![GD Midea Refrigeration Equipment Elite Series Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/gd-midea-refrigeration-equipment/elite-series/elite-series_technical-and-service-manual_3893814025.webp)
24
8.4.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode.
8.4.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except
for the defrosting mode or the end of defrost.
8.4.3 Action
conditions
of compressor at heating mode: compressor must run for 4 minutes after starting
and then judge temperature. Meanwhile other protections are still valid.
Condition
Compressor
Outdoor
fan
T> Ts+4
Off
Off
Room temp. up
T<Ts+4 On
On
T< Ts+3
On
On
Room temp. down
T>Ts+3 Off
Off
8.4.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller,
Anti-cold wind function 1.
Condition
T= Indoor exchanger temp.
Indoor fan speed
T<TE1 Off
TE1<T<TE2 Low
speed
Indoor exchanger temp. up
T>TE2
Setting fan speed
T>TE3
Setting fan speed
TE4<T<TE3 Low
speed
Indoor exchanger temp. down
T>TE4 Off
Anti- cold air protection 2 ( when the room temp. satisfy the setting temp.)
T=evaporator pipe sensor temp.
Indoor fan speed
T<TE14+2
Low speed or stop
Room temp. up
T> TE14+2
Setting speed.
T> TE14
Setting speed.
Room temp. down
T< TE14
Stop after 15 seconds Low speed
Auto wind
Condition
T=Indoor Temp.-Setting Temp.
Indoor fan speed
T<2 Med.
speed
Room temp. up
T>2 Low
speed.
T> 0
Low speed.
Room temp. down
T<0 Med.
speed
Indoor evaporator high-temperature protection
Condition
T= Indoor exchanger temp.
Compressor Outdoor
fan
T<TE15=54
℃
On
On(high
speed)
TE15<T<TE8 On
On(low
speed)
TE8<T<TE7 On
Off
Indoor exchanger temp. up
T>TE7 Off
Off
T>TE9 Off
Off
Indoor exchanger temp. down
T<TE9 On
On
8.5 Defrosting mode
8.5.1 Conditions of defrost:
Defrosting starts when either of the following :
T3 lower than 0°c, lasts for more than 40 minutes, provided that the time period when the temperature
is lower than -3°c consecutively reaches 3 minutes.
Calculate from the end of latest defrost, evaporator high temp. protection only closes outdoor fan with