background image

3

3.4 Electrolyte
The electrolyte for 

 NiCd batteries consists of a diluted 

potassium hydroxide (KOH) solution (specific gravity 1.20 kg/litre 

+/-0.01 kg/litre) with a lithium hydroxide component, in accordance 

with IEC 60993:1989. The potassium hydroxide solution is prepared 

in accordance with factory regulations. The specific gravity of the 

electrolyte does not indicate the state of charge of the battery. The 

specific gravity changes very little during charging and discharging, 

and has limited relationship to the temperature.
When checking the electrolyte levels, a variation in level between 

cells is not unusual and is due to the different quantity of gas held 

in the separators of each cell. Before the battery is put into service 

for the first time, check that the electrolyte level is not lower than 

10mm below the “MAX” mark. There is usually no need to adjust 

it. 
If the electrolyte level is lower than the “MIN” level during service, 

the battery should not be disconnected from the charger for a time 

longer than 12 hours.
If visual inspection is not possible, due to restricted view, use 

an electrolyte level testing tube to check the electrolyte level. 

For further instructions, please contact your GAZ/EnerSys 

representative. 
GAZ 

 cells fulfil the requirements of IEC 62259:2003, para 

7.9 for gas recombination efficiency. 

 

3.5 Commissioning
The following instructions are valid for commissioning between 

+20°C and +30°C. For different conditions please contact GAZ. 

Charging with constant current is the preferred method.

If a site test is requested, it must be carried out in accordance with 

IEC 62259:2003.

According to IEC 62259:2003, 0.1 C

5

 A is also expressed as 0.1 I

t

 A. 

The reference test current It is expressed as: 

Example:
0.1 I

t

 A means:  

10 A for a 100 Ah battery or

50 A for a 500 Ah battery

3.5.1 Commissioning with contant current

 cells stored up to 6 months:

A commissioning charge is normally not required and the cells 

are ready for service. If full performance is necessary immediately, 

a commissioning charge of 10 hours at 0.1 I

t

 A is recommended. 

This procedure is carried out without the red low-pressure vents 

installed. 

During the charge the temperature should be checked 

(see section 5). 

 cells stored for more than 6 months up to 1 year:

A commissioning charge of 15 hours at 0.1 I

t

 A is necessary. 

This procedure is carried out without the red low-pressure vents 

installed.

During the charge the temperature should be checked 

(see section 5).

3.5.2 Commissioning with constant voltage
A commissioning charge is normally not required and the cells are 

ready for service. If the charger´s maximum voltage setting is too 

low to supply constant current charging, divide the battery into two 

parts and charge them individually.

 cells stored up to 6 months:

A commissioning charge is normally not required and the cells 

are ready for service. If full performance is necessary immediately, 

a commissioning charge of 20 hours at 1.65 V/cell with current 

limited to 0.1 I

t

 A is recommended.

This procedure is carried out without the red low-pressure vents 

installed.

During the charge the temperature should be checked 

(see section 5).

 cells stored more than 6 months and up to 1 year:

A commissioning charge of 30 hours at 1.65 V/cell with current 

limited to 0.1 I

t

 A is necessary.

This procedure is carried out without the red low-pressure vents 

installed.

During the charge the temperature should be checked 

(see section 5).

In the case of variable charging conditions, please consult your 

GAZ

®

 representative.

3.5.3 Commissioning at ambient temperature above +30°C

Constant current charging is the only appropiate method for 

commissioning under such temperature conditions. During the whole 

process the electrolyte temperature must be monitored. 

The electrolyte temperature should never 45°C. 

On exc45°C the charging should be temporarily interrupted 

until the electrolyte temperature drops to +40°C. 
Duration:   

20 hours

Charging current:  0.1 I

t

 A

In case of any interruption during the commissioning process, the total 

charge time must be extended by the duration of the downtime. 

4. Charging in operation

Do not open or remove the low pressure vent caps during 

operation. The charging current limit should be 0.1 I

A maximum in 

general.
In order to reduce the water consumption it is recommended, but 

not obligatory to adjust the charge voltage.
Operation in high 

temperature area (>35°C):  Temperature coefficient of -2 mV/K
Operation in low 

temperature areas (<20°C):  Temperature coefficient of -3mV/K
Recommended charging voltages for ambient temperatures from 

+20°C to +35°C are:
Two step charge
Float charge: 

1.40-1.42 V/cell

Boost charge:  

1.45-1.46 V/cell

Current limitation:  

0.1 I

t

 A

Single step charge
Charging voltage: 

1.42-1.44 V/cell

Current limitation: 

0.1 I

t

 A

5. Periodic maintenance

GAZ

®

 

 cells require a minimum amount of maintenance. 

In order to maintain maximum performance, the following is 

recommend: 

Standard service inspection:
In a regular twelve month period, carry out a check-up under 

normal float conditions. Depending on site location, local 

regulations, or special application requests, these check-ups can 

vary in frequency or period.

When performing the standard service inspections please be sure 

to carry out the following:
•  General appearance and cleanliness of all the batteries and the 

battery room.

 

The battery must be kept clean using only water. Do not use a 

wire brush or solvents/additives of any kind. Ventilation must 

fulfill the requirements of section 3.2.

C

n

  Ah 

1h

I

t

 A=

Содержание lomain KGL P Series

Страница 1: ...Visit us at www enersys com Battery Installation Operation and Maintenance Instructions NEXT GENERATION OF BATTERIES KGM P KGL P Visit us at www enersys com ...

Страница 2: ... battery do not place tools or items on top of the battery Handling DataSafe XE batteries are supplied in a charged condition and are capable of extremely high short circuit currents Take care to avoid short circuiting terminals of opposite polarity California Proposition 65 Warning Battery posts terminals and related accessories contain lead an cause cancer and reproductive harm Wash hands after ...

Страница 3: ...onstant current charging divide the battery into two parts and charge them individually cells stored up to 6 months A commissioning charge is normally not required and the cells are ready for service If full performance is necessary immediately a commissioning charge of 20 hours at 1 65 V cell with current limited to 0 1 It A is recommended This procedure is carried out without the red low pressur...

Страница 4: ...ions Only use distilled or deionized water to top up the cells in accordance with IEC 60993 1989 NOTE Once the battery has been filled with the correct electrolyte at the factory there is no need to regulary check the electrolyte density Interpretation of density measurements is difficult and could lead to misunderstandings Electrical parameters Check the float voltage measurements of every single...

Страница 5: ...n Plugs and Fitting of Vent Caps KGL 12 440 P KGM 11 400 P KGL 500 1570 P KGM 450 1560 P Step 1 before commissioning charge Step 1 before commissioning charge Step 2 after commissioning charge Step 2 Step 3 after commissioning charge ...

Страница 6: ...35 P KGM 11 30 P KGL 45 60 P KGM 40 55 P 1 2 3 4 5 Cell container Cell connector Spring washer Hexagonal screw Connector cover 1 2 3 4 5 Cell container Cell connector Spring washer Hexagonal screw Connector cover Note typical layout only Refer to section 9 for details KGL 12 35 P KGM 11 30 P 1 Cell 2 Cell connector 3 Spring washer 4 Nut 5 Connector cover 8 Layout details inter cell connection KGL ...

Страница 7: ...r 4 Spring washer 5 Screw 6 Connector cover 7 End terminal connector 8 Cover end terminal connector 7 Note typical layout only Refer to section 9 for details KGL 70 440 P KGM 65 400 P 1 Cell 2 Cell connector 3 Spring washer 4 Screw 5 Connector cover 1 5 4 3 2 1 5 4 3 2 6 7 8 ...

Страница 8: ... KGL 45 P KGL 60 P Male thread M10 KGL 665 P KGL 835 P Female thread M10 KGL 70 P KGL 275 P Female thread M8 KGL 890 P KGL 1110 P Female thread M10 KGL 300 P KGL 440 P Female thread M10 KGL 1260 P KGL 1570 P Female thread M10 Cells assembled in a 2 row configuration 9 Cell Layout ...

Страница 9: ... M10 KGM 65 P KGM 250 P Female thread M8 KGM 270 P KGM 400 P Female thread M10 KGM 450 P KGM 570 P Female thread M10 KGM 600 P KGM770 P Female thread M10 KGM 800 P KGM 1130 P Female thread M10 KGM 1250 P KGM 1350 P Female thread M10 Cells assembled in a 2 row configuration ...

Страница 10: ...ing 11 03 Singapore 189721 Tel 65 6508 1780 EnerSys World Headquarters 2366 Bernville Road Reading PA 19605 USA Tel 1 610 208 1991 1 800 538 3627 EnerSys EMEA EH Europe GmbH Baarerstrasse 18 6300 Zug Switzerland 2017 EnerSys All rights reserved Trademarks and logos are the property of EnerSys and its affiliates unless otherwise noted Contact ...

Отзывы: