GASMAX II + GDS-IR Operation & Maintenance Manual, Revision 1.1
Page 22
IR ZERO PROCEDURE
NOTE: This step should be performed initially and every 3 months for the first year, then every six months
thereafter. If not performing the IR Zero procedure, proceed to GASMAX CALIBRATION PROCEDURE shown
below.
1.
Using the NEXT key, select the
single channel display
on the GASMAX II that shows the IR output.
2.
Apply zero air to the cal gas inlet and wait 30 seconds for the zero air to completely fill the volume
inside the sensor.
3.
Press and hold the IR Zero button for 10 seconds, then release. If the sensor is local, use the magnetic
wand or built-in zero button on the GASMAX gas monitor. If the sensor is remote, use the magnetic
wand or built-in zero button on the GASMAX monitor or on the remote GDS-IR junction box.
4.
Once the IR Zero command is recognized, the GDS-IR output will momentarily drop and the message
“I ZE O” w
ill appear on the GASMAX display. Do not disconnect the zero air cylinder.
GASMAX CALIBRATION PROCEDURE
1.
For dual channel units, press the NEXT key on the GASMAX until that the DATA Display screen for the
GDS-IR channel is shown.
2.
Enter CAL MODE by pressing the DOWN / CAL key and within 5 seconds press the EDIT key. The
screen will display an APPLY ZERO message. With zero air still flowing to the GDS-IR, press the EDIT
key to complete the ZERO calibration.
3.
If the zero calibration value is within limits, a ZERO CAL SUCCESSFUL message is displayed, followed
by an APPLY SPAN message.
4.
Turn off the regulator and disconnect the zero air cylinder. Connect the span gas cylinder and turn on
the regulator to apply the SPAN gas.
5.
After the reading is stable, (approximately 1 minute, could be as long as 2-3 minutes) press the EDIT
key to complete the SPAN GAS calibration. If the SPAN calibration is within limits, the display shows
SPAN CAL SUCCESSFUL followed by REMOVE CAL GAS.
6.
Immediately shut off the regulator and disconnect the tubing and regulator. At the end of the CAL
PURGE delay, the GASMAX II output is re-enabled and the unit is fully operational.
NOTE
: A CAL MODE INFO SCREEN IS AVAILABLE TO VIEW CERTAIN CAL MODE PARAMETERS DURING
CALIBRATION. HOLD THE UP KEY FOR 5 SECONDS DURING CAL MODE TO DISPLAY THIS SCREEN.