- 35 -
Australia A
Australia B
Australia C
New Zealand
Voltage
207V
44%supplying
215V
44%supplying
207V
60%supplying
205V
30%supplying
240V
0%
240V
0%
235V
0%
235V
0%
258V
60%absorbing
255V
60%supplying
244V
60%supplying
255V
40%supplying
220V
0%
230V
0%
220V
0%
220V
0%
Voltage
Voltage
Voltage
Inverter maximum ac�ve
power output level(P) % of S
rated
Inverter maximum ac�ve
power output level(P) % of S
rated
Inverter maximum ac�ve
power output level(P) % of S
rated
Inverter maximum ac�ve
power output level(P) % of S
rated
Default volt-var se�ngs for different regions are shown in the following table:
Reconnection Time
PF
60s
1.000
Grid Setting/Connect
Low frequency
Normal connect
48.00Hz
Low voltage
185.0V
High frequency
51.50Hz
Normal Ramp rate
10s
Reconnect Ramp rate
36s
High voltage
265.0V
Low frequency
Reconnect after trip
Low voltage
High frequency
51.30Hz
High voltage
263.0V
48.20Hz
187.0V
Grid
Set2
Normal connect
: The allowed grid voltage/frequency
range when the inverter first �me connect to the grid.
Normal Ramp rate
: It is the startup power ramp.
Reconnect a�er trip
: The allowed grid voltage
/frequency range for the inverter connects the grid
a�er the inverter trip from the grid.
Reconnect Ramp rate
:It is the reconnec�on power ramp.
Reconnec�on �me
: The wai�ng �me period for
the inverter connects the grid again
PF
: Power factor which is used to adjust inverter
reac�ve power
FW
: this series inverter is able to adjust inverter output
power according to grid frequency.
Droop F
: percentage of nominal power per Hz
For example, “Start freq F
>
50.2Hz, Stop freq F
<
51.5,
Droop F=40%P/Hz” when the grid frequency reaches
50.2Hz, the inverter will decrease its ac�ve power at
Droop F of 40%. And then when grid system frequency
is less than 50.1Hz, the inverter will stop decreasing
output power.
For the detailed setup values, please follow the local
grid code.
Grid Setting/F(W)
F(W)
Start freq F
Over frequency
50.20Hz
Start delay F
0.00s
Stop freq F
51.5Hz
Droop F
40
%P/Hz
Stop delay F
0.00s
Start freq F
Under frequency
49.80Hz
Start delay F
Stop freq F
49.80Hz
Droop F
40
%PE/Hz
Stop delay F
0.00s
0.00s
Grid
Set4
Over voltage U>(10 min. running mean)
Grid Setting/IP Protection
260.0V
Set3
Grid
--
HV1
265.0V
0.10s
--
HV2
265.0V
0.10s
HV3
--
LV1
185.0V
0.10s
--
LV2
185.0V
0.10s
185.0V
LV3
--
HF1
51.50Hz
0.10s
--
HF2
0.10s
HF3
--
LF1
48.00Hz
0.10s
--
LF2
0.10s
LF3
①
②
①
②
0
.
10s—Trip �me.
LV1:
Level 1 undervoltage protec�on point;
LV2:
Level 2 undervoltage protec�on point;
LV3
: Level 3 undervoltage protec�on point.
HV1:
Level 1 overvoltage protec�on point;
HV2:
Level 2 overvoltage protec�on point;
HV3
: Level 3 overvoltage protec�on point.
HF1:
Level 1 over frequency protec�on point;
HF2:
Level 2 over frequency protec�on point;
HF3
: Level 3 over frequency protec�on point.
LF1:
Level 1 under frequency protec�on point;
LF2:
Level 2 under frequency protec�on point;
LF3
: Level 3 under frequency protec�on point.
265.0V
51.50Hz
51.50Hz
48.00Hz
48.00Hz