- 34 -
Default volt-wa� se�ngs for different regions are shown in the following table:
Australia A
Australia B
Australia C
New Zealand
Voltage
253V
100%
253V
100%
242V
100%
250V
100%
260V
20%
260V
20%
250V
20%
260V
20%
215V
100%
215V
100%
224V
100%
215V
100%
207V
20%
207V
20%
216V
20%
195V
0%
Voltage
Voltage
Voltage
Inverter maximum ac�ve
power output level(P) % of S
rated
Inverter maximum ac�ve
power output level(P) % of S
rated
Inverter maximum ac�ve
power output level(P) % of S
rated
Inverter maximum ac�ve
power output level(P) % of S
rated
5.8.2 Grid Standard Selec�on
For The Australian Market:
For compliance with AS/NZS 4777.2:2020 please select from
• Australia A • Australia B • Australia C • New Zealand
Please contact your local grid operator for which op�on to select
Note: By selec�ng Australia A, Australia B or Australia C the power quality response mode and grid
protec�on se�ngs will be reset to their default values for Australia RegionA, B, C respec�vely.
Grid Mode:
General Standard
、
UL1741 & IEEE1547
、
CPUC RULE21
、
SRD-UL-1741
、
CEI 0-21
、
Australia A
、
Australia B
、
Australia C
、
EN50549_CZ-PPDS(>16A)
、
NewZealand
、
VDE4105
、
OVE-Direc�ve R25.
Please follow the local grid code and then choose the
corresponding grid standard.
Grid level
: there’re several voltage levels for the inverter
output voltage when it is in off-grid mode.
LN:230VAC LL:400VAC,LN:240VAC LL:420VAC
,
LN:120VAC LL:208VAC
,
LN:133VAC LL:230VAC.
IT system
: For the IT grid system, the Line voltage
0/11
Grid Setting/Grid code selection
Grid Mode
Grid Level
0/120/240
0/240/120
Grid
Set1
Grid Frequency
50HZ
60HZ
General Standard
Phase Type
IT system-neutral is not grounded
LN:220VAC LL:380VAC
U
V
W
220VAC
Rz
Rz: Large resistance ground resistor. Or the system doesn’t have Neutral line
220VAC 220VAC
N
is IT system, please enable “IT system” and �ck the “Grid level” as 133-3P as below picture shows.
(between any two lines in a three-phase circuit) is 230Vac, and the diagram is as follow.If your grid system
Содержание RY-12K-AUP3
Страница 5: ...03 2 2 Product Size Inverter Size Moun ng bracket...
Страница 12: ...Temp CT 11 1 2 3 3 3 Temperature sensor connec on for lead acid ba ery Inverter...