Figure 2. Installation of a SF circuit breaker kit on right side of interior, catalog number 
ASPP6SF3S, into an A-Series

®

 II Panelboards. 

 

6.  Mount bracket [8] on the interior rail with two screws [9] with 27-36 in-lb at the 

location defined. 

7.  Place the conical washer [6] over the three ¼-28 x 1 

3

/

8

 screws [5] and insert the 

screws through the holes in the top of the circuit breaker. Secure the three spools 
[4] to the underside of the breaker terminal with the screws [5]. Take care to 
assemble the screws to the spools as shown in Figure 1 or Figure 2, with the 
tapped end of the spool toward the breaker terminal. 

8.  Place the breaker over branch base[1],[2] and [3], align the spool[4] with 

protruded opening in branch bases and tighten the three ¼-28 X 1 

3

/

8

 screws [5] 

installed in step 7 to 60  in-lb. Maximum. 

9.  Insert two screws [14] into the holes in the circuit breaker and tighten to bracket 

[8] with 18-22 in-lb. 

10. Remove the four screws [12] of existing filler plate from dead front where SF 

breaker needs to be installed, as illustrated in Figure 3. 

Содержание A-Series II Panelboard

Страница 1: ...WS 10 32 X 3 8 N722P16006B6 4 Installation WARNING Before attempting to install one of these kits remove all power from the panelboard Use the following procedure to install a SF circuit breaker kit Call out numbers in the illustrations and numbers in brackets in the text refer to the Item Numbers in Table 1 Installation of a three pole kit is illustrated in Figure 1 or Figure 2 1 Remove the inter...

Страница 2: ...erior catalog number ASPP6SF3S into an A Series II Panelboards 5 Refer fig no 2 to mount the breaker on left side of interior Place branch base for A phase 2 adjacent to cross bar 13 as shown in fig 1 and insert the screw 7 through slot provided for A phase to clamp it with main busbar Similarly mount B phase 1 branch busbar to B phase main busbar but adjacent to A phase branch base and C phase 3 ...

Страница 3: ... to the underside of the breaker terminal with the screws 5 Take care to assemble the screws to the spools as shown in Figure 1 or Figure 2 with the tapped end of the spool toward the breaker terminal 8 Place the breaker over branch base 1 2 and 3 align the spool 4 with protruded opening in branch bases and tighten the three 28 X 1 3 8 screws 5 installed in step 7 to 60 in lb Maximum 9 Insert two ...

Страница 4: ...ated in Figure 4 Fasten filler plate to the dead front with four 10 32 x 3 8 screws 12 tightened to 27 36 in lb 12 To install branch breaker kit ASPP6SF3S on right side of interior flip filler plate 11 and place it over the dead front so that the four same size holes line up with the threaded holes of the dead front as similar to step 11 Fasten filler plate to the dead front with four 10 32 x 3 8 ...

Страница 5: ...d after SG as shown in Figure 5 then gap between the breakers dim A has to be followed as mentioned in Table 2 Replace the subsequent blank filler of dead front with SF filler plate given in kit ASPP6SF3S using steps 10 to 13 15 If SF breaker has to be installed immediately after crossbar as shown in Figure 6 then gap between the breaker and crossbar has to be 0 061inch ...

Страница 6: ...DEH40151 DEH40151 Rev No 02 6 Figure 5 Distance between breakers Table 2 Distance between breakers Gap with Breaker A in SG 0 582 ...

Страница 7: ...riations in equipment nor do they provide for every possible contingency that may be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser s purposes the matter should be referred to the GE Company ...

Страница 8: ...DEH40151 DEH40151 Rev No 02 8 g GE Industrial Systems ...

Отзывы: