Due
to
incorrect
adjustments
energy
saving
operation may not be observed and the whole
system or some parts of the units may be damaged.
Manufacturer cannot be held liable for malfunctions
and damages resulting from incorrect settings
made by unauthorized persons.
7.1
END USER PARAMETERS
7
PARAMETERS
Parameters of
WALLCON X-treme
boilers are divided into 4
groups according to their level:
END USER PARAMETERS
COMMISSIONING
ENGINEER
OEM
31
MENU
LINE NO
OPERATING LINE
UNIT
MIN.
MAX.
FACTORY SETTINGS
1
Hours / Minutes
hh:mm
00:00
23:59
--.--
2
Day / Month
tt:MM
1.01.
31.12.
--.--
3
Year
jjjj
2004
2099
--.--
29
Birimler
-
˚C, bar
500
Preselection
-
Mo-Su
501
Mo-Su: 1. Phase On
hh:mm
00:00
24:00
06:00
502
Mo-Su: 1. Phase Off
hh:mm
00:00
24:00
22:00
503
Mo-Su: 2. Phase On
hh:mm
00:00
24:00
--:--
504
Mo-Su: 2. Phase Off
hh:mm
00:00
24:00
--:--
505
Mo-Su: 3. Phase On
hh:mm
00:00
24:00
--:--
506
Mo-Su: 3. Phase Off
hh:mm
00:00
24:00
--:--
516
Default values
-
No
520
Preselection
-
Mo-Su
521
Mo-Su: 1. Phase On
hh:mm
00:00
24:00
06:00
522
Mo-Su: 1. Phase Off
hh:mm
00:00
24:00
22:00
523
Mo-Su: 2. Phase On
hh:mm
00:00
24:00
--:--
524
Mo-Su: 2. Phase Off
hh:mm
00:00
24:00
--:--
525
Mo-Su: 3. Phase On
hh:mm
00:00
24:00
--:--
526
Mo-Su: 3. Phase Off
hh:mm
00:00
24:00
--:--
536
Default values
-
No
560
Preselection
-
Mo-Su
561
Mo-Su: 1. Phase On
hh:mm
00:00
24:00
06:00
562
Mo-Su: 1. Phase Off
hh:mm
00:00
24:00
22:00
563
Mo-Su: 2. Phase On
hh:mm
00:00
24:00
--:--
564
Mo-Su: 2. Phase Off
hh:mm
00:00
24:00
--:--
565
Mo-Su: 3. Phase On
hh:mm
00:00
24:00
--:--
566
Mo-Su: 3. Phase Off
hh:mm
00:00
24:00
--:--
576
Default values
-
No
641
Preselection
-
Period 1
642
Period Start Day / Month
tt.MM
01.01
31.12
--:--
643
Periode End Day / Month
tt.MM
01.01
31.12
--:--
648
Operating level
-
Frost protection
651
Preselection
-
Period 1
652
Period Start Day / Month
tt.MM
01.01
31.12
--:--
653
Periode End Day / Month
tt.MM
01.01
31.12
--:--
658
Operating level
-
Frost protection
661
Preselection
-
Period 1
662
Period Start Day / Month
tt.MM
01.01
31.12
--:--
663
Periode End Day / Month
tt.MM
01.01
31.12
--:--
668
Operating level
-
Frost protection
710
Comfort setpoint
°C
Value from Line no. 712
35
20
712
Reduced setpoint
°C
4
Value from Line no. 710
16
714
Frost protection setpoint
°C
4
Value from Line no. 712
10
720
Heating curve slope
-
0,1
4
1,5
730
Summer/winter heating limit
°C
---/8
30
20
1010
Comfort setpoint
°C
Value from Line no. 1012
35
20
1012
Reduced setpoint
°C
4
Value from Line no. 1010
16
1014
Frost protection setpoint
°C
4
Value from Line no. 1012
4
1020
Heating curve slope
-
0,1
4
1,5
1030
Summer/winter heating limit
°C
---/8
30
20
1600
DHW operating mode
-
On
1610
Nominal setpoint
˚
C
Value from Line no. 1612
Value from Line no. 1614
55
1612
Reduced setpoint
˚
C
8
Value from Line no. 1610
40
2055
Pool setpoint solar heating
°C
8
80
26
2056
Pool sepoint boiler heating
°C
8
80
22
Boiler
2214
Setpoint manual control
°C
10
90
80
6705
SW Diagnose Code
-
-
-
Indication only
6706
Burner ctrl phase lockout pos
-
-
-
Indication only
Fault
Holidays
HC2
(When activated)
Period 1, 2, 3, 4, 5, 6, 7, 8
Frost protection, Reduced
Holidays
HC3
(When activated)
Period 1, 2, 3, 4, 5, 6, 7, 8
Frost protection, Reduced
HC1
HC2
(When activated)
DHW
On, Off, Eco
Swimming pool
Holidays
HC1
Period 1, 2, 3, 4, 5, 6, 7, 8
Frost protection, Reduced
Time program 4/DHW
Mo-Su, Mo-Fr, Sa-Su, Mo,Tu,We,Th,Fr,Sa,Su
Yes, No
English
˚
C, bar,˚F, PSI
Time program
HC 1
Mo-Su, Mo-Fr, Sa-Su, Mo,Tu,We,Th,Fr,Sa,Su
Yes, No
Time program
HC 2
(When activated)
Mo-Su, Mo-Fr, Sa-Su, Mo,Tu,We,Th,Fr,Sa,Su
Yes, No
Time of day and date
Operator section
20
Language
-
English, Deutsch, Francais, Italiano, Dansk,
Nederlands, Español, Česky, Slovenský, Türkçe
Содержание Wallcon X-treme 67
Страница 19: ...18...
Страница 20: ...19...
Страница 21: ...20...
Страница 22: ...21 OCI 351 Modbus Module...
Страница 31: ...6 5 MAIN FUNCTIONS 30...
Страница 41: ...16 TROUBLESHOOTING 40 16 TROUBLE SHOOT NG...
Страница 42: ...41...