- 8 -
Figure 16
Figure 17
Figure 18
Figure 19
Setting of error curve
VA
:
CT secondary side impedance value.
I-sn
:
CT secondary side rating current (1A or 5A).
Kalf
:
As for protection type CT (5P10 20VA)
,
“10”is Kalf
5%
:
Calculate the 5% error curve data and display the error curve.
10%
:
Calculate the 10% error curve data and display the error curve.
Error Curve Function Items
:
print the error curve graphics and data.
Data
:
inquire error curve graphics and data.
Back
:
return to the previous menu.
2) PT Excitation Characteristic Test (with connection mode shown in Figure 3)
Move the controller to Excitation , to enter PT Test interface(Figure 20)
U-sn : 100V
、
100/√3V
、
100/3V
、
150V
、
220V.
Current : the setting range for output current is 0
~
20A (It is usually set to be 1A)
Содержание ZXHQ-A+ CT
Страница 1: ...ZXHQ A CT PT Characteristics Tester ...