11. Precautions before Installation
■ Installation Height: 1,000 M below sea level
■ Relative Humidity: 5% ~ 99% (Non-condensing)
■ Installation Site: Indoor and Outdoor
■ Explosion Ignition Group for Target Gas or Vapor: Ex d IIC T6
■ During wiring work, use explosion-proof cable gland at cable inlet or tightly seal cable conduit during metal cable wiring
construction to prevent spread of flames in case of explosion or movement of gas, etc. through the cable conduit within
50 mm. All materials including materials used for sealing of unused inlets must have safety certificates!
■ When connecting the equipment with cable, screw thread must be tightened 5 threads or more.
■ Work in conditions satisfying other [Standards for Selection, Installation, and Maintenance, etc. of Explosion-proof Electric
Machine and Equipment Wiring, etc. at Work Site]