6
☀
Adopt non-intrusive detection method, no power failure during the test, maybe
no high voltage source is applied, which is more convenient to use than
traditional pulsed partial discharge detector;
☀
The test bandwidth range is 30kHz ~ 2.0GHz, suitable for the detection
principle of various frequency bands;
2.4 Product Application
ZXPD-200L partial discharge detector is widely used in the following fields:
☀
Development and distribution enterprises
☀
Railway system
☀
Petrochemical power supply system
☀
Aerospace testing field
☀
Automatic testing field
2.5 Parameters
TEV measurement
UHF measurement
Measuring range
0-60 dBmV
detection frequency
300-1500MHz
Resolution
1dB
measurement range
-75dBm-0dBm
Accuracy
±1dB
accuracy
<
1dBmV
Maximum pulse per
cycle
1400
Sensor band
300-2000MHz
Measurement
frequency band
1~100MHz
AA measurement
AE measurement
Measuring range
-6dBμV - 68dBμV
Measuring range
-6dBμV - 68dBμV
Resolution
1dB
Resolution
1dB
Accuracy
±1dB
Accuracy
±1dB
Sensor center
frequency
40 kHz
Frequency range
40~200 kHz
HFCT measurement
Sensor
transmission
impedance
5mV/mA
Detection frequency
1
~
30MHz
Sensitivity
≤50pC
hardware