GE Security NetworX Series NX-8V2 Скачать руководство пользователя страница 4

NX-8V2-Control Panel

Installation Instructions

4

Location 3 - Phone 1 dial attempts/backup control

Location 3 has two segments of numerical data.

Segment 1 - Phone 1 dial attempts

Program the number of dial attempts (1 to 15) the communi-
cator makes to phone 1 before ending the notification 
process. The default is 

8

, which means that the communi-

cator makes eight attempts to the first number.

Segment 2 - Phone 1 backup control

Program the backup control for phone 1. The default is 

0

.

• Program a 

0

 in segment 2 to cause the NX-8V2 to make 

the designated number of attempts to phone 2 before 
setting the fail to communicate condition to stop 
reporting. 

• Program a 

1

 in segment 2 to cause the NX-8V2 to stop 

trying to communicate after the designated number of 
attempts have been made to phone 1.

• Program a 

2

 in segment 2 to cause the NX-8V2 to make 

the dial attempts in increments of two. The first two 
attempts are made to phone 1, the next two attempts to 
phone 2. This repeats until the total number of attempts 
designated in segment 1 is completed.

Location 4 - Phone 1 events reported

Location 4 has two segments of feature selection data. Use 
this location to select those events reported to phone 1. 

• If you do not want dual or split reporting, use Location 4 

to select all events to phone 1.

• If you want dual or split reporting and the split is based on 

the event type (alarm, open/close, etc.), use Location 4 to 
select only those events that are reported to phone 1.

• If you don’t want events reported to phone 1, program 

0

 

in Location 4 (disabling all options).

Segment 1

1. Alarms and alarm restores.
2. Opening and closings.
3. Zone bypass and bypass restores.
4. Zone trouble and trouble restores.
5. Power fail, low battery, power restore, and low battery 
restore.
6. Bell cut, telephone line cut, bell cut restore, telephone 
line restore.
7. Test reports.
8. Start and end programming, download complete.

Segment 2 

1. Zone and box tamper and tamper restore.
2. Auxiliary power overcurrent, ground fault, and restore 
for both.
3. Wireless sensor missing and restore.
4. Wireless sensor low battery and restore.

5. Expander trouble and restore.
6. Fail to communicate.
7. Zone activity monitor.
8. Reserved

Location 18 - Custom communicator format

Location 18 has four segments of feature selection data. Use 
this location to program the communicator format used to 
transmit to the receiver connected to phone 3. Refer to your 
central station receiver documentation to determine which 
format is compatible. Select a format from 

Table  

on page 3. If 

you need a format other than those listed, review the over-
ride options described in this location to build the appropriate 
format.

Segment 1

1. On for 1800 Hz transmit; off for 1900 Hz.
2. On for 2300 Hz handshake; off for 1400 Hz.
3. On for cksum parity; off for double round parity.
4. On for two-digit event code; off for one-digit event 
code.
5. Reserved.
6. Reserved.
7. On for 20 pps; off for 10 or 40 pps.
8. On for 10 pps; off for 20 or 40 pps.

Segment 2

1. On for pager format (no handshake required).
2. On for 1400/2300 handshake.
3. Reserved.
4. Reserved.
5. On for contact ID.
6. On for SIA.
7. On for contact ID or 4+3.
8. On for DTMF.

Segments 3 and 4 - Reserved

21

3/1 or 4/1 fast with parity

Same as 10, but sends the alarm event 

code rather than the zone number

22

SIA

SIA with area modifiers

a.

Pulses per second.

Table 4.

Communicator formats (continued)

Data

Format

Description

Содержание NetworX Series NX-8V2

Страница 1: ...ted in location 37 this output becomes voltage output 12 VDC 1 Amp maximum load Note A 3 3 kohm resistor may be required across the bell terminals when a 12 VDC siren is used If no resistor is used you may experience voltage leakage into the siren which will cause these devices to output a small signal KP DATA Connect to the data terminal on the keypads and the expanders Maximum number of devices ...

Страница 2: ...previous location Press the Medical key for the same location 5 To review the data in a specific location repeat the above procedure pressing but with no numeric data entry Each time you press the programming data of the next segment displays Exit a location To exit the current programming location do the following 1 Press the key The Ready LED goes off and the Armed LED goes on You must press the...

Страница 3: ...f numerical data Use this loca tion to program the communicator format used to transmit to the receiver connected to phone 1 Refer to your central station receiver documentation to determine which format is compatible Table 4 describes the formats for this location If you need a format other than those listed review the over ride options described in Location 18 Custom communicator format on page ...

Страница 4: ... restores 2 Opening and closings 3 Zone bypass and bypass restores 4 Zone trouble and trouble restores 5 Power fail low battery power restore and low battery restore 6 Bell cut telephone line cut bell cut restore telephone line restore 7 Test reports 8 Start and end programming download complete Segment 2 1 Zone and box tamper and tamper restore 2 Auxiliary power overcurrent ground fault and resto...

Страница 5: ...tomatically bypasses if enabled in segment 1 16 Instant with group bypass This zone creates an instant alarm whenever it is tripped and the armed LED is on This zone bypasses when the group bypass command is entered at the keypad 17 Entry exit delay 1 with tamper A trip starts entry delay 1 The lack of a trip during exit delay enables the automatic bypass or instant mode if programmed This zone ty...

Страница 6: ...ad sounder If the late to close early to open feature is enabled the opening and closing reports must be enabled For Canadian installations the class II transformer secure tab must not be employed The four wire smoke detector employed must be rated to operate over the voltage range of 11 5 to 12 4 V Compatible listed devices special applications Bell output sirens Wheelock models NS 1215W NS 12157...

Страница 7: ... based on three 17 A batteries Table 6 Use markings Model number Use marking Subassemblies NX 8 S Res Fire1 and Burg2 Com Burg4 Acc5 Homehealth Care Control Unit Motherboard NX 8E S Res Fire1 and Burg2 Com Burg4 Acc5 Homehealth Care Control Unit Motherboard NX 8V2 S Res Fire1 and Burg2 Com Burg4 Acc5 Homehealth Care Control Unit Motherboard NX 508 NX 508E Res Fire1 and Burg2 Com Burg4 Acc5 Output ...

Страница 8: ...structions 8 CAUTION Observe polarity when installing a new battery Installing the battery backwards may cause damage to the panel Dispose of used batteries according to the manufacturer s instructions and or local government authorities ...

Страница 9: ...is feature is not programmable in the panel Exit time and progress are always enabled Enabled disabled for remote arming Entry delays b b Combined abort window time and entry delay must not exceed one minute Entry 1 delay 24 1 30 30 to 240 seconds Entry 2 delay 24 3 30 30 to 240 seconds Abort window for nonfire zones Dialer delay 40 8 30 Enabled may be disabled by zone zone type but no cancel repo...

Страница 10: ... draw Without sounder Dimensions 110 mA max 75 mA 6 4 x 5 3 x 1 0 in 16 3 x 13 5 x 2 5 cm Metal enclosure dimension 11 25 x 11 25 x 3 50 in 28 58 x 28 58 x 8 90 cm Shipping weight 9 lb 4 1 kg FCC This device complies with part 15 of the FCC rules Operation is subject to the following conditions 1 This device may not cause harmful interference 2 This device must accept any interference received inc...

Отзывы: