the compressor still running. Add up to 90 minutes 


8.5.2 Conditions 

of defrost ending: 

Defrosting ends when either of the following : 
The time gets to 10 minutes; 
T3>20°c 

 
8.5.3  Time sequence of the whole defrosting procedure is as follows: 
 

Remark: when the evaporator pipe sensor temp. more than TE16, The indoor fan start to run. 

                       Defrost 10or 6minutes  
                                       
                                                55S                                                      55S             
      Compressor                                                                             
                                                                                                         
    4-way Valve                                                                                  50S 
                                              50S                                                             
  Outdoor Fan                        
                                                                                                             
  Indoor Fan 
 
                                            15S 

 
8.6    Auto mode 
8.6.1  When running in automatic mode, the air conditioner automatically selects one of the following 

operation modes: cooling, heating or ventilation according to the difference between room temp. (TA) 
and set temp. (TS). 

TA—TS Operation 

mode 

TA—TS>2  Cooling 
-1

TA—TS

+2  Air-only 

TA—TS<-1  

Heating (air-only for cooling only type) 

 
8.6.2  At auto mode, the indoor fan blows automatically in selected mode. 
8.6.3  One mode should be carried out for at least 15 minutes once selected. If the compressor cannot start 

for 15 minutes, reselect the operation mode according to the room temp. and set temp., or reselect 
when the setting temp. changed 

 
8.7    Economic mode 

Cooling: The set temperature rise 1  per hour. Two hours later, the set temperature will maintain as a 
constant and the air circulation is kept at low speed,and the air condition will stop work after 7 hours. 
Heating: The set temperature decrease 1  per hour. Two hours later, the set temperature will 
maintain as a constant and the air circulation is kept at low speed, and the air condition will stop work 
after 7 hours. (Cold air proof function takes priority over all). 

 
8.8 Manual 

operation 

 

Manual operation is controlled by touching buttons and divided into force cooling and 

forced auto mode. It transfers between these two modes by pressing the buttons, the 

cycling order of the button press is: 

                       

 

 
 
8.8.1   Forced Cooling 

Forced cooling 

Forced auto 

Remote mode 

8.8.1.1  In forced cooling mode, the remote signal is not accepted. 

 25

8.8.1.2  The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan mode is 

set as low, the A/C operates in the forced auto mode under the requirements of the forced auto 
mode. 

Содержание Elite Series

Страница 1: ...GD Midea Refrigeration Equipment Co Ltd SPLIT TYPE HEAT PUMP AIR CONDITIONERS Technical service manual 2005 Elite Series R22 Wall Mounted Models MSE 21CR MSE 21HR MSE 24CR MSE 24HR MSE 28CR MSE 28HR...

Страница 2: ...R22 Contents 1 Features 02 2 Specification 03 3 Dimensions 05 4 Refrigeration cycle diagram 07 5 Capacity table 08 6 Wiring diagram 13 7 Troubleshooting 17 8 Electronic function 23 9 Characteristic of...

Страница 3: ...2 1 Features 1 1Compact design 1 2LED display...

Страница 4: ...0 225 1080 330 225 1080 330 225 1080 330 225 Packing W H D mm 1165X445X320 1165X445X320 1165X445X320 1165X445X320 Net Gross weight Kg 17 22 17 22 17 22 17 22 Model YDK53 6D YDK53 6D YDK53 6D YDK53 6D...

Страница 5: ...Kg 17 22 17 22 Model YDK53 6D YDK53 6D Brand Welling Welling Input W 169 169 Capacitor uF 5 5 Speed r min 800 800 m3 h 2500 2500 dB A 57 57 Dimension W H D mm 845X695X335 845X695X335 Packing W H D mm...

Страница 6: ...3 Dimensions 3 1 Indoor unit MSE 21CR MSE 21HR MSE 24CR MSE 24HR MSE 28CR MSE 28HR 5...

Страница 7: ...3 2 Outdoor unit MSE 21CR MSE 21HR MSE 24CR MSE 24HR MSE 28CR MSE 28HR 12 5 6...

Страница 8: ...4 Refrigeration cycle diagram 7...

Страница 9: ...5 58 Sensitive capacity kW 4 14 4 19 4 15 4 08 4 04 4 06 32 C D 23 C W Input kW 2 00 2 22 2 44 2 66 2 88 3 10 5 2 MSE 21HR SUMMER OUTDOOR TEMPERATURE DRY Indoor Conditions 25 C 30 C 35 C 40 C 45 C 50...

Страница 10: ...OUTDOOR TEMPERATURE DRY Indoor Conditions 25 C 30 C 35 C 40 C 45 C 50 C Total capacity kW 6 57 6 25 5 81 5 34 4 90 4 57 Sensitive capacity kW 4 61 4 47 4 28 4 06 3 85 3 69 21 C D 15 C W Input kW 2 30...

Страница 11: ...2 4 75 4 51 4 30 27 C D 19 C W Input kW 2 34 2 58 2 80 3 05 3 29 3 52 Total capacity kW 7 98 7 80 7 69 7 42 7 08 6 73 Sensitive capacity kW 5 24 5 09 5 04 4 96 4 90 4 92 32 C D 23 C W Input kW 2 41 2...

Страница 12: ...sitive capacity kW 6 44 6 29 6 24 6 16 6 10 6 12 32 C D 23 C W Input kW 2 81 2 99 3 27 3 55 3 82 4 10 5 6 MSE 28HR SUMMER OUTDOOR TEMPERATURE DRY Indoor Conditions 25 C 30 C 35 C 40 C 45 C 50 C Total...

Страница 13: ...10 46 9 44 8 49 5 91 5 14 5 01 15 C Input kW 3 47 3 11 2 80 2 43 2 26 2 13 Capacity kW 9 92 9 02 8 25 5 68 5 33 4 96 18 C Input kW 3 55 3 11 2 85 2 58 2 49 2 17 Capacity kW 9 88 9 10 8 20 5 45 5 15 4...

Страница 14: ...DD 2 P25 3 P26 4 P00 5 P01 6 P02 7 P03 8 P04 9 VSS1 10 P05 11 P50 12 P51 13 P52 14 P53 15 AVDD 16 AVREF 17 ANI0 18 ANI1 19 ANI2 20 ANI3 21 ANI4 22 ANI5 23 AVSS 24 P10 25 P11 26 P30 27 P31 28 P32 29 P3...

Страница 15: ...VAC2 1 2 3 CN1 TRANS_OUT P 1 23 INTP0 P24 INTP1 2 P25 INTP2 3 AVDD 4 P60 AN10 5 P61 AN11 6 P62 AN12 7 P63 AN13 8 AVSS 9 P50 10 IC 19 X2 20 X1 21 VSS 22 VDD 23 P10 24 P11 25 P20 ASCK20 26 P21 TxD20 27...

Страница 16: ...C N 7 C N 5 Y G R E D Y G W H I T E B LU E FU S E 3 15A 250V F A N 1 TR A N S 1 C A P 1 X T 1 R T 2 R T 1 TOO U T D O O RU N I T U N I T1 1 S W I R I N GD I A G R A M I N D O O R U N I T X S 2 X P 2 C...

Страница 17: ...5 Y G R E D Y G W H I TE B LU E FU S E 3 15A 250V FA N 1 TR A N S 1 C A P 1 X T 1 R T 2 R T 1 TOO U TD O O R U N I T U N I T1 1 S W I R I N GD I A G R A M I N D O O R U N I T X S 2 X P 2 C N 8 C N 11...

Страница 18: ...mp Over current protection of the compressor occurs 4 times X Indoor fan speed has been out of control for over 1 minute X No over zero signal Temp sensor on indoor evaporator is open circuit or short...

Страница 19: ...it occur in C ool mode Check speed of outdoor motor Yes Check theover current protector of compressor No Replace the main PCB board Replace the compressor Recycle the refrigerant and recharge No Does...

Страница 20: ...play board Yes No Replace the display board Yes Yes Does the unit run in Forced Cool m ode Abnormaln oise from the indoor unit Does it happen in Fan Only mode Yes No Does it happ en with auto swing Ch...

Страница 21: ...ed out of balance or partially missing Loose screws Tighten them Motor failure Replace the motor if knocking sounds continue when running or loose or the motor hums or noise appears to be internal whi...

Страница 22: ...the inlet outlet wind flow of the unit Sunlight Add a awning if the outdoor unit is exposed to the sunlight Outdoor fan motor Check the fan capacitor on outdoor power control board and replace the boa...

Страница 23: ...l not perform Replace the reverse valve after checking the reason Water drainage failure Check the drainage pipe and repair if failure The indoor unit is incorrect installed Correct the installation i...

Страница 24: ...Indoor fan speed T 1 Low 1 T 4 Med Temp up T 5 High T 4 High 1 T 4 Med Temp down T 1 Low Anti freezing control to indoor evaporator Condition Temp Time Compressor Outdoor fan T TE6 On On Temp up T TE6...

Страница 25: ...ndoor exchanger temp down T TE4 Off Anti cold air protection 2 when the room temp satisfy the setting temp T evaporator pipe sensor temp Indoor fan speed T TE14 2 Low speed or stop Room temp up T TE14...

Страница 26: ...the operation mode according to the room temp and set temp or reselect when the setting temp changed 8 7 Economic mode Cooling The set temperature rise 1 per hour Two hours later the set temperature...

Страница 27: ...s indicates 8 8 2 2 The system performs control according to the remote control auto mode with a set temperature of 24 c 8 9 Timer 24 hours timer on or off 8 10 Protecting Function 8 10 1 Compress wit...

Страница 28: ...SEC 14A 14A 14A 14A I5MIN 20A 20A 20A 20A IFAN 22A 22A 22A 22A IRESTORE IDEFROST TE1 25 25 TE2 32 32 TE3 30 30 TE4 20 20 TE5 2 2 2 2 TE6 12 12 12 12 TE7 63 63 TE8 57 57 TE9 50 50 ANGLCOOL 67 67 67 67...

Страница 29: ...28CR MSE 28HR I3SEC 18A 18A I5MIN 24A 24A IFAN 26A 26A IRESTORE IDEFROST TE1 25 TE2 32 TE3 30 TE4 20 TE5 2 2 TE6 12 12 TE7 63 TE8 57 TE9 50 ANGLCOOL 67 67 ANGLHEAT 93 ANGLOFF 130 130 THDEFROST TMDEFRO...

Страница 30: ...1918 1 37 1988 26 9 5507 53 3 0707 0 35 2024 27 9 1245 54 2 959 1 33 3269 28 8 7198 55 2 8442 2 31 5635 29 8 3357 56 2 7382 3 29 9058 30 7 9708 57 2 6368 4 28 3459 31 7 6241 58 2 5397 5 26 8778 32 7 2...

Отзывы: