F-Guard IR3 HD User Manual
Approvals
Note: All items are designed and tested to meet the relevant requirements.
•
Explosion proof:
o
ATEX: II 2 G D
Ex db IIC T5 Gb or Ex db eb IIC T5 Gb and Ex tb IIIC T95°C Db -
55°C<Ta<75°C
Ex db IIC T4 Gb or Ex db eb IIC T4 Gb and Ex tb IIIC T105°C Db -
55°C<Ta<85°C
o
IECEx, PESO:
Ex db IIC T5 Gb or Ex db eb IIC T5 Gb and Ex tb IIIC T95°C Db -
50°C
≤
Ta
≤
75°C
Ex db IIC T4 Gb or Ex db eb IIC T4 Gb and Ex tb IIIC T105°C Db -
50°C
≤
Ta
≤
85°C
o
FM & FMC:
Class I, Div. 1, Groups B, C & D; T4 Ta = -50°C
≤
Ta
≤
85°C or T5 Ta = -
50°C
≤
Ta
≤
75°C
Class II/III, Div. 1, Groups E, F, G; T4 Ta = -50°C
≤
Ta
≤
85°C or T5 Ta = -
50°C
≤
Ta
≤
75°C
Class I, Zone 1, AEx/Ex db IIC T4 Gb or Class I, Zone 1, AEx/Ex db eb IIC T4 Gb
T4 Ta = -50°C
≤
Ta
≤
85°C or T5 Ta = -50°C
≤
Ta
≤
75°C
and
Zone 21, AEx/Ex tb IIIC T95°C Db -50°C
≤
Ta
≤
75°C or
Zone 21, AEx/Ex tb IIIC T105°C Db -50°C
≤
Ta
≤
85°C
•
Performance:
o
ANSI FM 3260
o
EN 54-10
•
Functional safety: Meets the requirements for SIL 2 per IEC 61508.
•
MED B&D issued by DNV GL:
Temperature Class D; Vibration Class A; EMC Class B and Humidity IP68
•
California Fire Marshall
•
EAC CU TR
Electromagnetic Compatibility
The detector fully complies with EMC directive 2014/30/EU and is protected against interference
caused by RFI and EMI. The cables to the detector must be shielded and the detector must be
grounded to comply with the EMC directive.