ...

Страница 6: ...to radio or tele vision reception which can be determined by turning the equip ment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet or a circuit different than that to which the receiver is connected...

Отзывы: