6.2.1 Modbus TCP
EN-40 MODBUS TCP Status
Range:
Function:
[0]
[1]
Read only. Displays the Modbus TCP- specific 16-bit Status word.
Bit
Description
Bit = [0]
Bit =[1]
0
Link Status port
1
Disconnected
Connected
1
Link Status port
2
Disconnected
Connected
2
Link speed
0/10 Mbps
100 Mbps
3
Link Duplex
Half
Full
4
Port 502 com-
munication
No
Yes
5
UNUSED
-
-
6
Valid IP address No
Yes
7
Modbus time-
out (30 s)
No
Yes
8
Duplicate IP
No
Yes
9
Register 7 error No
Yes
10
FTP server
Disabled
Enabled
11
HTTP server
Disabled
Enabled
12
SMTP service
Disabled
Enabled
13
Cable diagnosis Disabled
Enabled
14
Auto crossover Disabled
Enabled
15
IGMP snooping Disabled
Enabled
EN-41 Slave Message Count
Option:
Function:
Read only.
Displays the number of Modbus messages received and processed by the slave.
EN-42 Slave Exception
Option:
Function:
Read only.
Displays the number of Modbus messages for which the slave has sent an exception response.
EN-80 FTP Server
Option:
Function:
[0] *
Disable
Disables the built-in FTP server.
[1]
Enable
Enables the built-in FTP server.
EN-81 HTTP Server
Option:
Function:
[0] *
Disable
Disables the build-in HTTP (web) server.
[1]
Enable
Enables the build-in HTTP (web) server.