GASMAX II + GDS-IR Operation & Maintenance Manual, Revision 1.1
Page 29
INPUT TYPE
indicates what kind of input or sensor the GASMAX II is configured to accept and is typically
pre-configured at the factory. When installed, Smart Sensors upload sensor type and other data to the
GASMAX II and this data may be viewed on the SMART SENSOR information screen.
NEW SENSOR
displays the date when a new sensor was last installed.
RECENT CAL
displays the most recent calibration date.
CLOCK / DELAY SETUP PAGE
The GASMAX II is equipped with a crystal-controlled, battery-backed real-time clock that maintains local
Time and Date. These values are factory preset to US Central Time and should be reset to correctly match
the current time zone during installation to make sure that time-stamped Event Log entries are correct.
Figure 7-7: Clock Delay Menu
TIME
adjusts time of day in hours, minutes and seconds.
DATE
adjusts date in month, day, year.
WARM UP DELAY
sets the amount of time from power-on until the 4-20mA output signal begins to
track the sensor output. Default setting is 60 seconds. Maximum value is 255 seconds.
CAL PURGE DELAY
sets the amount of time from the completion of span calibration until the 4-20mA
output signal restarts tracking the sensor output. The default setting is 60 seconds and the maximum
value is 255 seconds.
LCD CONTRAST ADJUSTMENT PAGE
The LCD Contrast Adjustment allows the display to be set for optimum viewing.
Figure 7-8: Contrast Menu
C L O C K / D E L A Y
S E T U P
T i m e
1 2 : 3 5 : 4 2
D a t e
0 4 / 2 2 / 0 4
W a r m
U p
S e c
1 2 0
C a l
P u r g e
S e c
1 0 0
C O N T R A S T
U P / D O W N
t o
c h a n g e
N E X T
t o
E X I T