2
ESL 1500 Series Fire Alarm Control Panel
Panel Description
Standard Features:
•
Modular design; 1, 3, or 5 zones
•
Power limited
•
1.5 Amp. 24 VDC FWR output
•
All functions DIP switch activated
•
Built-in walktest and alarm verification
•
Sprinkler supervisory and waterflow alarm activation
•
Class A (Style D) or Class B (Style B) initiating wiring
•
Reliability of surface-mount design
•
Superior lightning protection
Table 1. Ordering Information
Model
Title
Description
1501
Single zone fire panel
1 initiating circuit,
2 indicating circuits
1503
Three zone fire panel
3 initiating circuits,
2 indicating circuits
1505
Five zone fire panel
5 initiating circuits,
2 indicating circuits
1500-BMB
Basic Master Board
1 initiating circuit,
2 indicating circuits
1500-ZEM
Zone Expansion Module
2 initiating circuits,
Class A or B
1500-LEM
Local Energy Module
Connect to Listed
master box
1500-ZRM-5
1500 Zone Relay Module
5 relays
1500-SH
System housing
System housing
with transformer
1500-TK
Flush mount trim ring
Mounting panel
semi-flush with wall
1500-TR
Transformer
Transformer
replacement
1500-2.7
End-of-line resistor
Initiating and
indicating circuits
2.7 Ky 1/2 W
1500-RA-5A
Remote Annunciator
5 alarm zones w/
trouble and
sounder
204-12/24 V
Power supervision unit
EOL power
supervisory unit
405-01
Polarity reversal relay
Single circuit,
24 VDC
Optional Features:
•
Local Energy Module (LEM)
•
Zone Relay Module (ZRM) 5 relays
•