4.6 Alarms and Warnings
A warning or an alarm is signalled by the relevant LED on the front of the frequency converter and indicated by a code on the display.
A warning remains active until its cause is no longer present. Under certain circumstances operation of the motor may still be continued. Warning messages may
be critical, but are not necessarily so.
In the event of an alarm, the frequency converter will have tripped. Alarms must be reset to restart operation once their cause has been rectified. This may be
done in four ways:
1.
By using the [Reset] control button on the Keypad.
2.
Via a digital input with the “Reset” function.
3.
Via serial communication/optional network.
4.
By resetting automatically using the [Auto Reset] function.
NB!
After a manual reset using the [RESET] button on the Keypad, the [Auto] button must be pressed to restart the motor.
If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked (see also table on following page).
Alarms that are trip-locked offer additional protection, since the mains supply must be switched off before the alarm can be reset. After being switched back on,
the frequency converter is no longer blocked and may be reset as described above once the cause has been rectified.
Alarms that are not trip-locked can also be reset using the automatic reset function in par. H-04
Auto-Reset (Times)
(Warning: automatic wake-up is possible!)
If a warning and alarm is marked against a code in the table on the following page, this means that either a warning occurs before an alarm, or it can be specified
whether it is a warning or an alarm that is to be displayed for a given fault.
This is possible, for instance, in par. F-10
Electronic Overload
After an alarm or trip, the motor carries on coasting, and the alarm and warning flash on the frequency
converter. Once the problem has been rectified, only the alarm continues flashing.
High Power Service Manual for Unit Sizes 6x
50
4
Содержание AF-650 GP Series
Страница 31: ...High Power Service Manual for Unit Sizes 6x 30 3...
Страница 39: ...Illustration 3 5 Intermediate and inverter sections High Power Service Manual for Unit Sizes 6x 38 3...
Страница 41: ...Illustration 3 7 Inverter section High Power Service Manual for Unit Sizes 6x 40 3...
Страница 43: ...Illustration 3 8 Brake option High Power Service Manual for Unit Sizes 6x 42 3...
Страница 97: ...High Power Service Manual for Unit Sizes 6x 96 7...
Страница 111: ...High Power Service Manual for Unit Sizes 6x 110 8...
Страница 121: ...High Power Service Manual for Unit Sizes 6x 120 9...
Страница 134: ...11 Block Diagrams High Power Service Manual for Unit Sizes 6x 133 11...
Страница 135: ...Illustration 11 1 Unit Size 6x drive Top Level Block Diagram High Power Service Manual for Unit Sizes 6x 134 11...