background image

AUTHORIZED DISTRIBUTOR - GasDetectorsUSA.com - Houston, Texas USA

Quickstart Guide 

GASMAX II + GDS-IR Gas Monitor

 

[email protected]

IMPORTANT

 - 

Before installing the GASMAX II + GDS-IR, 

make sure there are no toxic or combustible gases present. 
Declassify the area if necessary. 

 

Factors  such  as  air  movement  by  fans,  prevailing  winds, 
convection,  gas  density,  emission  sources  and  environmental 
variables  should  be  taken  into  account  when  determining  sensor 
location. As with all sensors, the GASMAX II + GDS-IR should be 
protected from falling or directed water, shock, vibration and dirt. 
The  GDS-IR  sensor  may  be  mounted  either  horizontally  or 
vertically (preferred). If mounted horizontally, make sure the GDS-
IR is protected from dripping water.  
Use  conduit  and  installation  practices  approved  for  the  area 
classification. When installed correctly, the GASMAX II + GDS-IR 
is certified for use in areas rated Class 1, Div 1, Groups B, C & D.  

S2 

Ribbon to Display 

P

W

R

 

O

U

T

 4

-2

“E

C

H

E

M

” 

O

U

T

 4

-2

“L

E

L”

 

G

N

D

 

R

E

F

 

C

O

M

 

A

C

T

 

CATBEAD 

S1 

C7 

C8 

C1 

C2 

I/O Power Supply 

Assy 10-0233 

TB1 

TB2 

The  GASMAX  II  power  supply  board  is  attached  to  the  inside  of 
the explosion-proof housing (see Figure 1).   
Connect  the  +DC  power  wire  to  TB2  pin  1.  Connect  the  –DC 
power to TB2 pin 4. DC voltage range is 18 to 30 VDC. 
The 4-20mA output signal is available at TB2 pin 3. If an optional 
toxic sensor is also connected to the GASMAX II, the toxic sensor  
4-20mA output is available on TB2 pin 2.  

Fig 1. GASMAX II Power Supply Board 

INSTALLATION 

POWER & 4-20mA WIRING 

Optional Relay / RS-485 DIGITAL WIRING 

The optional GASMAX II Alarm Relay / MODBUS interface board 
is attached to the back of the GASMAX II display assembly.  

RS-485  MODBUS  wiring  should  be  attached  to  TB2  pins  1  &  2. 
Attach  the  signal  shield  wire  to  TB2  pin  3. 

NOTE

:  RS-485  is 

polarity-sensitive  and  the  wires  on  pins  1  &  2  may  need  to  be 
swapped for proper operation. If wiring in a “daisy chain”, terminals 
4 & 5 are available for outgoing RS-485 wiring.  

If necessary, select Jumper 1 (J1) position “A” to enable the RS-
485  termination  resistor.  This  is  typically  done  on  the  device 
furthest from the RS-485 master controller.  

Wiring for the three alarm relays is available on TB1. The normally 
open,  common  and  normally  closed  contacts  are  rated  at  5A  / 
125VAC. Inductive loads should be protected by a reverse biased 
diode or other transient suppression device.  

U1 

TB3 

K2 

K3 

K1 

J1 






NO 

NC 

NO 

NC 
NO 

NC 

TB2 

TB1 


J1-A - Installs RS-485 
Termination Resistor 

J1-B - Omits RS-485 

RS-485 “A” & “B” terminals are 
connected internally. “S” is no-
connect for shield continuation 

Remote Alarm Reset 

Assy 10-0234 

Relay 1 

Relay 2 

Relay 3 

Fig 2. GASMAX II Alarm / MODBUS Board 

- 832-615-3588

Отзывы: