GEK-106426B
MIB High Impedance Bus Differntial Relay
4-15
4 COMMUNICATIONS
4.4 ACTUAL
4
4.4.2 EVENT RECORDER
Actual – Event Recorder
option makes the last 24 relay events to be retrieved (up to 32) and displayed in the window
appearing in Figure 4-16. Each event record is labeled with date, time (with 1msec. resolution), the cause of the event
(pickup, trip of a certain function, etc.), and a list of the status of all inputs, outputs and functions during the event.
Additionally, the program also shows current and voltage values for all phases and ground, frequency and single line
sequence voltage during the event.
Figure 4–16: EVENTS WINDOW
The retrieved events can be reviewed in this window or also saved to disk (to be opened with ENERVISTA MII SETUP
program) or exported to CSV (Comma Separated Values) format. This is a standard text table format that can be opened
with most commercially available database or spreadsheet programs such as MS Access or Excel.
Содержание 90.017.102
Страница 19: ...1 14 MIB High Impedance Bus Differntial Relay GEK 106426B 1 4 USING THE KEYPAD AND DISPLAY 1 GETTING STARTED 1 ...
Страница 103: ...6 8 MIB High Impedance Bus Differntial Relay GEK 106426B 6 2 OUTPUTS AND LEDS CONFIGURATION 6 I 0 CONFIGURATION 6 ...
Страница 115: ...7 12 MIB High Impedance Bus Differntial Relay GEK 106426B 7 4 OPERATIONS 7 KEYPAD AND DISPLAY 7 ...
Страница 135: ...8 20 MIB High Impedance Bus Differntial Relay GEK 106426B 8 17 ADVANCED SETTINGS 8 RELAY COMMISSIONING 8 ...
Страница 162: ...GEK 106426B MIB High Impedance Bus Differntial Relay A 23 APPENDIX A A 8 USED FORMATS A ...
Страница 163: ...A 24 MIB High Impedance Bus Differntial Relay GEK 106426B A 8 USED FORMATS APPENDIXA A ...