background image

www.gastron.com

10

_

11

4.1. Components

No

NAME

DESCRIPTIONS

9

Reset Key

To cancel or return to the previous status during Parameter setting, use the Magnet-Bar and 
touch once.
(Each touch returns to the previous status by one unit.)

10

↑(UP) Key

During conversion of mode or number, use the Magnet-Bar and touch once. Each touch converts 
or increases displayed value by one unit.

11

↓(DOWN) Key

During conversion of mode or number, use the Magnet-Bar and touch once. Each touch converts 
or increases displayed value by one unit.

12

External Earth Ground

It must be grounded to ourside of detector for protection from external noise or strong electric 
field.
Use a conductor that is 4 mm or longer when coupling ground line.

13

Mount Hole

Hole to fix the gas detector on external wall or other installation sites.

14

Sensor

It is a site that detects actual gas leak. It converts the amount of gas leak into electrical signal and 
transmits to the Main PCB.

15

Conduit Connection

It is supplied for inlet of power supply and measurement output signal for the detector during 

installation. For cable inlet, PF or NPT 3/4", 1/2" are prepared.

16

Internal Ground

It must be grounded to inside of detector for protection from external noise or strong electric 
field.
Use a conductor that is 4 mm or longer when coupling ground line.

17

FRONT CASE

It is an explosion-proof case made of explosion-proof plastic and emits LED light externally 
through transparent window.

18

CASE RING

It serves as a cover to prevent deviation of front case.

19

SEXANGLE BOLT

It serves to prevent deviation after case ring assembly and is fixed by mood bolt.

20

CASE BODY

It is the main body that protects internal buzzer and other parts by body.

21

BUZZER

It receives signal upon an event of error and generates warning sound.

22

FIXED RING

It prevents deviation of sinter filter upon external shock.

23

FLAME ARRESTER

It blocks flow in of dust, debris, water, gas and delivers warning sound from the buzzer to 
outside.

24

ARREST CAP

It protects sinter filter from external shock.

25

LED COVER

It is a joint for LED PCB ASS'Y and covered with moulding.

26

LED PCB ASS’Y

It is a multi-color LED that displays status.

27

NUT

It serves to fix parts to the compliment part.

28

SHAFT BODY

It serves to fix parts to the opponent.

29

CABLE WIRE

It supplies power and transmits data.

[Table 1. GTD-2000ExW Transmitter Components Description]

GTD-2000ExW

Instruction Manual

4.2. LAMP Function Description

■ In normal status, green LED lights on and buzzer does not ring.

■ When Alarm-1 signal is received, red LED flickers in 1 sec interval and buzzer rings in 1 sec interval.

■ When Alarm-2 signal is received, red LED lights on and buzzer rings continuously.

■ When Trouble signal is received, yellow LED lights on and buzzer does not ring.

4. Name and Description of Each Part

4. Name and Description of Each Part

Содержание GTD-2000Ex

Страница 1: ...vance d Industry 1 ro Bugok dong Gunpo si Gyeonggi do Tel 82 31 490 0800 Fax 82 31 490 0801 Yeongnam business office Plant 55 Gonghangap gil 85beon gil Gangseogu Busan Metropolitan City Tel 51 973 8518 Fax 51 973 8519 E mail info gastron com www gastron com Read in detail for correct use ...

Страница 2: ...y when the calibration period is not specified The product and manual are subject to change without a notice for the product s functional improvement and ease of use For a precise operation of the gas detector please perform an inspection and a calibration at least once per 6 months In reference to KOSHA GUIDE P 135 6 2018 7 2 In house inspection section 2 For a precise operation of the gas detect...

Страница 3: ...vision History 32 1 Overview 6 2 Configuration 6 3 Specifications 7 3 1 Basic Specification 7 3 2 Mechanical Specifications 7 3 3 Electrical Specifications Standard Type 8 3 4 Environmental Specifications 8 4 Name and Description of Each part 9 4 1 Components 9 4 2 LAMP Function Description 11 5 Installation 12 5 1 Detachment of Housing Cover 12 5 2 Main PCB Configuration 13 5 2 1 Wiring for 4 20m...

Страница 4: ... and high pressure explosion proof small warning light made of SUS materials It uses magnet bar outside the main body of detector enabling calibration from the outside of the detector thus maintenance is convenient 2 Configuration Figure 1 GTD 2000ExW Overview Gas Sensor Module GSA860EX Main Board Transmitter 24V DC 4 20mA Analog Signal Output Display Board User Interface Transmitter enclosure GDH...

Страница 5: ... 3 MAIN PCB Amplifies fine outputs generated from Sensor Element to transmit a converted output in 4 20 mA DC standard It sends data to display part 4 Display PCB Displays data measurement sent from Main Terminal Transmitter PCB on LCD and displays power status with a power lamp 5 Power Signal Terminal CN8 consists DC18V 31 24 V power supply and DC 4 20 mA standard output connection terminal VISO ...

Страница 6: ...ASE It is an explosion proof case made of explosion proof plastic and emits LED light externally through transparent window 18 CASE RING It serves as a cover to prevent deviation of front case 19 SEXANGLE BOLT It serves to prevent deviation after case ring assembly and is fixed by mood bolt 20 CASE BODY It is the main body that protects internal buzzer and other parts by body 21 BUZZER It receives...

Страница 7: ...trical current is flowing Turn the slotted set screw M4 x 1ea fixing the cover part of main body 3 4 turns counter clockwise ccw using a hex wrench M2 then turn the cover of gas leak detector ccw to detach the cover When the cover is detached LCD appears After detaching the cover disassemble the display parts as below Push in left and right fixing rings located on front side of LCD at the same tim...

Страница 8: ... CN8 Terminal Configuration Table 3 CN8 Terminal Detailed Description NO PCB SILK PIN NAME DESCRIPTION 4 20mA Source Drive J1 Jumper ON 4 20mA Sink Drive J1 Jumper OFF 1 VISO VIS N C 4 20mA Sink In 2 24V 24V POWER 3 mA mA 4 20mA Source Out 4 20mA Sink Out 4 GND GND POWER 5 ETH ET EARTH Use CVVS or CVVSB 2 0sq Shield Cable for terminal configuration To connect 4 Pin terminal from the existing old G...

Страница 9: ...OP Maximum Power Loop Voltage Drop Power Supply voltage min operating voltage IMAX Max Current of GTD 2000ExW WIRER m The resistance of the wire ohms meter value available in wire manufacturer s specification data sheet Example of installation lengths using 24 V power supply and 16 AWG is as follows GTD 2000ExW minimum operating voltage 18 Vdc VMAXDROP 24 18 6V IMAX 0 2A 200mA 6 0 2 0 01318 2 2276...

Страница 10: ...ously run until it is released using the reset key LEL ALARM1 LEL OVER When gas measurement larger than 10 of set high scale value OVER displays in 1 sec interval At this time 4 20 mA runs as 22 mA LEL UNDER When gas measurement smaller than 10 UNDER displays in 1 sec interval and 4 20 mA runs below 2 mA The following function only runs when UNDER is on FAULT1 SEN EMPT When trouble occurs in the d...

Страница 11: ...hat sets gas name type and contacting or key changes gas type DEFIN USER DEFIN Is acronym for Define and is selected when using built in setting of gas name USER is selected when the user directly sets a gas name When a desired gas type is displayed contact FUNC key to set the gas name and enter Program Mode GAS SEL COMB Mode that sets gas name and contacting or key changes gas name When gas type ...

Страница 12: ...ODE Contact or key to select Calibration Mode Contact FUNC key when CALIBRA MODE is displayed to enter Calibration Mode Contact RESET key to return to Measuring Mode CALIBRA SPAN Contact or key to achieve SPAN then contact FUNC key to enter Span Calibration Mode SPAN CAL NO Contact or key to achieve YES then contact FUNC key to perform Span Calibration SPAN GAS 50 Using a calibration tool inject t...

Страница 13: ...aneous malfunction of detector due to external shock and noise other than from normal operation and time can be set in a range between 0 60 sec For Alarm1 dwell time setting press or key to increase or decrease in unit of 1 sec respectively When a desired Alarm 1 dwell time is displayed press FUNC KEY to set it and enter the next item Ex Alarm threshold value 20 LEL Delay time When it is at 5 sec ...

Страница 14: ... ADC FAULT7 H W REV H W Version Error Defective MPU inside Transmitter FAULT8 SEN HUNT When there is repeated hunting error in gas measurement sensor output status may be poor or check for input power noise Table 5 Fault List 8 2 Recovery List Table 6 Recovery List NO CAUSE SOLUTION 1 Defective Sensor Module Connection 1 Check Sensor Connection and Connection status of the Connector 2 Change Senso...

Страница 15: ... GTD 2000ExW Instruction Manual 9 2 Warning Light GTL 100 9 3 When Connecting Warning Light Figure 13 GTL 100 Drawing Figure 14 GTD 2000Tx Warning Light Connection Drawing 9 Drawings and Dimensions 9 Drawings and Dimensions ...

Страница 16: ...th electrical barriers such as rain water etc It is recommended to be installed in areas that are easier to work in since regular maintenance is needed Avoid areas with vibration or shock since they can affect output values Sensor part must be installed towards the direction of gravity This equipment has explosion proof construction for internal pressure and belongs to GROUP II for gas and vapor i...

Страница 17: ...www gastron com 32_33 GTD 2000ExW Instruction Manual VERSION CONTENTS DATE 0 1 Manual Initial Revision 2017 09 29 11 Revision History ...