background image

466-1534G • August 2006

Copyright © 2006, GE Security Inc.

Indoor/Outdoor PIR Motion Sensors

Installation Instructions

Introduction

This is the GE 

Indoor/Outdoor PIR Motion Sensors Installation 

Instructions

 for model numbers:

• 60-639-95R (indoor)
• 60-639-95R-OD (outdoor)
• 60-639-43-EUR (indoor, not investigated for use by UL)
• 60-639-43-ERT-OD (outdoor, not investigated for use by 

UL)

Passive-infrared (PIR) motion sensors detect movement within a 
specific area by sensing the infrared energy emitted from a body 
as it moves across the sensor’s field of view, causing a tempera-
ture change in the sensor’s zones. When the sensor detects this 
motion, it transmits an alarm signal to the control panel.
Use the indoor sensors to protect large areas and open floor plans 
or as backup protection for door/window sensors.
Use the outdoor sensors to identify motion in a protected outdoor 
area. Detected motion in this protected area can sound chimes or 
turn on outside lights. Do not use the outdoor sensors for intru-
sion protection.
Features include:

• 35 by 40 ft. (10.7 x 12.2 m) coverage area for standard and 

optional pet alley lenses;

• masking kit to block portions of the coverage area;
• three-minute transmitter lockout time after an alarm to 

extend battery life;

• cover-activated tamper (an optional wall-activated tamper is 

provided);

• supervisory signal transmitted every 64 minutes to the 

control panel;

• sensor low battery reports (trouble) to the control panel; and
• field-selectable sensitivity options.

Indoor sensor installation

Use the following installation guidelines:

• If possible, mount the sensor within 100 ft. (30.5 m) of the 

panel. While the transmitter may have a range of 500 ft. 
(152.4 m) or more out in the open, the environment at the 
installation site can have a significant effect on transmitter 
range.

• Position the sensor to protect an area where an intruder is 

most likely to walk across the detection pattern. (

Figure 1

).

Figure 1. Overhead detection pattern

• Mount the sensor between 5 and 8 ft. (1.5 and 2.4 m) from 

the floor (

Figure 2

). We recommend a height of 7.5 ft. (2.3 

m). Higher mounting provides better range, and lower 
mounting provides better protection close to the sensor. See 

Pet alley lens

 on page 3.

Figure 2. Detection pattern

 

 

   

 

 

 

Side view with mounting height of 7.5 ft. (2.3 m)

Top view

20 ft.

 6 m

20 ft.
 6 m

10 ft.

 3 m

10 ft.

 3 m

 0 ft.
 0 m

  5 ft.
 1.5 m

 15 ft.
 4.5 m

 25 ft.

 7.5 m

 35 ft.
10.5 m

  5 ft.
 1.5 m

 15 ft.
 4.5 m

 25 ft.
 7.5 m

 35 ft.

10.5 m

  5 ft.
 1.5 m

 15 ft.
 4.5 m

 25 ft.
 7.5 m

 35 ft.

10.5 m

  5 ft.
 1.5 m

 15 ft.
 4.5 m

 25 ft.

 7.5 m

 35 ft.
10.5 m

 0 ft. (0 m)

 0 ft. (0 m)

 0 ft. (0 m)

 8 ft. (2.4 m)

 8 ft. (2.4 m)

 4 ft. (1.2 m)

 4 ft. (1.2 m)

Side view with mounting height of 5 ft. (1.5 m)

Side view with pet alley lens and flush mount

 8 ft. (2.4 m)

 4 ft. (1.2 m)

Содержание 60-639-95R

Страница 1: ...tivated tamper an optional wall activated tamper is provided supervisory signal transmitted every 64 minutes to the control panel sensor low battery reports trouble to the control panel and field selectable sensitivity options Indoor sensor installation Use the following installation guidelines If possible mount the sensor within 100 ft 30 5 m of the panel While the transmitter may have a range of...

Страница 2: ...ote The wall tamper switch cannot be used when you mount the sensor in a corner or on the swivel mount Figure 3 Mounting options To mount the sensor do the following 1 To remove the mounting plate depress the button on the top of the sensor Figure 4 and pull the mounting plate away from the sensor Figure 4 Sensor parts 2 Punch out the mounting holes applicable for your installa tion Figure 5 Use t...

Страница 3: ...o flush mount or corner mount the sensor with the back of the sensor parallel to the walls Do not use the inclined mount position because this will tilt the sensor s field of view downward Position the sensor so that is has a clear line of sight across the protected room Sensitivity settings The sensor is set to standard sensitivity at the factory This sensi tivity is preferred for most applicatio...

Страница 4: ... Testing Testing the sensor includes a walk test an environment test and a final test with the control panel Walk test Walk test the unit from both directions to determine the pattern boundaries The edge of the coverage pattern is determined by the first flash of the LED This may change slightly depending on the sensitivity setting To walk test the sensor do the following 1 Remove the sensor from ...

Страница 5: ...utes after installing the batteries before you activate walk test mode Troubleshooting If the system doesn t respond correctly when the sensor is acti vated follow these guidelines Check sensor programming refer to the panel s program ming instructions and reprogram the sensor if necessary Move the sensor to another location and test for correct response To relocate the sensor do the following 1 T...

Страница 6: ...r sensor Outdoor sensor 32 to 120 F 0 to 49 C 10 to 120 F 12 to 49 C Storage temperature 30 to 140 F 34 to 60 C Maximum relative humidity 90 relative humidity noncondensing Dimensions L x W x H 2 9 x 2 4 x 1 9 in 74 x 61 x 48 mm Austria Italy Denmark Netherlands France Portugal Germany Spain Ireland Sweden Manufacturers Declaration of Conformity Product identification Model type 60 639 43 EUR and ...

Отзывы: