D-Guard
2
46
The default state for HART communications is OFF.
Use the up or down soft-keys to toggle the setting between
'ON and 'OFF'.
Once a change is made the save icon will show. Operate the
'save' soft-key to commit the changes to configuration
memory.
Following the save, the detector will reboot.
13.3.3
HART Tag data
13.3.4
HART Tag data – fixed loop mode
Navigating to the 'VIEW HART TAGS' screen allows the
detector ID strings to be viewed (read only), along with other
relevant HART related parameters. For full details, refer to the
D-Guard
2
HART implementation manual.
The present communication operating mode of the
detector’s is reflected in the screen top banner.
‘Variable’ indicates that the detector is set for ‘point to
point’ operation. If the detector is operating in ‘multi-
drop mode’, the fixed current loop value is indicated.
13.4.
System Configuration
The system configuration screen allows configuration of the detector in a general sense, such as detector isolation.
System Setup is accessed from the Quick-Nav Screen
13.4.1
SYSTEM Setup Main Screen
To access the SYSTEM data setup, unlock the menu and
operate the 'SYSTEM' soft-key.
The main SYSTEM setup page displays the features that may
be configured by the user.
The 4-20mA output settings are also accessed from this menu
location.
Operate the ‘SET 4mA’ key to setup the loop current.
Operate the 'SETTINGS' soft-key to start system
configuration.
13.4.2
Turning Detector Isolation On or OFF
The default state for isolation is OFF.
Use the up or down soft-keys to toggle the setting between
'NOT ISOLATED and 'ISOLATED'.
Once a change is made the save icon will show. Operate the
'save' soft-key to commit the changes to configuration
memory.
When isolated, the output current is fixed at 3.3mA.
The main measurement screen indicates a clear message that
the detector is in isolate mode.
Содержание D-Guard2
Страница 2: ...D Guard2 1 This Page Left Intentionally Blank ...
Страница 65: ...D Guard2 62 23 APPENDIX F 23 1 System Menu Map ...
Страница 68: ...D Guard2 65 25 APPENDIX H Product Certificates 25 1 IECEx Product Certificate ...
Страница 69: ...D Guard2 66 ...
Страница 70: ...D Guard2 67 ...
Страница 71: ...D Guard2 68 ...
Страница 72: ...D Guard2 69 25 2 ATEX Product Certificate ...
Страница 73: ...D Guard2 70 ...
Страница 74: ...D Guard2 71 ...
Страница 75: ...D Guard2 72 ...
Страница 76: ...D Guard2 73 26 APPENDIX I Product Dimensions ...
Страница 77: ...D Guard2 74 Doc_Rev 03 12 15 ...