background image

1 0

ESL 1500 Series Fire Alarm Control Panel

Alarm Initiating Devices

This section describes how to field wire initiating devices such as smoke detectors, pull stations, and heat detectors. Refer to
Figure 5 for Class A (Style D) and Figure 6 for Class B (Style B) wiring.

Two-Wire Smoke Detectors, Heat Detectors, and Manual Pull Stations

Connect only two-wire smoke detectors UL Listed as compatible to the 1500 Series Fire Control Panel. Refer to the
list of compatible detectors in Appendix A.

Two-wire detectors receive their power direct from the zone terminals and transmit the alarm signal via the same wires. Be
certain to observe polarity when installing detectors.

All initiating devices must be wired sequentially for proper supervision with the end-of-line resistor (2.7K Ohm 1/2 W)
installed after the last device. ESL has detectors available with EOL built in.

Four-Wire Smoke Detectors

Four-wire detector power is shared with indicating circuits; do not exceed total power requirements of 1.5 Amps.

Always supervise four-wire detector power with an end-of-line power supervisory device (ESL model 204-12/24V) after
the last unit.

See Figure 5 for Class A (Style D) wiring and Figure 6 for Class B (Style B) connection to the panel.

Do not overlook adequate lightning protection. Lightning damage commonly occurs from three sources:

1.

Through alarm loop wiring

2.

Through AC power inputs

3.

Through earth ground or power ground connections

The 1500 System has substantial lightning protection incorporated in all three areas. However, proper lightning protection for AC
power must be accomplished where the wire enters the building. Arrestor circuitry and earth grounding should be in accordance
with Article 250 of the National Electrical Code.

There is no known protective device available which is capable of protecting equipment from damage caused by “direct hit”
strikes of lightning due to the extremely high energy released (10 million to 100 million volts @ 10,000 to 30,000 amps).
However, line surges from indirect strikes can be minimized.

Additional protection is suggested in areas subject to above-average lightning activity or induced voltage spikes and fluctuations
due to power line load switching.

Field Wiring Checkout Procedures

Note

: Make sure that AC and battery power are disconnected before proceeding.

1.

Test all field wiring before connecting any equipment.

A. Make sure no unwanted voltages are present on circuit conductors and ground. They are a hazard and may prevent

proper system operation.

B. All wiring except those intentionally and permanently grounded must be tested for isolation from ground using an

insulation testing device such as a “Megger”.

Note: 

Caution must be exercised when using voltage generating test instruments such as a “Megger”. Damage

to equipment could result if the equipment is connected (wired) during wiring tests.

C. All wiring, other than those intentionally connected together, must be tested for conductor-to-conductor

isolation using an insulation testing device.

2.

With each circuit pair short-circuited at the end of the circuit, measure circuit resistance with an ohmeter. Record the circuit
resistance of each circuit and store this data with the control panel. Loop resistance must be less than 100 ohms on
initiating zones.

3.

Perform testing as described previously after any addition, deletion, or mechanical or electrical damage to the system
has occurred.

4.

A periodic test should be performed in accordance with the schedules recommended in NFPA 72, Chapter 7, or more
frequently, if required by the authority having jurisdiction. Whenever possible a 100 percent test should be performed.
When less than a 100 percent test is performed, a record must be maintained of the devices tested each time, so different
devices are tested in subsequent tests.

Содержание 1500-2.7

Страница 1: ...ESL 1500 Series Fire Alarm Control Panel Installation and Operations Manual GE Security g ...

Страница 2: ......

Страница 3: ...on 6 Supervisory Functions 6 Remote Test Drill 6 Field Wiring 7 Installation Recommendations Precautions 9 Field Wiring Checkout Procedures 10 Alarm Initiating Devices 10 Alarm Indicating Devices 11 Connecting Supplementary Contacts 11 Connecting Optional Remote Notification Devices 13 Programming 14 BMB Programming 14 ZEM Programming 14 Testing and System Checkout 15 Maintenance 15 Troubleshootin...

Страница 4: ......

Страница 5: ...ure 10 Terminal Connections 12 Figure 11 Local Energy Module LEM Wiring Diagram 13 Figure 12 BMB Default Settings 13 Figure 13 ZEM Default Settings 14 Figure 14 ZEM Programming Switches Location 14 Tables Table 1 Ordering Information 2 Table 2 Status Indicators 5 Table 3 Wire Resistance 9 Table 4 Alarm Indicating Circuit Wire Size 9 Table 5 BMB Programming Features 14 Table 6 ZEM Programming Featu...

Страница 6: ...n good mechanical and working order If any application or installation information is not understood or is not covered in this manual please contact Technical Support 800 648 7424 Sales 800 547 2556 System Overview The ESL 1500 Series Control Panels are designed to provide reliable and economical fire alarm control solutions for commercial industrial residential and institutional applications The ...

Страница 7: ...re panel 5 initiating circuits 2 indicating circuits 1500 BMB Basic Master Board 1 initiating circuit 2 indicating circuits 1500 ZEM Zone Expansion Module 2 initiating circuits Class A or B 1500 LEM Local Energy Module Connect to Listed master box 1500 ZRM 5 1500 Zone Relay Module 5 relays 1500 SH System housing System housing with transformer 1500 TK Flush mount trim ring Mounting panel semi flus...

Страница 8: ...ries Determine the total system power requirements by using the Standby Battery Power Worksheet in Appendix B 9 System Check Make certain the 1500 panel is operating properly before connecting field wiring by performing a system check ESL makes this easy by factory installing end of line resistors to the proper Class B zone terminals To test the panel make sure all switches are in their normal pos...

Страница 9: ...hat has not been disabled will activate the indicating devices as normal The zone disconnect switch is defeated when a zone has been programmed for waterflow service See BMB Programming Walktest makes it possible for one service person to functionally test initiating devices without having to constantly return to reset the control panel When activiated the walktest feature sounds the indicating de...

Страница 10: ...hen using alarm verification total alarm delay alarm verification smoke detector power up time cannot exceed 60 seconds according to the National Fire Alarm Code NFPA 72 or 30 seconds for installations governed by the California State Fire Marshall Alarm delay includes verification time 12 seconds and smoke detector power up time Smoke detector power up time varies by manufacturer however the ESL ...

Страница 11: ... red local alarm LED lights In addition the supervisory LED on the BMB will activate During supervisory trouble the integral sounder activates a rapidly pulsing tone zone 2 yellow local trouble LED lights and the system trouble relay contacts transfer Remote Test Drill A remote test drill function is provided for testing the 1500 System Closing a listed normally open switch connected to terminals ...

Страница 12: ...w 1 Alarm verification 1 2 RA B A A B RA B A A B LEM ZEM Zone 4 5 ZEM Zone 2 3 System GND ON 1 2 3 4 5 6 7 8 429C 429C 2 7K EOL Resistor 1 2W Pull station Heat sensor 2 7K EOL Resistor 1 2W 449C 449C Zone 2 Zone 3 Zone 4 Zone 5 2 7K EOL Resistor 1 2W 204 12 24V Power supervision relay 2 7K EOL Resistor 1 2W RA B A A B RA B A A B B A A B B B A A B B A A Zone 1 is shown with 4 wire detectors wired i...

Страница 13: ...lktest 2 Zone 1 waterflow 1 Alarm verification 1 2 RA B A A B RA B A A B LEM ZEM Zone 4 5 ZEM Zone 2 3 System GND ON 1 2 3 4 5 6 7 8 429C 521B 429C 521B 2 7K EOL Resistor 1 2W Pull station Heat sensor 449C 541C 449C 541C Zone 2 Zone 3 Zone 4 Zone 5 204 12 24V Power supervision relay RA B A A B RA B A A B 2 7K EOL Resistor 1 2W 2 7K EOL Resistor 1 2W 2 7K EOL Resistor 1 2W 2 7K EOL Resistor 1 2W 2 ...

Страница 14: ...tem to a conduit or green wire circuit that also is used to power resistance heating motors fans air conditioning equipment or florescent lighting circuits since leakage currents into the ground return could damage system components A separate earth ground or cold water pipe with properly bypassed water meter should be used Provide a separate earth ground if water mains are non conductive Run sign...

Страница 15: ... capable of protecting equipment from damage caused by direct hit strikes of lightning due to the extremely high energy released 10 million to 100 million volts 10 000 to 30 000 amps However line surges from indirect strikes can be minimized Additional protection is suggested in areas subject to above average lightning activity or induced voltage spikes and fluctuations due to power line load swit...

Страница 16: ... 15 or 3 16 diameter drill and deburr 4 Install the supplied push rivets from the outside of the cabinet through both the cabinet side wall and the snap track driving the push pins flush with the rivet head In semi flush mounting installations install the push rivets from the inside of the cabinet 5 Complete electrical connections between the ZRM and the BMB before mounting it to the snap track Th...

Страница 17: ...e 1 trouble Supervisory Low no AC Low no battery Ground fault Indicating 1 trouble Indicating 2 trouble 1 2 3 4 5 6 7 8 9 10 1 Mounting hole 2 Basic Master Board BMB 3 Housing backbox 4 Programming switches 5 Zone Expander Modules ZEM 6 Mounting location for Zone Relay Module 1500 ZRM 5 7 Mounting hole 8 Battery area 9 Local Energy Master Box Trip Module 1500 LEM 10 1500 TR Transformer Figure 10 T...

Страница 18: ...ule LEM trip circuit is designed to interface to a Listed Master Box with a local energy trip mechanism This optional module provides a supervised trip circuit from the 1500 system that activates the Master Box upon a system alarm Make connections as detailed in Figure 11 For systems which include remote annunciation 1500 RA 5A use Figure 10 Remove all power from the system before beginning proced...

Страница 19: ... 1500 BMB is disabled See Supervisory Functions 2 on zone 3 5 Remote Connection to remote indicator not supervised Annunciator 1 on zone 2 4 Remote Connection to remote indicator not supervised Annunciator Do not program zones for waterflow in conjunction with walktest because the communicator or optional LEM module may transmit an alarm condition In addition the sytem alarm relay will be activiat...

Страница 20: ... the batteries Maintenance Batteries The 1500 Series control unit uses two sealed lead acid batteries as the secondary power source The batteries must be replaced if the Low Battery LED remains on for more than 48 hours indicates one or more of the battery cells are dead or the batteries will not hold a charge If the batteries are dead replace with batteries of the same size and electrical rating ...

Страница 21: ...oo low upgrade or move to new circuit Low No AC power LowAC power If secondary shows less than 22 VAC replace transformer System trouble LED Less than 94 VAC at transformer primary no load Trouble sounder slow Less than 102 VAC with maximum load intermittent Less than 22 VAC at transformer secondary no load Damaged transformer or loose connection Check for loose or broken connections Battery low R...

Страница 22: ...le Y or Z Maximum current per circuit 1 0 Amps Maximum total current 1 5 Amps Output voltage 24 VDC FWR End of line 2 7 K Ohms 1 2 Watt Supplementary alarm trouble contacts System trouble 2 0 A 30 VDC resistive System alarm 2 0 A 30 VDC resistive Sounder output Alarm Constant output Fault 0 25 sec on 2 5 sec off Supervisory 0 25 sec on 0 25 sec off Remote indicator Voltage 12 VDC Current 15 mA max...

Страница 23: ...etectors shown in Table 10 Table 8 Compatible Indicating Devices Manufacturer Part Number Amseco SLB24 75C Amseco SLB24G 75C Amseco SMS1 3A EST G1 R HOV110 EST G1 R HOV15 EST G1 R HOV75 EST G1 R V15 EST G1 R V75 EST G1 R HO EST G1 R H EST G1 R P EST G1M EST G1M RM Gentex ST24 15 75WR Gentex GES24 15 75WR Gentex HS24 15 75WR Gentex GEC24 15 75WR Gentex HS24 110WR Gentex GEC24 110WR System Sensor S2...

Страница 24: ...ility Identifier per Circuit Ohms Identifier ESL 400 Series 429C 429CT 100 C01 S10A 20 Self Diagnostic 429CRT 429CST 100 C01 S11A 20 ESL 500 Series 521B 521NB 100 C01 DIP SW 1 ON S09A 20 and ESL 500N Series DIP SW 1 OFF S10A 521BXT 521NBXT 100 C01 DIP SW 1 ON S09A 20 DIP SW 1 OFF S10A 521CRXT 521NCRXT 100 C01 S11A 20 521NCSXT 100 C01 S10A 20 521NCSRXT 100 C01 S11A 20 ESL 700 Series Heads 711U 711U...

Страница 25: ...p 1000 mA mA Auxiliary System Power mA 1 Amp 1000 mA mA 1500 ZEM Zone 2 8 mA mA 70 mA mA 1500 ZEM Zone 3 8 mA mA 70 mA mA 1500 ZEM Zone 4 8 mA mA 70 mA mA 1500 ZEM Zone 5 8 mA mA 70 mA mA 1500 LEM 1 mA 320 mA 1500 ZRM 5 0 mA 75 mA 1500 RA5A 0 mA mA 75 mA mA mA mA mA mA mA mA Total Current Requirements mA mA mA X 001 Amp mA X ___________ hours _____________ Ah Standby AMP Hours mA X 001 Amp mA X __...

Страница 26: ... from any other zone is not affected Alarm Disconnect Switch Operated After Alarm Condition For Maintenance Use Only Auxiliary alarm relay contacts remain latched Alarm indicating circuits are turned OFF Red local zone alarm LED remains ON Supervised remote annunciator indication remains ON Alarm signal from any other zone is not affected Reset Switch Operated Initiating circuit power removed smok...

Страница 27: ......

Страница 28: ...12603 Rev J 04 04 64812687 Rev J Tech Support 800 648 7424 FaxBack 800 483 2495 www GESecurity com GE Security 12345 SW Leveton Drive Tualatin OR 97062 503 692 4052 USA Canada 800 547 2556 GE Security g ...

Отзывы: