GEK-106426B
MIB High Impedance Bus Differntial Relay
6-7
6 I/0 CONFIGURATION
6.2 OUTPUTS AND LEDS CONFIGURATION
6
Virtual trip signals are activated as soon as the protection unit trip conditions are present, independently from the trip
enable setting. This signal can be used to activate LEDs or auxiliary outputs. If the user wants the protection unit to trip,
then the trip enable setting must be activated. In this case, the relay will activate the trip contact.
MISCELLANEOUS 2
Close Breaker
Active when the close breaker operation is performed
MIXED 2
ACTIVE GROUP
Settings group 2 is active
Local
Active when the relay display is inside MAIN SETTINGS, ADVANCED
SETTINGS or OPERATIONS menu