11
Function Factory Settings
•
Acceleration ramp time
5 sec
•
Deceleration ramp time
4 sec
•
Maximum speed
4000 rpm (For 750's = 640mm/sec, for 550's = 490mm/sec)
•
Opening Speed
3640 rpm (For 750's = 580mm/sec, for 550's = 440mm/sec)
•
Opening and closing slow speed
600 rpm (For 750's = 100mm/sec, for 550's = 75mm/sec)
•
Closing Speed
3000 rpm (For 750's = 480mm/sec, for 550's = 360mm/sec)
•
The motor start-up function has been pre-set in the factory and should not need altering
Parameter Settings
Par
Nx
•
Pt 39
Input Status
•
Pt 59
Output Status
•
Pt 80
Fault memory (records the previous faults which occurs with the inverter)
•
Pt 136
PE stop time (0.5 s)
•
N11
Opening speed (3640 rpm)
•
N13
Closing speed (3000 rpm)
•
N21
When set to formulae and powered off and on will reinitialise the gate
•
N22
Pedestrian opening position (% of full opening position max 80%)
•
N23
Opening and closing slow speed (600 rpm)
•
Pt 400
Gate counter, maximum 5000 (500,000 operations) Note. 100 gate operations will
be recorded as 1 on the inverter counter).
•
Pt 401
Internal serial number for recalibration
•
Pt 450
low current setting (usually 60 %)
Selecting a Function
•
To select a function use the up/down arrow keys to select corresponding symbol for desired function.
•
A LED will light up the symbol and the display will show the programmed settings for that function.
Setting Function Values
•
Having selected the desired function; to enter or change a setting press the enter key. The display will flash.
•
A value for the function can now be entered or changed using the up/down arrow keys.
•
To confirm the value for the desired function press the enter key, this will set the value, then press the out
button, this will return you to the previous screen.
Gate Direction Set-Up
•
It is important that the gate is set up to operate correctly for the open and closing cycles.
•
When the gate is closing a minus sign will be displayed on the screen when monitoring the RPM.
•
If the operation is not as above, two motor wires need to be swapped over.