750/760 FEEDER MANAGEMENT RELAY – COMMUNICATIONS GUIDE
5 - 1
750/760 Feeder Management Relay
Chapter 5: DNP Communications
GE
Grid Solutions
DNP Communications
DNP 3.0 Device Profile Document
The communications port configured as a DNP slave port must support the full set of
features listed in the Level 2 DNP V3.00 Implementation (DNP-L2) described in Chapter 2 of
the subset definitions. See the DNP protocol website at
http://www.dnp.org
for details
DNP 3.0: DEVICE PROFILE DOCUMENT
Vendor Name: General Electric Multilin Inc.
Device Name: 750/760 Feeder Management Relay
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Device Function:
Master Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP
Levels Supported (the complete list is described in the attached table):
Binary Input (Object 1, variations 1 and 2)
Binary Output (Object 10, variation 2)
Analog Input (Object 30, variations 1, 2, 3, and 4)
Analog Input Change (Object 32, variations 1, 2, 3, and 4)
Warm Restart (Function Code 14)
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received: 292
Maximum Application Fragment Size
(octets):
Transmitted: 2048
Received: 2048
Maximum Data Link Re-tries:
None
Fixed
Configurable (note 1)
Maximum Application Layer Re-tries:
None
Configurable
Ë
Ë
Ë
Ë
Ë
Ë