www.gastron.com
08
_
09
4. Name and Description of Each Part
3.3. Electrical Specifications (Standard Type)
ITEMS
SPECIFICATION
Input Voltage(Standard)
※ Customer supplied PSU must meet
requirements IEC1010-1 and CE
Marking requirements.
Absolute min:
Nominal:
Absolute max:
Ripple maximum allowed:
18V
24V
31V
1V pk-pk
Wattage
Max. wattage:
Max. current:
3.6W @+24 VDC
150mA @+24 VDC
Analog output Current
0-20mA(500 ohms max load)
All readings ± 0.2mA
Measured-value signal:
4mA(Zero) to 20mA(Full Scale)
Fault:
0-100% LEL:
100-109%LEL:
Over 110% LEL:
Maintenance:
0mA
4mA - 20mA
20mA - 21.4mA
22mA
3mA
Analog output current ripple & noise max
±20uA
Wiring requirement
Power
CVVS or CVVSB with shield
Analog
CVVS or CVVSB with shield
Cable Connection Length
Analog
2500m
RS-485
1000m
EMC Protection:
Complies with EN50270
3.4. Environmental Specifications
ITEMS
SPECIFICATION
Operation Temperature
Transmitter
-20 to 50 ℃
Sensor
Refer to Sensor Specification
Storage Temperature
Transmitter
-20 to 50 ℃
Sensor
Refer to Sensor Specification
Operation Humidity
Transmitter
5 to 99% RH (Non-condensing)
Sensor
Refer to Sensor Specification
Pressure Range
90 to 110KPa
Max. air velocity
6m/s
3. Specification
GTD-1000Tx(M)
Instruction Manual
4.1. Components
[Figure 2. GTD-1000Tx(M) Components]
NO
NAME
DESCRIPTIONS
1
Housing Body
Protects PCB Board built in Sensor and Housing from external environmental change and shock.
2
Housing Cover
It is assembled with detector housing body and protects PCB Board built in Sensor and Housing from
external environmental change and shock
3
Sensor
It is a site that detects actual gas leak. It converts the amount of gas leak into electrical signal and
transmits to the Main PCB.
4
Internal Ground
It must be grounded to inside of detector for protection from external noise or strong electric field.
- Use a conductor that is 4 mm or longer when coupling ground line.
5
External Earth Ground
It must be grounded to outside of detector for protection from external noise or strong electric field.
- Use a conductor that is 4 mm or longer when coupling ground line.
6
Conduit Connection
It is supplied for inlet of power supply and measurement output signal for the detector during
installation. For cable inlet, PF or NPT 1/2", 3/4" are prepared.
7
Main PCB
Amplifies fine outputs generated from Sensor Element to transmit a converted output in 4~20 mA
DC standard. It sends data to display part.
8
Mount Hole
Hole to fix the gas detector on external wall or other installation sites.