D-Guard
2
63
24.
APPENDIX G:
24.1.
Performance Specifications
24.1.1
General Specifications
24.1.2
Methane Detector Specifications
Parameter
Specification
SS-1
Gas Type
Methane INFRA-RED
SS-2
Detection ranges
0 – 5% v/v, 0 – 100% v/v
SS-3
Sensor technology
NDIR Infra-Red
SS-4
Sensor Size
20mm diameter
SS-5
Sensor Life
>10 Years
SS-6
Calibration method
2 point, zero, full-scale
SS-7
Accuracy (scale and linearity)
To AS2290.3, ANZ60079.29 and AS4641
SS-8
Stated accuracy temperature limits
0°c to +40°C
SS-9
Operating temperature limits
-10°C to +40°C
SS-10
Operating humidity range
0% to 98%
SS-11
Operating pressure range
80kPa to 120kPa
SS-12
Humidity/Condensation effects
Negligible
SS-13
Long term drift
Zero: Less than specified by 61779.2 over 3 months
Sens: Less than specified by 61779.2 over 3 months
SS-14
Cross Sensitivity
CO: none. NO: none. H
2
: none
SS-15
Response time
T90: <=22 seconds
SS-16
Environmental protection
Replaceable hydrophobic membrane (part of enclosure).
Parameter
Description / Conditions
Limits
Units
Min
Max
GS-1
Measurement Techniques
Electro-Chemical Cell, Infra-Red.
-
-
-
GS-2
Target Gas
Depends upon model (see table 2 – gas types and ranges).
-
-
-
GS-3
Full Scale Ranges
Depends upon model (see table 2 – gas types and ranges).
-
-
-
GS-4
Measurement Accuracy
Refer to Sensor Performance tables.
GS-5
Maximum Loop Current
Under any condition of operation or fault.
-
30
mA
GS-6
Minimum Supply Voltage at 20mA
Minimum operating voltage at detector
13.0
-
VDC
GS-7
Maximum Supply Voltage (Ui) Group I variant
Group I maximum input voltage entity parameter (Ui).
-
22
VDC
GS-8
Maximum Loop Resistance. Group I variant
At Vpsu = Ui = 22V with backlight (see graph).
-
380
Ohms
GS-13
Maximum Supply Voltage (Ui) Group II variant Group II maximum input voltage entity parameter (Ui).
-
28
VDC
GS-14
Maximum Loop Resistance. Group II variant
At Vpsu = Ui = 28V with backlight (see graph).
-
720
Ohms
GS-16
Absolute Maximum Supply Voltage
Maximum supply voltage no damage to electronics (All versions)
-
30
VDC
GS-17
Loop Error Signal (low – electronics fault)
Detected faults within hardware or software
-
3.3
mA
GS-18
Loop Error Signal (low – sensor fault)
IR Head failure
3.3
mA
GS-19
Display
Graphical display 400 pixels by 240 pixels. High contrast type
-
-
-
GS-20
Temperature Sensor
Semiconductor temperature sensor
-20
+110
ºC
GS-21
Pressure sensing – Ambient (optional)
MEMS based absolute value. Instrument body and head.
50
115
kPa
GS-22
Sensor keep-alive battery (optional)
3.6V 55mAH lithium coin cell. PCB mounted ‘encapsulated’
GS-23
Digital Communications
HART 7.0 over 2-wire current loop (refer separate specification)
Содержание D-Guard2
Страница 2: ...D Guard2 1 This Page Left Intentionally Blank ...
Страница 65: ...D Guard2 62 23 APPENDIX F 23 1 System Menu Map ...
Страница 68: ...D Guard2 65 25 APPENDIX H Product Certificates 25 1 IECEx Product Certificate ...
Страница 69: ...D Guard2 66 ...
Страница 70: ...D Guard2 67 ...
Страница 71: ...D Guard2 68 ...
Страница 72: ...D Guard2 69 25 2 ATEX Product Certificate ...
Страница 73: ...D Guard2 70 ...
Страница 74: ...D Guard2 71 ...
Страница 75: ...D Guard2 72 ...
Страница 76: ...D Guard2 73 26 APPENDIX I Product Dimensions ...
Страница 77: ...D Guard2 74 Doc_Rev 03 12 15 ...