466-2339A • October 2009

© 2009 GE Security, Inc.

g

NX-8V2-Control Panel

Installation Instructions

Introduction

This is the GE 

NX-8V2-Control Panel Installation Instructions. 

Installations should only be done by trained professionals. 
Use this document to install the system with default settings 
that comply with UL requirements. 
To install the keypad, other peripherals, and sensors, refer to 
the documentation for those devices.

Installation

There are four slots for board insertions inside the metal 
enclosure, two on the top and two on the bottom. These allow 
the PC board to be positioned vertically (

Figure 1

). When you 

slide the board between the grooves of the slots, make sure 
the terminal strip is toward the front opening (toward you) to 
allow for the wire connections.

Note:  

Install the metal enclosure with the door opening from the top 

to bottom.

Figure 1. Board installation

NetworX keypad maximum wire run

Table 1

 lists wire lengths for one keypad at the end of the 

wire. When connecting more than one keypad to the end of 
the wire, a higher gauge wire is required. 

Terminal descriptions

Table 2

 describes the panel terminals..

Table 1.

Maximum keypad wire run

Length in feet

Wire gauge for NX-8V2

Wire gauge for NX320-E

250

24

22

500

20

18

1000

18

16

1500

16

14

2500

14

12

Table 2.

NX-8V2 terminals

Terminal

Description

R1

House telephone ring (grey).

R

Telephone ring (red).

T

Telephone tip (green).

T1

House telephone tip (brown).

EARTH

Earth ground. Connect to a cold water pipe or a 6 to 10 ft. 

driven rod.

AC

AC input. Connect to a 16.5 V, 40 or 50 VA Class II UL 

approved transformer.

Bell + and 

Bell -

If used as a siren output (default), the speaker rating should 

be 15 watt at 8 or 16 ohm, or 30/40 watt at 4, 8, or 16 ohms. If 

voltage ouput is selected in location 37, this output becomes 

voltage output, 12 VDC, 1 Amp maximum load. Note: A 3.3 

kohm resistor may be required across the bell terminals 

when a 12 VDC siren is used. If no resistor is used, you may 

experience voltage leakage into the siren, which will cause 

these devices to output a small signal.

KP DATA

Connect to the data terminal on the keypads and the 

expanders. Maximum number of devices (keypads plus 

expanders) is 32. See Maximum Wire Run table. 

KP COM

Connect to the common terminal on the keypads and the 

expanders.

KP POS

Connect to the POS terminal on the keypads and the 

expanders. Individually, this terminal is limited to 1 amp. 

Combined, this terminal and AUX PWR+ are limited to 2 amps 

total current.

SMOKE+

Smoke detector power 12 VDC, 1.5 amps maximum (for those 

jurisdictions which allow the Priority zone to be used with 

smoke detectors).

COM

Common negative wire of powered devices such as motion 

detectors and smoke detectors.

AUX PWR+

Connect positive wire of all powered devices except smoke 

detectors and keypads. Individually, this terminal is limited to 

1 amp. Combined, this terminal and KP POS are limited to 2 

amps total current.

ZONE 8

Connect to one side of zone 8 loop. Connect the other side to 

com terminal. Open or short causes alarm. Only zone 8 may 

be used for a two-wire smoke detector using a 680 ohm EOL 

resistor.  Refer to the wiring diagram. Program location 37, 

segment 6, option 1. 

COM

Common (-) terminal for zones 7 and 8.

ZONE 7

Connect to one side of zone 7 loop. Connect the other side to 

COM terminal. Open or short causes alarm.

ZONES 6 to 

1

Connect as described for zones 7 and 8. Only zone 8 can be a 

two-wire zone. Refer to the wiring diagram for examples.

AUX 1 to 

AUX 4

Connect negative lead of low current device [relay, LED 

(install 1kohm resistor in series with LED), etc.] Connect posi-

tive lead of device to COM. Current is limited to 50 mA when 

output is negative, and 250 uA when output is positive.

Содержание NetworX Series NX-8V2

Страница 1: ...ted in location 37 this output becomes voltage output 12 VDC 1 Amp maximum load Note A 3 3 kohm resistor may be required across the bell terminals when a 12 VDC siren is used If no resistor is used you may experience voltage leakage into the siren which will cause these devices to output a small signal KP DATA Connect to the data terminal on the keypads and the expanders Maximum number of devices ...

Страница 2: ...previous location Press the Medical key for the same location 5 To review the data in a specific location repeat the above procedure pressing but with no numeric data entry Each time you press the programming data of the next segment displays Exit a location To exit the current programming location do the following 1 Press the key The Ready LED goes off and the Armed LED goes on You must press the...

Страница 3: ...f numerical data Use this loca tion to program the communicator format used to transmit to the receiver connected to phone 1 Refer to your central station receiver documentation to determine which format is compatible Table 4 describes the formats for this location If you need a format other than those listed review the over ride options described in Location 18 Custom communicator format on page ...

Страница 4: ... restores 2 Opening and closings 3 Zone bypass and bypass restores 4 Zone trouble and trouble restores 5 Power fail low battery power restore and low battery restore 6 Bell cut telephone line cut bell cut restore telephone line restore 7 Test reports 8 Start and end programming download complete Segment 2 1 Zone and box tamper and tamper restore 2 Auxiliary power overcurrent ground fault and resto...

Страница 5: ...tomatically bypasses if enabled in segment 1 16 Instant with group bypass This zone creates an instant alarm whenever it is tripped and the armed LED is on This zone bypasses when the group bypass command is entered at the keypad 17 Entry exit delay 1 with tamper A trip starts entry delay 1 The lack of a trip during exit delay enables the automatic bypass or instant mode if programmed This zone ty...

Страница 6: ...ad sounder If the late to close early to open feature is enabled the opening and closing reports must be enabled For Canadian installations the class II transformer secure tab must not be employed The four wire smoke detector employed must be rated to operate over the voltage range of 11 5 to 12 4 V Compatible listed devices special applications Bell output sirens Wheelock models NS 1215W NS 12157...

Страница 7: ... based on three 17 A batteries Table 6 Use markings Model number Use marking Subassemblies NX 8 S Res Fire1 and Burg2 Com Burg4 Acc5 Homehealth Care Control Unit Motherboard NX 8E S Res Fire1 and Burg2 Com Burg4 Acc5 Homehealth Care Control Unit Motherboard NX 8V2 S Res Fire1 and Burg2 Com Burg4 Acc5 Homehealth Care Control Unit Motherboard NX 508 NX 508E Res Fire1 and Burg2 Com Burg4 Acc5 Output ...

Страница 8: ...structions 8 CAUTION Observe polarity when installing a new battery Installing the battery backwards may cause damage to the panel Dispose of used batteries according to the manufacturer s instructions and or local government authorities ...

Страница 9: ...is feature is not programmable in the panel Exit time and progress are always enabled Enabled disabled for remote arming Entry delays b b Combined abort window time and entry delay must not exceed one minute Entry 1 delay 24 1 30 30 to 240 seconds Entry 2 delay 24 3 30 30 to 240 seconds Abort window for nonfire zones Dialer delay 40 8 30 Enabled may be disabled by zone zone type but no cancel repo...

Страница 10: ... draw Without sounder Dimensions 110 mA max 75 mA 6 4 x 5 3 x 1 0 in 16 3 x 13 5 x 2 5 cm Metal enclosure dimension 11 25 x 11 25 x 3 50 in 28 58 x 28 58 x 8 90 cm Shipping weight 9 lb 4 1 kg FCC This device complies with part 15 of the FCC rules Operation is subject to the following conditions 1 This device may not cause harmful interference 2 This device must accept any interference received inc...