Using inverter monitoring parameters for monitoring and fault finding
•
From the main screen “0.00” press the PRG button once to get to the parameter menu screen “D-00”.
•
Use >> button to select required digit on screen to change then scroll that digit up or down with the up/down
↕
button.
•
Use up/down
↕
buttons to get to the required parameter number, once number selected, press “SET” to enter into
required parameter. The screen will display the information for that parameter number.
Selection of handy parameters to use: *full list shown inverter manual
D-19 to D-21 = Last 3 fault records *handy especially if the power has been turned off after a fault and you need to
Know what the fault code was.
D-15 to D-16 = Temperature reading *Check if suspected overheating of inverter.
Inverter components
D-14 = Inverter input terminal *Used to check that the inverter is receiving the correct signals from CB-6
Status Board. In this way you can determine if the existing fault is related to either
The CB-6 board or the inverter.
*Use diagram below to determine status of inverter inputs different
LED display segments represent each input.