MDE-4652F Atlas® 9800 Electronics Field Installation Instructions · September 2019
Page 13
Installing Atlas 9800 CPU Board (M06333KXXXX)
JP2 - Mode
This jumper selects the mode in which the pump/dispenser operates. Set the mode to “Online”
if the pump/dispenser communicates to a controlling system (for example, Gasboy TopKAT
PLUS or CFN PLUS System). Set the mode to “Standalone” for all other configurations [for
example, Gasboy Series 1000 Fuel Management System (FMS) or no controlling system].
Mode
JP2
Standalone Jumpered
Online
Open
JP3, JP4 - Leak Detect Delay
These jumpers select the delay time used by leak detectors in Submersible Turbine Pump
(STP) applications. The delay time is the period between the activation of the submersible
pump and the activation of the slow flow valve. The delay time must be set according to the
type of leak detector installed on the STP to allow for a normal leak test for each transaction.
The delay time must be set to 0 seconds for suction pumps.
Delay Time JP3
JP4
0 seconds
Jumpered
Jumpered
4 seconds
Jumpered
Open
5 seconds
Open
Jumpered
6 seconds
Open
Open
JP5 - Hose Pressurization
For US Gallons (always in Hose Pressurization mode), this jumper is ignored. This jumper is
used to determine if hose pressurization is used. If enabled, the slow flow valve is opened
before reset is complete, to allow the hose to be pressurized before fuel dispensing begins.
Pressurization JP5
Enabled
Jumpered
Disabled
Open
JP6 - Authorization
This jumper allows activation or non-activation of the pump/dispenser from an external source
(for example, an FMS). When jumpered, a 115/230 VAC signal must be present on the Control
Feed/authorization line (refer to the wiring diagram for your model pump/dispenser) for pump
activation to occur (required setting for Gasboy Series 1000). When open, the Control Feed
line signal is ignored (required setting for Standalone mode).
Authorization JP6
Enabled
Jumpered
Disabled
Open
Note: For JP6 Authorization, in Standalone mode, the authorization signal must be present to
activate the pump.