![GE Intelligent Platforms, Inc. PAC8000 Скачать руководство пользователя страница 74](http://html.mh-extra.com/html/ge-intelligent-platforms-inc/pac8000/pac8000_getting-started-manual_571899074.webp)
74
PAC8000 Workbench Getting Started Guide
8. The IO configuration must now be downloaded to the controller to become active.
Click the green traffic light in the toolbar
to place the controller online.
9. Select
the
Configuration
|
Download Controller
menu item to initiate the download.
The
Download Configuration Options
dialog appears. Leave the options as
default. (
Save configuration to NVM
after download
and
Continue Module
Scanning
selected.)
As these options are appropriately defaulted based on the changes made to the
configuration, we recommend that you leave the options set at default. The options
are defined as follows:
•
Save configuration to NVM after download
– Causes the hardware
configuration to be saved to flash memory once the download is complete.
Therefore, if power to the controller is cycled, the configuration is retained.
•
Restart controller after download
– Once the download is complete, the
controller is restarted. This is only necessary if address changes are made
(IP addresses or node numbers) and should not be done on a running plant.
•
Continue Module Scanning
– If this option is not selected, each module is
restarted once the configuration is downloaded. Therefore, selecting this
option allows the modules to continue scanning during the configuration
download, ensuring that configuration changes can be made to a running
plant.
GE Intelligent Platforms, Inc.
September 2010