GEK-106426B
MIB High Impedance Bus Differntial Relay
3-13
3 HARDWARE
3.4 HIGH-SPEED OVERCURRENT PROTECTION MODULE
3
Each output has a different configuration, and it is able to operate independently to the others.
If Jx jumper is removed, the output contact configuration change as shown in the following figure:
After removing the Jx Jumper, the outputs are divided in two groups: Independent and isolated.
Group1:
Terminals B8-B7: Provide one output contact combining OUT1 and OUT2
Group 2:
Terminals B9-A7: OUT3 Standard output contact
Terminals B10-A7: OUT4 Standard output contact
3.4.6.1 OUTPUT CONFIGURATION AT TERMINALS B8-B7:
To have a
normally open
contact across terminals B7-B8, configure OUT1 and OUT2 as shown bellow:
•
Remove JX internal jumper
•
Keep OUT1 and OUT2 as normally open contacts (factory default conf.)
•
Using the PC software, configure the two outputs to operate using the same internal signal. The internal signal used in
the example is "XX TRIP"
OUT1 and OUT2 must operate together to operate like a single output.The configuration of OUT1 and OUT2 must be the
same so both outputs close.
Содержание 90.017.102
Страница 19: ...1 14 MIB High Impedance Bus Differntial Relay GEK 106426B 1 4 USING THE KEYPAD AND DISPLAY 1 GETTING STARTED 1 ...
Страница 103: ...6 8 MIB High Impedance Bus Differntial Relay GEK 106426B 6 2 OUTPUTS AND LEDS CONFIGURATION 6 I 0 CONFIGURATION 6 ...
Страница 115: ...7 12 MIB High Impedance Bus Differntial Relay GEK 106426B 7 4 OPERATIONS 7 KEYPAD AND DISPLAY 7 ...
Страница 135: ...8 20 MIB High Impedance Bus Differntial Relay GEK 106426B 8 17 ADVANCED SETTINGS 8 RELAY COMMISSIONING 8 ...
Страница 162: ...GEK 106426B MIB High Impedance Bus Differntial Relay A 23 APPENDIX A A 8 USED FORMATS A ...
Страница 163: ...A 24 MIB High Impedance Bus Differntial Relay GEK 106426B A 8 USED FORMATS APPENDIXA A ...