13
SEW Program with LED fault indication
The fault status right hand led segment in P 35 will move up and down so many times according to what
state each input is in. Some earlier model operators had a red led mounted in the back plate of the operator
so the status of the operator could be seen without taking the cover off.
No of flashes
Fault description
1 flash Inverter fault other than fault 08
2 flashes Gate fully open and with open input held so gate won`t close
3 flashes
Gate fully open and with PE input fault so gate won`t close
4 flashes Operator manual release door open so gate won`t operate
5 flashes Gate at pedestrian open position and pedestrian input held so the gate will not close.
6 flashes Gate will do next move at slow speed because gate travel
Interrupted and previous run did not find the limit at the
Correct position
7 flashes Gate fully open and pedestrian input held so gate will not close.
8 flashes F 08 speed monitoring fault, motor can`t get to desired speed.
Check the following:
If unit is brand new, chances are the inverter has not been commissioned properly.
Check gate runs free in manual, track, wheels, guides, gate alignment.
Rack fitted correctly and meshing properly with pinion.
Clutch done up tight.
Clutch disks in good condition.
Track in good condition and no stones etc on or too close to track.
Both close and open stops in good condition.
If a brake motor, check to see if brake is releasing.
Check maximum speed and make sure opening speed
Does not exceed maximum speed.
If gate is extremely heavy, the ramp times may need to be
Increased to give the gate more time to reach its designated operating speed.
If gate is extremely heavy the low speed current setting may
To be increased. It can be adjusted from 60 percent to a Value less or equal to 80%.