background image

13 

 

 
 
 

 
Position 6 

P.E STOPS CLOSE CYCLE 

OFF -  Activating the P.E input while motors are closing causes the motors to reverse. 
ON -   Activating the P.E input while motors are closing causes the motors to stop but not reverse. 

 

Position 7 

P.E STOPS OPEN CYCLE 

OFF -  Activating the P.E input while motors are opening is ignored by the controller. 
ON -   Activating the P.E input while motors are opening causes the motors to stop. 

 

Position 8 

P.E TRIGGERED AUTO-CLS 

OFF -  Not selected 
ON -   Selects the P.E triggered auto-close mode which causes the motors to auto-close if  

  the P.E input is activated then released. (Auto-close delay time is 0 seconds*) 

 

Position 9 

PEDESTRIAN AUTO-CLS 

OFF -  No pedestrian access auto-close 
ON -   Selects auto-close in the pedestrian access mode. (Auto-close delay time is 15 

seconds*) 

 

Position 10 

STANDARD AUTO-CLS 

OFF -  Not selected  
ON -   Selects standard auto-close mode which will close the motors after fully opening. 

(Auto-close delay time is 30 seconds*) 

 

 
 
 
 
 
Setting Cycle Timers & Auto Close Times 

 
The control board has pre-set cycle times which are used to set the maximum time the controller will drive 
the motors in the open and closed directions. The pre-programmed time for the open and close cycle timer’s 
is 60 seconds. The control board also has a pre-set pedestrian access time of 5 seconds which is intended to 
open the motor connected to M1 output only part way. If these default times do not suit your needs simply 
use the procedure below to adjust them. Note the same procedure can be used to adjust the auto-close times. 

1.

 

Place the slide switch into the “set” position  

2.

 

Adjust the timer’s value by pressing and holding the required push button for the desired time. 

3.

 

Repeat step 2 for the next timer (if desired). 

4.

 

Place the slide switch back into the “RUN” position. 

5.

 

Test operation.  

Make sure that the slide switch is placed back into the “RUN” position before testing the new timer value.  
As you can see the procedure used to set each timer’s value is the same only the push button used changes. 
Each push button is clearly labelled underneath as to which timer’s value it sets. Note when setting the OPEN, 
CLOSE and PEDESTRIAN cycle times the controller will drive the motors as if a “real” cycle is being 
executed. The difference being that the motors will stop as soon as the button is released, or the limit switches 
are reached. The OPN status LED on the control board will flash at 1 second intervals to assist setting times. 
Note when setting the OPEN and CLOSE cycle times when limit switches are used, release the push button 
a few seconds after the limit switch cuts motor power. This allows for the motors to slow down over the life 
of the operators without the need to adjust again. 

 

 
 
 
 

Содержание 630 CH

Страница 1: ...1 Installation and Maintenance Manual Chain Slider Gate Operators Inbuilt Models GDS 630 CH GDS 630 CH HD Made in Australia from Australian quality imported components A B N 62 059 806 405 July 2014...

Страница 2: ...lation 9 13 Electrical Cabling Mechanical Installation Electrical Connections Plan view layout conduit positions CB6 Control Board layout CB 6 Control inputs mode settings 4 Variable Speed Drive VSD 1...

Страница 3: ...e through the full travel to check the gate is not bent to the extent that the gate hits the operator and has ample clearance through it s full travel Check the height of the operator compared to the...

Страница 4: ...re the chain adjuster rods are level with the bottom teeth of the idler sprockets Fit the spacer support tubes for the chain to rest on along the length of the gate at approximately 1m spacing s and a...

Страница 5: ...ver the drive sprocket and under the other idler sprocket on the chain drive operator The chain can then be connected to each of the chain adjuster connector rods this is done by using the 4mm high te...

Страница 6: ...t indicator led s turn off when the corresponding limit switch is activated If they are the wrong way around swap the op and cl limit wires around To commission the gate move the gate to approximately...

Страница 7: ...and ramp times Automation settings operating modes can be adjusted via the CB6 board refer to manual for further instructions Once Inverter settings are appropriately set proceed to make final adjustm...

Страница 8: ...and any other safety devices to protect both equipment and personnel Extra caution should be employed when using operator in auto close mode Display any necessary signs to indicate any danger areas an...

Страница 9: ...When bringing power and control cables into the control enclosure inside the operator please leave enough slack in the cables in this way the enclosure can still be lifted up in order to see and work...

Страница 10: ...10 PLAN VIEW LAYOUT CONDUIT POSITION FRONT VIEW R H S VIEW TOP VIEW OF BASE CHASSIS...

Страница 11: ...r 7 Motor 2 Limit Switch Inputs not shown 8 Terminals for Isolated 24vAC Supply 21 Firmware Version Label for Limit Switch and Control Inputs 22 Light Control Relay Interface 9 Pedestrian Access Contr...

Страница 12: ...not exceed 30V A C D C 5Amps If an electromagnetic lock is used change one wire on the control board lock output to the normally closed output Use the light relay module if fitted to switch the applie...

Страница 13: ...a pre set pedestrian access time of 5 seconds which is intended to open the motor connected to M1 output only part way If these default times do not suit your needs simply use the procedure below to a...

Страница 14: ...nal MI2 Reverse close command input linked to MI3 for speed setting Terminal MI3 Closing Speed Multi Step speed command input Terminal DCM command output terminal used for common PARAMETER NUMBER PARA...

Страница 15: ...se led should start to flash if they are the wrong way around turn power off to the operator wait until the inverter powers down then swap over any 2 of the motor phase wire at the inverter Turn power...

Страница 16: ...16 6 CONTROL DIAGRAMS...

Страница 17: ...pened by hand To re engage the clutch move the gate by hand Into approx The half way position and turn the Knurled knob clockwise until it is very tight If when turning the knurled knob clockwise and...

Страница 18: ...y to ensure operator will not run inadvertently Gate rolls freely when in manual Gate wheels and guide rollers in good condition Gate stops are installed and in good condition not loose Gate chain is...

Страница 19: ...ing circumstances i If no proof of date of purchase can be produced ii If the product has been used in a manner beyond its design parameters iii If the product is tampered with or repaired by personne...

Отзывы: