4 - 14
750/760 FEEDER MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 4: MODBUS MEMORY MAP
0301
Phase B RMS Current
0 to 65535
A
F1
---
0302
Phase C RMS Current
0 to 65535
A
F1
---
0303
Percent of Load-to-Trip
0 to 2000
%
F1
---
0304
Ground Current
0 to 65535
A
F1
---
0305
A-N RMS Voltage
0.00 to 655.35
kV
F3
---
0306
B-N RMS Voltage
0.00 to 655.35
kV
F3
---
0307
C-N RMS Voltage
0.00 to 655.35
kV
F3
---
0308
A-B RMS Voltage
0.00 to 655.35
kV
F3
---
0309
B-C RMS Voltage
0.00 to 655.35
kV
F3
---
030A
C-A RMS Voltage
0.00 to 655.35
kV
F3
---
030B
3
Reserved for Polarizing Current
---
---
---
---
030C
Average Current
0 to 65535
A
F1
---
030D
Average Line Voltage
0.00 to 655.35
kV
F3
---
030E
Average Phase Voltage
0.00 to 655.35
kV
F3
---
030F
Neutral Current
0 to 65535
A
F1
---
FREQUENCY AND THREE-PHASE POWER (read only actual values)
0310
2, 12
Three-Phase Real Power
–30000 to 30000
kW
F86
---
0311
2, 12
Three-Phase Reactive Power
–30000 to 30000
kvar
F86
---
0312
2, 12
Three-Phase Apparent Power
0 to 30000
kVA
F86
---
0313
Three-Phase Power Factor
–0.99 to +1.00
---
F6
---
0314
System Frequency
0.00 to 65.00
Hz
F3
---
0315
1
System Frequency Decay Rate
–10.00 to 10.00
Hz/s
F6
---
0316
1
Auto Ranging Power / Energy Multiplier
1 to 100
---
F1
---
SYNCHRONIZING VOLTAGE (read only actual values)
0318
Synchronizing RMS Voltage
0.00 to 655.35
kV
F3
---
0319
Synchronizing RMS Voltage Frequency
0.00 to 65.00
Hz
F3
---
031A
Synchronizing Voltage Difference
0.00 to 655.35
kV
F3
---
031B
Synchronizing Phase Difference
0 to 359
°
F1
---
031C
Synchronizing Frequency Difference
0.00 to 65.00
Hz
F3
---
031D
Synchronizing Voltage Angle
0 to 359
° Lag
F1
---
ENERGY USE (read only actual values)
0320
2
Positive Watthours (2 words)
0 to 4e9
kWh
F86
---
0322
Positive Watthour Cost (2 words)
0 to 4e9
$
F7
---
0324
2
Negative Watthours (2 words)
0 to 4e9
kWh
F86
---
0326
Negative Watthour Cost (2 words)
0 to 4e9
$
F7
---
0328
2
Positive Varhours (2 words)
0 to 4
×
10
9
kvarh
F86
---
032A
2
Negative Varhours (2 words)
0 to 4
×
10
9
kvarh
F86
---
032C
Energy Use Data Last Reset (2 words)
---
---
F23
---
LAST DEMAND (read only actual values)
0330
Last Phase A Current Demand
0 to 65535
A
F1
---
0331
Last Phase B Current Demand
0 to 65535
A
F1
---
0332
Last Phase C Current Demand
0 to 65535
A
F1
---
0333
2
Last Real Power Demand
–30000 to 30000
kW
F86
---
0334
2
Last Reactive Power Demand
–30000 to 30000
kvar
F86
---
0335
2
Last Apparent Power Demand
0 to 30000
kVA
F86
---
MAXIMUM DEMAND (read only actual values)
0340
Maximum Phase A Current Demand
0 to 65535
A
F1
---
0341
Maximum Phase A Current Date (2 words)
---
---
F23
---
0343
Maximum Phase A Current Time (2 words)
---
---
F22
---
0345
Maximum Phase B Current Demand
0 to 65535
A
F1
---
Table 3: Modbus Memory Map (Sheet 9 of 40)
ADDR
DESCRIPTION
RANGE
UNITS
TYPE
DEFAULT
1 2 3 4 5 6 7 8 9 10 11 12 13
For explanation of Table footnotes, see the Memory Map Notes at the end of this table.