background image

Due

to

incorrect

adjustments

energy

saving

operation may not be observed and the whole
system or some parts of the units may be damaged.

Manufacturer cannot be held liable for malfunctions
and damages resulting from incorrect settings
made by unauthorized persons.

7.1

END USER PARAMETERS

7

PARAMETERS

Parameters of

WALLCON X-treme

boilers are divided into 4

groups according to their level:

END USER PARAMETERS

COMMISSIONING

ENGINEER

OEM

31

MENU

LINE NO

OPERATING LINE

UNIT

MIN.

MAX.

FACTORY SETTINGS

1

Hours / Minutes

hh:mm

00:00

23:59

--.--

2

Day / Month

tt:MM

1.01.

31.12.

--.--

3

Year

jjjj

2004

2099

--.--

29

Birimler

-

˚C, bar

500

Preselection

-

Mo-Su

501

Mo-Su: 1. Phase On

hh:mm

00:00

24:00

06:00

502

Mo-Su: 1. Phase Off

hh:mm

00:00

24:00

22:00

503

Mo-Su: 2. Phase On

hh:mm

00:00

24:00

--:--

504

Mo-Su: 2. Phase Off

hh:mm

00:00

24:00

--:--

505

Mo-Su: 3. Phase On

hh:mm

00:00

24:00

--:--

506

Mo-Su: 3. Phase Off

hh:mm

00:00

24:00

--:--

516

Default values

-

No 

520

Preselection

-

Mo-Su

521

Mo-Su: 1. Phase On

hh:mm

00:00

24:00

06:00

522

Mo-Su: 1. Phase Off

hh:mm

00:00

24:00

22:00

523

Mo-Su: 2. Phase On

hh:mm

00:00

24:00

--:--

524

Mo-Su: 2. Phase Off

hh:mm

00:00

24:00

--:--

525

Mo-Su: 3. Phase On

hh:mm

00:00

24:00

--:--

526

Mo-Su: 3. Phase Off

hh:mm

00:00

24:00

--:--

536

Default values

-

No 

560

Preselection

-

Mo-Su

561

Mo-Su: 1. Phase On

hh:mm

00:00

24:00

06:00

562

Mo-Su: 1. Phase Off

hh:mm

00:00

24:00

22:00

563

Mo-Su: 2. Phase On

hh:mm

00:00

24:00

--:--

564

Mo-Su: 2. Phase Off

hh:mm

00:00

24:00

--:--

565

Mo-Su: 3. Phase On

hh:mm

00:00

24:00

--:--

566

Mo-Su: 3. Phase Off

hh:mm

00:00

24:00

--:--

576

Default values

-

No 

641

Preselection

-

Period 1

642

Period Start Day / Month

tt.MM

01.01

31.12

--:--

643

Periode End Day / Month

tt.MM

01.01

31.12

--:--

648

Operating level

-

Frost protection

651

Preselection

-

Period 1

652

Period Start Day / Month

tt.MM

01.01

31.12

--:--

653

Periode End Day / Month

tt.MM

01.01

31.12

--:--

658

Operating level

-

Frost protection

661

Preselection

-

Period 1

662

Period Start Day / Month

tt.MM

01.01

31.12

--:--

663

Periode End Day / Month

tt.MM

01.01

31.12

--:--

668

Operating level

-

Frost protection

710

Comfort setpoint

°C

Value from Line no. 712

35

20

712

Reduced setpoint

°C

4

Value from Line no. 710

16

714

Frost protection setpoint

°C

4

Value from Line no. 712

10

720

Heating curve slope

-

0,1

4

1,5

730

Summer/winter heating limit

°C

---/8

30

20

1010

Comfort setpoint

°C

Value from Line no. 1012

35

20

1012

Reduced setpoint

°C

4

Value from Line no. 1010

16

1014

Frost protection setpoint

°C

4

Value from Line no. 1012

4

1020

Heating curve slope

-

0,1

4

1,5

1030

Summer/winter heating limit

°C

---/8

30

20

1600

DHW operating mode

-

On

1610

Nominal setpoint

˚

C

Value from Line no. 1612

Value from Line no. 1614

55

1612

Reduced setpoint

˚

C

8

Value from Line no. 1610

40

2055

Pool setpoint solar heating

°C

8

80

26

2056

Pool sepoint boiler heating

°C

8

80

22

Boiler

2214

Setpoint manual control

°C

10

90

80

6705

SW Diagnose Code

-

-

-

Indication only

6706

Burner ctrl phase lockout pos

-

-

-

Indication only

Fault

Holidays                                                                                         
HC2                                                                                 
(When activated)                                                 

Period 1, 2, 3, 4, 5, 6, 7, 8

Frost protection, Reduced

Holidays                                                                                         
HC3                                                                                 
(When activated)                                                 

Period 1, 2, 3, 4, 5, 6, 7, 8

Frost protection, Reduced

HC1

HC2
(When activated)

DHW

On, Off, Eco

Swimming pool

Holidays                                                                                        
HC1                                                

Period 1, 2, 3, 4, 5, 6, 7, 8

Frost protection, Reduced

Time program 4/DHW

Mo-Su, Mo-Fr, Sa-Su, Mo,Tu,We,Th,Fr,Sa,Su

Yes, No

English

˚

C, bar,˚F, PSI

Time program                                 
HC 1                                                       

Mo-Su, Mo-Fr, Sa-Su, Mo,Tu,We,Th,Fr,Sa,Su

Yes, No

Time program                                 
HC 2                                                                     
(When activated)                               

Mo-Su, Mo-Fr, Sa-Su, Mo,Tu,We,Th,Fr,Sa,Su

Yes, No

Time of day and date

Operator section

20

Language

-

English, Deutsch, Francais, Italiano, Dansk, 

Nederlands, Español, Česky, Slovenský, Türkçe

Содержание Wallcon X-treme 67

Страница 1: ...INSTALLATION AND USER MANUAL WALL HUNG CONDENSING BOILERS EN 50 70 90 115 125 150 Wallcon X treme 42 Wallcon X treme 50 Wallcon X treme 67 WALLCON X treme...

Страница 2: ...ments 34 10 1 Emission Setpoints 34 10 2 Nominal Load Emission Settings 35 10 3 Minimum Load Emission Settings 35 11 LPG Conversion 36 12 Maintenance 37 12 1 Maintenance Process 37 13 Energy Saving Re...

Страница 3: ...quent repairs and modifications Boiler may not be used by persons with inadequate physical mental and perceptual capacity and without experience and knowledge 1 3 SAFETY INSTRUCTIONS IF GAS SMELLS Do...

Страница 4: ...and the power cut off DON T TOUCH THE BOILER WHEN YOUR HANDS ARE WET OR STEPPING ON A WET AREA 1 4 STANDARDS AND REGULATIONS This boiler is manufactured in accordance with the following directives an...

Страница 5: ...commercial or industrial purposes The manufacturer cannot be held responsible for the problems caused by the usege except of the design purpose WARRANTY PERIOD AND LIFE TIME Warranty is 2 years from...

Страница 6: ...below 0 C against the risk of freezing Read the FROST PROTECTION section WALLCON X treme condensing boilers must be installed in spaces that have the necessary ventilation openings according to curren...

Страница 7: ...by an authorized Gassero service The boiler must be located in a location that is separate from the living quarters and only in accordance with the ventilation legislation 2 6 INFORMATION LABEL 2 5 P...

Страница 8: ...REME 67 A 485mm 485mm 485mm B 490mm 490mm 490mm C 610mm 610mm 610mm D 3 4 3 4 3 4 D1 160mm 160mm 160mm D2 185mm 185mm 185mm E 1 1 1 E1 77mm 77mm 77mm E2 129mm 129mm 129mm F 1 1 1 F1 77mm 77mm 77mm F2...

Страница 9: ...21 Pressure Safety Valve 4 Heat Exchanger 13 Syphon 22 Drain Hose 5 Ignition Electrode 14 Syphon Sensor 23 Circulation Pump 6 Sight Glass 15 Water Outlet Connection 24 Air Pressure Switch 7 Ignition T...

Страница 10: ...Efficiency Qmin 80 60 C 97 04 97 82 96 86 97 58 97 99 98 80 Minimum Efficiency Qmin 50 30 C 105 63 104 94 105 76 104 37 107 08 106 35 Partial Load Return 30 C Direct Method Flue Gas Temperature 80 60...

Страница 11: ...ING Carry the boiler together at least two persons together by holding from the top and the bottom Do not carry or lift the boiler by holding the control panel After the boiler is removed from the box...

Страница 12: ...d by UNDERFLOOR HEATING SYSTEM PLATE HEAT EXCHANGER should be used and the system should be separated from each other as primary and secondary Faults that may arise if the water conditions are not in...

Страница 13: ...building s heat demand All necessary components must be installed and supplied correctly in the installation in a manner to perform their duty Protective and safety devices must be used in the heating...

Страница 14: ...ircuits are used to eliminate excessive pressure differences between boiler s inlet and outlet water temperatures and to prevent thermal stresses in the boiler Dimensions input and output distances sh...

Страница 15: ...the return line of the boiler When the dirt particles and similar deposits in the system water are not cleaned The efficiency of the system decreases Installation equipments pumps valves plate heat e...

Страница 16: ...the environment and throws flue gas to the outside C13 It is a flue system that takes the combustion air from the outside and throws flue gas to the outside with the horizontal concentric flue pipe s...

Страница 17: ...m 30 m Max output p 140 Pa 140 Pa 140 Pa Wallcon X Treme 67 C13 C33 C43 C53 C63 C83 Air inlet 125 mm 125 mm 80 mm Flue 80 mm 80 mm 80 mm Max length 21 m 21 m 21 m Max output p 300 Pa 300 Pa 300 Pa Wal...

Страница 18: ...intenance Electrical operations must be made by authorized technical personal in in accordance with regulations and standards Electrical cables should not be passed close to hot surfaces such as hot w...

Страница 19: ...18...

Страница 20: ...19...

Страница 21: ...20...

Страница 22: ...21 OCI 351 Modbus Module...

Страница 23: ...and vents Open the sensor housing cover by turning it counterclockwise to access the sensor connection terminal and the wall fixing holes Mark the fixing points on the wall and drill the wall using t...

Страница 24: ...ization tank should be used for condensate water occurring in systems with a total power o f 200 kW and above WATER SOFTENER UNIT HYDRAULIC SEPERATOR RADIATOR CIRCUIT Pump Expansion Tank Safety Valve...

Страница 25: ...W and above MECHANICAL SCHEME WITH HYDRAULIC SEPERATOR Installation of 2 WALLCON X treme CONDENSING BOILERS in cascade with 1 RADIATOR CIRCUIT 1 DHW CIR CUIT Pump Expansion Tank Safety Valve Air Seper...

Страница 26: ...r occurring in systems with a total power o f 200 kW and above Plate Heat Exchanger must be used in FLOOR HEATING SYSTEMS Pump Expansion Tank Safety Valve Air Seperator Deposit and Dirt Seperator Outd...

Страница 27: ...enance etc must be performed by authorized personnel Improper interventions may cause loss of life and property increased fuel consumption and deterioration in safe and comfortable operation Manufactu...

Страница 28: ...dby mode pumps will be energised periodically mixing valves ran into middle position This function will be turned off automatically after the cycle FLUE FUNCTION E Used for flue gas emission measuring...

Страница 29: ...perature limit for the room temperature When the room temperature falls below the set temperature the boiler will be activated and keep the room temperature constant Factory setting is 10 C To adjust...

Страница 30: ...unit etc in the system all personalized settings parameters fault resets will be made via the control panel E g Date and time adjustment Push OK button Select Time of day and date then push OK button...

Страница 31: ...6 5 MAIN FUNCTIONS 30...

Страница 32: ...el Frost protection 651 Preselection Period 1 652 Period Start Day Month tt MM 01 01 31 12 653 Periode End Day Month tt MM 01 01 31 12 658 Operating level Frost protection 661 Preselection Period 1 66...

Страница 33: ...e 1 sensor error 177 Water pressure 2 too low 349 Buffer return valve Y15 not available 78 Water pressure sensor error 178 Limit thermostat heating circuit 1 350 Puffer address sensor 82 LPB address c...

Страница 34: ...ler works evenly ensuring high efficiency and long life time In cascade systems one of the boilers is used as MASTER LEADER others are used as SLAVES FOLLOWERS While all settings of the cascade system...

Страница 35: ...ever if there is a deviation in the values which are given below emission settings should be changed by GASSERO authorized service 10 COMBUSTION ADJUSTMENTS These combution settings mentioned below mu...

Страница 36: ...rement on a boiler operating at nominal capacity A To run the boiler at nominal load Press and hold Heating Mode button for 3 sec Controller Stop Function On will be mentioned on the screen Modulation...

Страница 37: ...NGS min maks min maks CO2 emission 9 54 11 36 9 57 11 47 Gas consumption m3 h 0 25 1 52 0 33 1 87 Gas Nozzle mm 5 5 5 5 G31 Wallcon X treme 50 Wallcon X treme 67 Seperate the air inlet pipe and the ve...

Страница 38: ...cleaned and replaced if necessary Control of the sensors can be done by checking the temperature resistance tables to detect that sensors are working properly Burner and Heat Exchanger will be cleane...

Страница 39: ...ing COMFORT and REDUCED TEMPERATURE values will save energy Excessively selected COMFORT temperature will increase the energy consumption To save more energy use REDUCED TEMPERATURE function more ofte...

Страница 40: ...2mg kWh 25mg kWh 21mg kWh Seasonal Space heating efficiency s 96 20 96 10 96 20 Annual energy consumption QHE 0 962 136GJ 176GJ Sound power level indoors LWA 109 8GJ 50 8dB 66dB A Condensing boiler 50...

Страница 41: ...16 TROUBLESHOOTING 40 16 TROUBLE SHOOT NG...

Страница 42: ...41...

Страница 43: ...l other equipments connections must not be reduced more than 2 calibers in accordence with KVS factor For each boiler it is mandatory to use an appropriate diameter filter and check valve on the retur...

Страница 44: ...ed MANUFACTURER Gassero Isi Teknolojileri Sanayi Limited Sirketi stanbul End stri ve Ticaret Serbest Bolgesi 4 Sokak No 8 34957 Tuzla Istanbul TURKEY Phone 90 216 394 09 85 86 87 Fax 90 216 394 24 91...

Отзывы: