MAINTENANCE
4.1 WARNING
Do not disconnect connector while circuit is energized (or live), unless area is known to be non-hazardous.
4.2 CAUTION
The operating temperature range of the Flame Sensor is
-40°C to 150°C
.
Do not
attempt to work on the
Flame Sensor or the cable until they have reached a safe handling temperature.
The Flame Sensor output will deteriorate as the lens becomes dirty. It is recommended, when initially
installed, that the signal level be recorded during normal operation. During subsequent running, the signal
level should be compared with the initial values. If a significant reduction in the signal level is noticed, then it is
recommended that the lens be cleaned at the next opportunity (with the turbine shut down and cold). Clean the
lens with isopropyl alcohol or other residue free solvent compatible with Sapphire. In order to reduce the risk of
galling, an anti seize compound should be applied to the mounting thread prior to reinstallation of the sensor.
5
TROUBLESHOOTING
5.1 WARNING
Do not disconnect connector while circuit is energized (or live), unless area is known to be non-hazardous.
5.2 CAUTION
The operating temperature range of the Flame Sensor is
-40°C to 150°C
.
Do not
attempt to work on the
Flame Sensor or the cable until they have cooled to a safe handling temperature.
PROBLEM
CAUSE
SOLUTION
No current flows
Reversed polarity
Open wire
Change polarity
Check connections
Low sensitivity during checkout or
operation
Dirty lens
Grounded cable
Clean lens (Section 4.0)
Check cable for grounds
Low flame intensity signal during
operation
Misalignment of the sensor mount
Check the squareness of all flanges
and pipes of the sensor mount. Verify
that the sensors have a clear view of
the flame.
Periodic low reading on secondaries
of DLN1 turbines
Condensation on the lens that can
occur under high humidity
situations.
A shorter mount tube (PN# E1-
0058P002), is available from GE
Reuter Stokes and may improve this
condition. Please contact GE Reuter
Stokes for further information.