ESL 1500 Series Fire Alarm Control Panel
17
18
19
20
21
22
23
24
B-
B+
A+
A-
B-
B+
A+
A-
Connect to
120 V AC
60Hz
Connector from
transformer
Blk
Wht
Case
ground
Auxiliary
power (+)
Optional drill
test switch
Fire drill
1
B+
A+
A-
B-
6
7
8
Local Zone 1 alarm
(Supervised)
System 15VDC
System trouble
contacts
Auxiliary alarm
contacts
BMB standoff
9
10 11 12 13 14 15 16
C N/O N/C C N/C N/O
Power ON
(standby condition)
Zone 1
Zone 1
alarm
System
trouble
AC
power
Connector from
24 V DC battery in
BMB
8-Not used
7-Not used
6-Not used
5-Zone 2 supervisory
4-Zone 1 remote annunciator
3-Silent walktest
2-Zone 1 waterflow
1-Alarm verification
1
2
RA
B+
A+
A-
B-
RA
B+
A+
A-
B-
LEM
ZEM
Zone 4 & 5
ZEM
Zone 2 & 3
System
GND
ON
1
2
3
4
5
6
7
8
+
+
-
-
+
+
-
-
429C
521B
429C
521B
2.7K EOL
Resistor 1/2W
Pull station
Heat sensor
-
-
+
+
449C
541C
449C
541C
Zone 2
Zone 3
Zone 4
Zone 5
-
-
+
+
-
-
+
+
-
-
+
+
204-12/24V
Power
supervision relay
RA
B+
A+
A-
B-
RA
B+
A+
A-
B-
2.7K EOL
Resistor 1/2W
2.7K EOL
Resistor 1/2W
2.7K EOL
Resistor 1/2W
2.7K EOL
Resistor 1/2W
2.7K EOL
Resistor
1/2W
2.7K EOL
Resistor 1/2W
Zone 2 is shown with
2-wire detectors, wired in
Class B (Style B)
Zone 5 is shown with
2-wire heat detectors
and pull stations, wired
in Class B (Style B)
Zone 1 is shown with 4-wire
detectors, wired in Class B (Style B)
Bell circuit 1 is shown with Class B
(Style Y) wiring
Figure 6. Class B System Wiring Diagram
Class B System Wiring Diagram