DEH40151
DEH40151 Rev.No.02
4
Figure 3. Removing the shield inserts from the shield for SF breaker installation in
A –Series
®
II Panelboards.
11. To install branch breaker (kit ASPP6SF3S) on left side of interior, place the filler
plate [11] over the dead front so that the four same-size holes line up with the
threaded holes of the dead front, as illustrated in Figure 4. Fasten filler plate to the
dead front with four #10-32 x
3
/
8
screws [12] tightened to 27-36 in-lb.
12. To install branch breaker (kit ASPP6SF3S) on right side of interior, flip filler
plate [11] and place it over the dead front so that the four same-size holes line up
with the threaded holes of the dead front, as similar to step 11. Fasten filler plate
to the dead front with four #10-32 x
3
/
8
screws [12] tightened to 27-36 in-lb.
13. Reattach the dead front to the interior with the 8 screws removed in step 2.
Tighten the screws to 27-36 in-lb.